7.4.3 RM OCCUPANCY DISPLAY
If an RM sensor with occupancy display is connected, it will automatically
display the occupancy state as follows.
State
Description
RM Display
Occupied
An enable signal is present
i.e. Fans are running.
Unoccupied
No enable & no trickle.
i.e. Fans are stopped.
Standby
No enable signal but fans
are trickling
7.5 MULTIPLE SENSORS
Where multiple sensors are connected the following options are available.
Network Input Name
Options
Temp Sensor Operation
Room module average (Default)
Return Air only
Room Module & Return Air Average
Setpoint Operation
Last Value Changed (Default)
Software Setpoint Only (ignore
room module)
Humidity Sensor Operation
Average (Default)
Max
Ignore
CO2 Sensor Operation
Average (Default)
Max
Ignore
Pressure Sensor Operation
Average (Default)
Max
Ignore
7.6 AUXILIARY INPUTS 4 & 5 (0-10V INPUTS)
The function of IN4 & IN5 can be set by the network inputs IN4 Function &
IN5 Function. The available options are as follows.
Function
Description
Available Ranges
None
The signal is ignored
N/A
Fan Speed
A 0-10V input is used as a
Control
fan speed demand.
N/A
0V = Min Speed
10V = Max speed
EGG (Ecosmart
0-10V from the EGG PCB is
Gateway
Control used as a fan speed
N/A
Gadget)
demand. The optional EGG
PCB can be used for back-
wards compatibility with some
Ecosmart Classic sensors.
0-10V CO2
0-10V is scaled as defined
0-2,000ppm
Sensor
by the network input
0-4,000ppm
“CO2 0-10V Output Range”
0-5,000ppm
0-10,000ppm
0-20,000ppm
Function
Description
Available Ranges
0-10V
0-10V is scaled as defined by
0 to 50°C
Temperature
the network input
0 to 40°C
Sensor
“Temperature Sensor
0 to 100°C
0-10V Output Range”
0 to 80°C
0 to 90°C
0-10V Pressure
0-10V is scaled as defined by
0-25Pa
Sensor
the network input
0-50Pa
“Pressure Sensor”
0-100Pa
0-300Pa
0-500Pa
0-1000Pa
0-1600Pa
0-2500Pa
0-3000Pa
0-10V
0-10V is scaled to 0-100%
Humidity
humidity
0-100% only
Sensor
7.6.1 FAN SPEED CONTROL INPUT
Once assigned to either input 4 or 5, the 0-10V input is scaled to 0-100% fan
speed demand.
7.6.2 ECOSMART GATEWAY GADGET (EGG)
If an EGG PCB is installed on the system this will give an enable signal and also
a 0-10V fan speed demand. The EGG allows an existing NET sensor network to
give a fan speed demand to a controller.
7.6.3 CO2 CONTROL
When a CO2 sensor is assigned to the system and an enable signal is received,
ventilation will increase fans speeds to reduce CO2 concentration. The target
CO2 sensor setpoint can be changed as one of the commissioning setpoints.
Room Module CO2 sensors are detected automatically. 0-10V CO2 sensors
need to be assigned to input 4 or 5.
7.6.4 HUMIDITY CONTROL
When a humidity sensor is assigned to the system and an enable signal is
received, ventilation will increase fans speed to reduce humidity. The target
humidity setpoint setpoint can be changed as one of the commissioning
setpoints. Room Module humidity sensors are detected automatically. 0-10V
humidity sensors need to be assigned to input 4 or 5.
7.6.5 CONSTANT PRESSURE CONTROL
When a pressure sensor is assigned to the system and an enable signal is
received, ventilation will increase fans speeds to increase pressure to the target
setpoint.
The target pressure setpoint can be changed as one of the commissioning
setpoints. 0-10V pressure sensors need to be assigned to input 4 or 5. Room
Module pressure sensors are not available.
XBOXER XBC
ECOSMART (CO) MODELS
7.0 DESCRIPTION OF CONTROL SOFTWARE STRATEGY
(MS/TP)
Содержание ecosmart CONNECT XBOXER XBC
Страница 50: ...029 2085 8200 50 XBOXER XBC ECOSMART CO MODELS Figure 34 13 0 DIAGRAMS 13 3 BASIC CONNECTION DIAGRAM...
Страница 51: ...51 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 52: ...029 2085 8200 52 XBOXER XBC ECOSMART CO MODELS Figure 35 13 0 DIAGRAMS 13 4 PHYSICAL LAYOUT...
Страница 53: ...53 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 54: ...029 2085 8200 54 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 5 XBC10 15 NO HEATER LPHW Figure 36...
Страница 55: ...55 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 56: ...029 2085 8200 56 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 6 XBC25 65 NO HEATER LPHW Figure 37...
Страница 57: ...57 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 58: ...029 2085 8200 58 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 7 XBC10 15 ELECTRIC HEATERVERSION Figure 39...
Страница 59: ...59 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 60: ...029 2085 8200 60 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 8 XBC25 65 ELECTRIC HEATERVERSION Figure 40...
Страница 61: ...61 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...