029 2085 8200
62
Isolation - Before commencing work make sure that
the unit and Nuaire control are electrically isolated
from the mains supply.
XBOXER XBC
ECOSMART (CO) MODELS
14.0 MAINTENANCE
It is recommended that PPE is always used during the maintenance of Air
Handling Equipment – gloves, eye shields and respiratory mask.
In some Ecosmart units and in some third party controls, variable speed
drives (inverters) are used to provide fan speed control. After the fan is
isolated, allow at least 5 minutes for the capacitors in the inverter to
discharge before commencing any work on the unit.
14.1 DAMPERS
At regular intervals check that the blades move freely.
14.2 FILTERS (4 X G4 FITTED AS STANDARD)
Disposable filters should be changed when an appropriate
pressure drop is achieved.
14.3 HEATING COILS
Coils should have their finned surface examined for accumulation of dirt, lint
and biological contaminants or similar.
If necessary, wash down affected areas with a mild detergent solution and a
soft brush. Care should be taken not to damage the finned surface, and any
cleaning fluids should be rinsed away with water.
A compressed air line may be used to blow out any solids between fins. Do
not probe the coil fin block with metal objects as damage may cause leaks.
Drain lines should be checked to ensure that they are unobstructed and free
draining.
Drain pans should be flushed out periodically to remove contamination.
Note: The unit application may require particular attention to this item –
Check with Building Management personnel for details.
14.4 COUNTERFLOW PLATE HEAT EXCHANGER
The heat exchanger block is normally protected from dust and
contamination by upstream pre-filters. It is possible to clean the unit with
compressed air in the case of dust deposits or by spraying with a mild
detergent solution for grease deposits. Solvents, strong alkaline, acidic or any
products that may be aggressive to aluminium should not be used. Do not
use cleaning water over 50 deg C.
Drain lines should be checked to ensure that they are unobstructed and free
draining. Traps should be checked that they are fully primed and functioning.
Drain pans should be flushed out periodically to remove
contamination, and chemical treatments may be used to provide protection
between service visits.
Note: The unit application may require particular attention to this item –
Check with Building Management personnel for details.
14.5 FANS AND MOTORS
Fan bearings should be manually checked at regular intervals for condition.
Standard fan bearings are supplied as ‘sealed for life’ and have an anticipated
life of 40,000 hours.
Motors have an enclosed bearing housing and are pre-greased
for life.
Check all fixings are secure.
14.6 GENERAL
Inspect all internal and external surfaces to check for corrosion or peeling of
painted surfaces.
Thoroughly clean affected areas with a wire brush, apply a coat of zinc rich
primer or similar, and re-touch with suitable finishing paint. Ensure tightness
of all nuts, bolts, and fixings.
Check all components for general condition.
15.0 SERVICE SCHEDULE
Typical–will depend on site conditions.
6 MONTHS
12 MONTHS
G4 FILTERS
4
or
4
F7 FILTERS
4
DAMPERS
4
DAMPER ACTUATORS
4
VENT WATER COILS
4
COIL FINNED SURFACES
4
CHECK DRAIN LINES + DRIP TRAY
4
4
CLEAN DRAIN PANS
Building
Schedule ?
4
NUTS, BOLTS, FIXINGS SECURE
4
FAN BEARINGS
4
ELECTRIC HEATERS
4
ELECTRICAL WIRING
4
FAN IMPELLER
4
GENERAL
4
16.0 WARRANTY
5 year warranty on ECOSMART (CO) models for peace of mind.
The warranty starts from the day of delivery and includes parts and labour
for the first year.
The remaining period covers replacement parts only.
This warranty is void if the equipment is modified without authorisation, is
incorrectly applied, misused or not installed
commissioned and maintained in accordance with the details
contained in this manual and general good practice.
If control software is modified or removed
Nuaire will accept warranty on the hardware (unit) provided the replacement
does not control the unit beyond its specified limits (refer to Nuaire testing
standards and Application Guidance Notes document NA-QS-W029-3 which
can be found on our website
www.nuaire.co.uk
)
17.0 SPARES
Spare parts and replacement components, and general advice are available
from the Nuaire Ltd Service department.
TELEPHONE 029 2085 8400
FAX 029 2085 8444
Содержание ecosmart CONNECT XBOXER XBC
Страница 50: ...029 2085 8200 50 XBOXER XBC ECOSMART CO MODELS Figure 34 13 0 DIAGRAMS 13 3 BASIC CONNECTION DIAGRAM...
Страница 51: ...51 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 52: ...029 2085 8200 52 XBOXER XBC ECOSMART CO MODELS Figure 35 13 0 DIAGRAMS 13 4 PHYSICAL LAYOUT...
Страница 53: ...53 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 54: ...029 2085 8200 54 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 5 XBC10 15 NO HEATER LPHW Figure 36...
Страница 55: ...55 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 56: ...029 2085 8200 56 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 6 XBC25 65 NO HEATER LPHW Figure 37...
Страница 57: ...57 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 58: ...029 2085 8200 58 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 7 XBC10 15 ELECTRIC HEATERVERSION Figure 39...
Страница 59: ...59 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Страница 60: ...029 2085 8200 60 XBOXER XBC ECOSMART CO MODELS 13 0 DIAGRAMS 13 8 XBC25 65 ELECTRIC HEATERVERSION Figure 40...
Страница 61: ...61 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...