background image

46

XBOXER XBC 

ECOSMART (CO) MODELS

12.0 ELECTRICAL DETAILS

12.6 CONNECTION CHART

Description

Controller

Din Rail

Relay

Terminal No

Terminal No

DI

AI

Output

AO

Fresh Air Sensor

IN 1

1

Supply Air Sensor

IN2

1

Return/Room Air Sensor

IN3

25-26

1

Input 4

IN4

1

Input 5

IN5

31-32

1

Alarm Circuit 1 (Fan, Heater)

IN6

27-28 (Some Models)

1

Alarm Circuit 2 (Pump, Filter)

IN7

29-30

1

Volt-Free Enable Input Signal

IN8

33-34

1

Volt-Free Boost Input Signal

IN9

35-36

1

Extract Fan 0-10V

OUT1

1

Supply Fan 0-10V

OUT2

1

Heat Demand 0-10V

OUT3

1

Cool Demand 0-10V

OUT4

1

Bypass Damper Relay

OUT5

1

Volt-Free Healthy Relay

OUT6

1

Volt-Free Fan Run Relay

OUT7

1

Volt-Free Cool Demand Relay

OUT8

1

Volt-Free Heat Demand Relay

OUT9

1

230V Enable Input

10

1

230V Fan Boost Input

11

1

(MS/TP)

Содержание ecosmart CONNECT XBOXER XBC

Страница 1: ...r 671710 FOR THE COMPLETE VENTILATION SOLUTION M A D E I N T H E U K M A DE IN THE U K ErP COMPLIANT 2016 XBOXER XBC UNIT SIZES 10 65 WITH ECOSMART CONNECT CONTROL CO INSTALLATION CONTROL DETAILS OPER...

Страница 2: ...OPERATING MAINTENANCE INSTRUCTIONS 3 13 DESCRIPTION OF CONTROL SOFTWARE STRATEGY 15 44 ELECTRICAL DETAILS 45 47 HARDWARE POSITIONS ON THE UNIT 48 WIRING DIAGRAMS 49 61 MAINTENANCE SERVICE SCHEDULE 62...

Страница 3: ...ASSEMBLY 6 XBC UNIT DIMENSIONS 7 ATTENUATOR FLANGE CONNECTOR DIMENSIONS 8 ATTENUATOR DIMENSIONS 9 INSTALLING THE XBC FAN UNIT ATTENUATORS 10 INSTALLING THE XBC WEATHERPROOF ROOF ON ECOSMART CONNECT CO...

Страница 4: ...e Discharge Attenuator 1050 1250 1600 mm long optional Duct Connection Blanking Panel Access to Intake Filter Fan Condensate tray and Pump Attenuator Flange connector Attenuator Flange connector CODE...

Страница 5: ...mum of around 600mm clearance as stated in ADF 2010 is allowed 8 Where these arrangements are not suitable the Consultant s and Contractor s project specific requirements will always be accommodated w...

Страница 6: ...alled in accordance with good industry practice These units may only be mounted horizontally and must be fully levelled in the horizontal plane The units are heavy and should be mounted using the fixi...

Страница 7: ...hed to every unit Add 50mm to dimension A to include both flanges Type of heater battery 4 1 XBOXER XBC UNIT HANGING BRACKET POSITIONS C B A C 1 2 3 4 Unit code Dimensions to hole centres mm A B C XBC...

Страница 8: ...R XBC55 FLANGE CONNECTOR 11 INLET OUTLET 10 417 5 607 5 22 438 5 628 5 1067 472 430 11 450 M8 Inserts 10 XBC65 FLANGE CONNECTOR INLET OUTLET 10 290 5 551 5 22 311 5 572 5 884 402 360 11 380 0 M8 Inser...

Страница 9: ...E MS12 1250 280 365 66 XBC45 HS MS16 1600 525 365 114 XBC45 HE MS16 1600 280 365 81 XBC55 HS MS10 1050 580 435 79 XBC55 HE MS10 1050 410 435 62 XBC55 HS MS12 1250 580 435 101 XBC55 HE MS12 1250 410 43...

Страница 10: ...e length of the associated attenuators Installation of the XBOXER XBC units including all external services and controls should be installed in accordance with the appropriate site procedures and MUST...

Страница 11: ...to be removed if necessary WEATHERPROOF COMPONENTS Item Description Quantity A Roof Assembly 1 B Control Cover 1 C Fixing Channel 4 D Control Lid with Heater 1 OPTIONAL EXHAUST INTAKE TERMINALS Item D...

Страница 12: ...levels are kept to a minimum The motorised damper units will be supplied loose and are designed to fit directly onto the flange connector by others l Fully interlocking parallel blades half inch diame...

Страница 13: ...ss to the fan section is via lift off panels see figs 1 13 For non Ecosmart units wiring to the fan motor unit terminal box should be mechanically protected and in made in accordance with the details...

Страница 14: ...NCTIONS 15 18 EXPOSED BACNET OBJECT LIST BY CATEGORY 19 23 NETWORKING 24 BUS DEVICES 25 33 ROOM MODULE WIRING 34 ROOM MODULE DIMENSIONS 35 AVAILABLE ROOM MODULES 36 SENSOR ADDRESSING 37 CONNECTION AND...

Страница 15: ...er via a SA Sensor Actuator MS TP bus See NetworkAccessory section for more connection details 7 4 1 ROOM MODULE PIR When a Room Module PIR sensor is connected via the SA bus the control will automati...

Страница 16: ...0 to 100 C 0 10V Output Range 0 to 80 C 0 to 90 C 0 10V Pressure 0 10V is scaled as defined by 0 25Pa Sensor the network input 0 50Pa Pressure Sensor 0 100Pa 0 300Pa 0 500Pa 0 1000Pa 0 1600Pa 0 2500P...

Страница 17: ...nables Fan Boost mode l Heater Boost The heater function will be enabled Fan speeds will be increased where necessary to keep supply temp at the heater boost setpoint Default 35 C 7 7 1 FAN BOOST When...

Страница 18: ...k input Trickle Deadband 7 13 HIBERNATE This mode is available for LPHW and CW units where the valves are required to be driven open in anticipation of a period where the unit is electrically isolated...

Страница 19: ...ription Object Object ID DefaultValue Units Page Type 32 Enable Software enable switch MSV 10218 Off Off On 19 SL Enable The state of the enable input BI 10161 N A Off On 10 Run on Enable Run on timer...

Страница 20: ...us 15 RTC Min SupplyTemp Min supply temp when in RTC mode AV 10308 12 Degrees Celsius 7 15 EXPOSED BACNET OBJECT LIST BY CATEGORY FAN COMMISSIONING LCD Browser BACnet Object Description Oject Object I...

Страница 21: ...AV 14534 N A Degrees Celsius XBCTEMPERATURE SENSORS 1 SupplyAirTemp B The supply air temperature AI 10005 N A Degrees Celsius 1 FreshAirTemp H The fresh air temperature AI 10008 N A Degrees Celsius 1...

Страница 22: ...Seconds in a frost protection state 12 Frost Prot Temp Supply temperature at which frost AV 10275 4 Degrees Celsius protection becomes active HIBERNATE 32 Hibernate Mode Unit is ready for hibernation...

Страница 23: ...larm 38 Nor A Circ 1 For LCD Event Signal only MSV 17282 N A Normal Alarm 38 Ala Low SupplyTemp For LCD Event Signal only MSV 17285 N A Normal Alarm 38 Nor Low SupplyTemp For LCD Event Signal only MSV...

Страница 24: ...200 24 XBOXER XBC ECOSMART CO MODELS 8 0 NETWORKING Sensor Actuator SA bus Ethernet IP MSTP to IP Router Field Controller FC bus For best results use a linear network and switch on the EOL resistors a...

Страница 25: ...USB 2 0 Type B receptacle which is only used to obtain power from a computer or USB adapter A mains adapter and cable is supplied The router connects to the FC bus via screwed terminals AddressType De...

Страница 26: ...to the previous section Home Shortcut to the configured Home Page Back Moves to the previous page in the same section Forward Moves to the next page in the same section Enter Applies changes Device Na...

Страница 27: ...9 5 1 SETTING UPATARGET OBJECT Target objects allow the user to view a target device and object within the entire network To choose a target object l Navigate to the settings page l Select the right...

Страница 28: ...To add or remove favourites l Navigate to the settings page l Select the right arrow six times to reach theView Config screen l Select the function tickbox and favourite star l Select the home icon l...

Страница 29: ...et page When the home page is set to target 9 5 3 2TO SETA SERVICE PASSWORD l Navigate to the settings page l Select the right arrow twice to reach the display settings screen l Change the service pas...

Страница 30: ...ing the delete icon If all events are deleted alarm states can still be checked by navigating to the BACnet alarm objects via the network browser page See the BACnet alarm list for alarm objects The L...

Страница 31: ...cut button Service Password Password required to enter settings page 0 User Password Password Required to change locked values 0 All values are locked by default Stand By It defines the behaviour of t...

Страница 32: ...unches a Network Discovery function The purpose of this function is to find other BACnet devices residing on the same MS TP trunk The maximum number of devices supported by the FAD discovery function...

Страница 33: ...o permanently change the default display 1 If the display backlight is off press and release the push button to illuminate the backlight If the display backlight is already on proceed to Step 2 2 Pres...

Страница 34: ...Bus Screw Terminal Block Network Sensor Bus Com SA SA SA Power from Controller 15 VDC COM SA PWR Standard SensorWiring CO2 SensorWiring SA Bus 24V Brown Grey Screw Terminal Block Network Sensor Bus Co...

Страница 35: ...35 nuaire co uk 10 0 SA BUS DEVICES XBOXER XBC ECOSMART CO MODELS 80 80 35 120 80 35 10 5 DIMENSIONS ROOM MODULES MM Figure 28 30 11 15 Leaflet Number 671710...

Страница 36: ...TDFS 80x80 YES YES YES YES 199 Max of 1 Per fixed per Controller controller ESCO TS 80x80 YES 200 203 ESCO THS 80x80 YES YES 200 203 ESCO TDS 80x80 YES YES 200 203 ESCO TDHS 80x80 YES YES YES 200 203...

Страница 37: ...FF 201 OFF ON 202 ON OFF 203 ON ON 212 219Address Switch Settings Address Switch Settings Switch 4 Switch 2 Switch 1 212 OFF OFF OFF 213 OFF OFF ON 214 OFF ON OFF 215 OFF ON ON Not supported ON ANY AN...

Страница 38: ...ther by modular RJ12 connections or by screwed terminals using plain ended cable All sensors are fitted with both 8 2 3 1 MODULAR CABLE UPTO 30METRES The Room Modules can connect using a 24AWG twisted...

Страница 39: ...he following cable is recommended ESCO MSTPC30M Ecosmart Connect MSTP cable reel 30m ESCO MSTPC150M Ecosmart Connect MSTP cable reel 150m Note On the SA Bus the and wire are one twisted pair and the C...

Страница 40: ...ss 215 AI 10146 Parts Per Million N A 6 RM212Temp The temperature at RM address 212 AI 10149 Degrees Celsius N A 6 RM213Temp The temperature at RM address 213 AI 10152 Degrees Celsius N A 6 RM214Temp...

Страница 41: ...oint AV 10309 Degrees Celsius 22 15 STC H C Pref STC Heat Cool Pref AV 10310 No units 50 16 STC HX Efficiency STC HX Efficiency AV 10311 No units 0 8 16 Supply Fan Max Individual fan maximum speed set...

Страница 42: ...otification Notification N A 25 Time Schedule LocalTime Schedule SCH 10496 N A 25 PurgeTime Schedule PurgeTime Schedule SCH 10499 N A 25 Night C Sample Daytime schedule for winter or summer SCH 15875...

Страница 43: ...sor operation MSV 10213 AverageValue MaxValue Average Value 31 SetPoint Op Setpoint operation MSV 10214 LastValue Changed LastValue Software Only Changed 31 T Sens Op Temperature sensor operation MSV...

Страница 44: ...11 Normal Alarm N A 37 High SA TAlarm High SupplyAirAlarm MSV 17012 Normal Alarm N A 37 FrostAlarm FrostAlarm MSV 17013 Normal Alarm N A 37 Ala Acir 1 For LCD Event Signal Only MSV 17281 Normal Alarm...

Страница 45: ...d 12 3 SWITCHED LIVE Switch Live SL terminal A signal of 100 230V a c will activate the switched live signal Switch Live 2 SL2 terminal A signal of 100 230V a c will activate the switched live 2 Fan B...

Страница 46: ...rcuit 1 Fan Heater IN6 27 28 Some Models 1 Alarm Circuit 2 Pump Filter IN7 29 30 1 Volt Free Enable Input Signal IN8 33 34 1 Volt Free Boost Input Signal IN9 35 36 1 Extract Fan 0 10V OUT1 1 Supply Fa...

Страница 47: ...d conductors are simply pushed in until they hit the backstop No tool required TERMINATION OF FINE STRANDED CONDUCTORS Open the clamp by inserting an operating tool as shown below until it clicks into...

Страница 48: ...fan drive health B Delivery air temperature sensor C Extract air temperature sensor D Re heater trip electric heater models only E LPHW re heat drive LPHW models only F Bypass damper drive G Condensa...

Страница 49: ...49 nuaire co uk 30 11 15 Leaflet Number 671710 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 2 I O DAMPER CONNECTION 24VACTUATORVERSION XBC15 MD CO Figure 33...

Страница 50: ...029 2085 8200 50 XBOXER XBC ECOSMART CO MODELS Figure 34 13 0 DIAGRAMS 13 3 BASIC CONNECTION DIAGRAM...

Страница 51: ...51 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...

Страница 52: ...029 2085 8200 52 XBOXER XBC ECOSMART CO MODELS Figure 35 13 0 DIAGRAMS 13 4 PHYSICAL LAYOUT...

Страница 53: ...53 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...

Страница 54: ...029 2085 8200 54 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 5 XBC10 15 NO HEATER LPHW Figure 36...

Страница 55: ...55 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...

Страница 56: ...029 2085 8200 56 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 6 XBC25 65 NO HEATER LPHW Figure 37...

Страница 57: ...57 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...

Страница 58: ...029 2085 8200 58 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 7 XBC10 15 ELECTRIC HEATERVERSION Figure 39...

Страница 59: ...59 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...

Страница 60: ...029 2085 8200 60 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 8 XBC25 65 ELECTRIC HEATERVERSION Figure 40...

Страница 61: ...61 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...

Страница 62: ...raps should be checked that they are fully primed and functioning Drain pans should be flushed out periodically to remove contamination and chemical treatments may be used to provide protection betwee...

Страница 63: ...or ropes must be arranged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants 4 0...

Страница 64: ...art of our policy of continuous product development Nuaire reserves the right to alter specifications without prior notice Telephone calls may be recorded for quality and training purposes FOR MORE IN...

Отзывы: