22. 04. 21. Document Number  671506

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BESPOKE BOXER

Installation Manual

4.1.3 BMS Differential Pressure Switch

An external power supply delivering 10-35 VDC with a minimum 
current capability of 40ma must be used to power the control loop in 
which the PDGAUGE2/BMS is connected. 

If the receiver requires a 1-5 volt input, insert a 250 ohm, 1/2 watt 
resistor in series with the current loop but in parallel with the receiver 
input (Figure 14). RL becomes the 250 ohm resistor and point X and Y 
are connected to the receiver input, point X being positive (+) and point 
Y negative (–) or ground.

 

14 

BMS Differential Pressure Switch Wiring

PDGAUGE2/BMS

POWER
SUPPLY
10-35 VDC

RECEIVER (RL)

NOTE: RECEIVER MAY BE IN SERIES WITH 

+ OR - LEG OF CONTROL LOOP

RL MAX = V

X

Y

-

+

-

+

PS

 - 10.0V

20 mA DC

MAXIMUM VALUE (1250)

Mandatory Customer Connection

Optional Customer Connection

Key:

4.1.4 Bulkhead Lights

Lights are designed for permanent connection to fixed wiring. This 
should be either a suitable lighting circuit (protected with a 5 or 6 Amp 
MCB or fuse) or a fused spur (with a 3 Amp fuse) via a fused connection 
unit. 

15 

Bulkhead Light Wiring

COM

1

2

EARTHING 

N

LOOP

L

L

N

EARTH
FROM
LIGHT

TO

INTERNAL

LIGHT 

Internal Factory Connection
Mandatory Customer Connection

E

Mains

230V

50Hz

Key:

4.1.5 Electric Heater Wiring

For models with electric heating, the heating circuit is powered by a 
higher current, 400Vac 50Hz 3 phase & Neutral supplies. This must be 
isolated to the unit and fitted with appropriate overcurrent protection. 
The main supply is still required. Electric heater elements are protected 
by a fail-safe over-temperature switch which will disconnect the heater 
supply if a temperature of 80°C is reached. Once the elements cool, the 
switch will reset but a power cycle is required to reset the heater supply 
contactor. 

 

16 

Typical Electric Heater Wiring

E

1

2

3

N

AIR-FLOW PROVING SWITCH

PIPED TO OUTSIDE

Internal Factory Connection

Mandatory Customer Connection

BR

O

W

N

G

REY

BL

UE

L1

L2

L3

STAR POINT 

NO NEUTRAL CONNECTED

2A

2

1

3

4

5

6

N

L

C1

MANUAL RESET

OVER-HEAT

CUT-OUT

L1 L2 L3

AUTO RESET

OVER-HEAT

CUT-OUT

3

5

1

2

6

4

PUSH

TO RESET

HEATER

E

EARTH BOLT

BL

AC

K

BR

O

W

N

BROWN

0-

10

V

0V

REMOTE 

START 

SIGNAL

FUSED 400V 

POWER SUPPLY 

FROM LOCAL ISOLATOR

SCREENED 

TEMPERATURE 

CONTROL INPUT

HEATER TRIPPED 

VOLT-FREE SIGNAL

CLOSED = HEALTHY 

OPEN = TRIPPED

1 2 3 4

L1 LO

AD

1

L2

L3

/L

O

AD

3

LO

AD

2

TH

Key:

4.1.6 Thermal Wheel

The thermal wheel incorporates a purge section and is fitted with a  
rotational drive. Any temperature sensors and enabling signal are to be 
provided by others.

A frequency converter with a modular design is used as the control 
unit; it can adjust the speed of three-phase motors. The control unit is 
delivered ready for operation with the factory-set parameters. Various 
settings can be changed with an optionally available operating unit. 
Error messages can be read out directly at a flashing LED.

The power unit is protected from under voltage, over voltage or  
non-approved converter temperature.

Recommended tightening torque on terminals 0.5 Nm; maximum 
tightening torque 0.8 Nm.

MicroMax370

Output  

Motor 

Side

Maximum motor power

kW

0.37

Nominal output current

A

1.9

Maximum output voltage

V

3 x 0-230

Output frequency

Hz

(Fixed)4...40-100/150

Mains  

Input

Rated voltage

V

1x230-240 +/-15%

Mains frequency

Hz

50/60

Fuses

A T

10

General  

Data

Protection rating

IP54

Ambient temperature

°C

-20…45

Air humidity

kg

1.1

Dimensions

H x W x D

mm

198 x 164 x 60

Содержание BESPOKE BOXER

Страница 1: ...uipment will contain sharp edges on the internal and external surfaces Care should be taken to ensure that all personnel are aware of this and precautions are implemented to ensure no wounding is caus...

Страница 2: ...vant protective equipment and attire is worn by each relevant member of staff That the unit Nuaire have supplied meets the standards written in the technical specification The necessary lifting gear a...

Страница 3: ...a flattening or settlement of the shaft in the bearing housing The conditions above will apply and any deviation from them could nullify the warranty 2 2 Handling Of Equipment The images in Figure 1 s...

Страница 4: ...sms may also have to be adjusted Nuaire cannot be held responsible for the units failing a site leakage test if the above have not been carried out correctly 3 3 Modular Unit Section Joints All sectio...

Страница 5: ...ess pumped If a frost coil is not fitted then appropriate control methods must be taken to prevent the coils filters and other equipment from freezing by others 3 6 3 Pipework Care should be taken to...

Страница 6: ...and number of transit brackets varies by unit Check the unit drawing for the location and number of blowers Before use ensure the transit brackets have been removed from each blower within the unit Fi...

Страница 7: ...ssignment KL1 1 L1 Mains supply connection supply voltage 3 380 480 VAC 50 60 Hz KL1 2 L2 Mains supply connection supply voltage 3 380 480 VAC 50 60 Hz KL1 3 L3 Mains supply connection supply voltage...

Страница 8: ...ver temperature switch which will disconnect the heater supply if a temperature of 80 C is reached Once the elements cool the switch will reset but a power cycle is required to reset the heater supply...

Страница 9: ...rrect direction The electrical current being drawn by motors should not exceed the manufacturers recommendations specified on the motor plate If the current exceeds this check the fan volume flow rate...

Страница 10: ...he suction header connection and the equalising line The recommendations of the TE valve manufacturer should be referred to when locating the phial and adjusting the superheat In all cases settings sh...

Страница 11: ...ear warranty starts from the day of delivery and includes parts and labour for the first year This warranty is void if the equipment is modified without authorisation is incorrectly applied misused di...

Страница 12: ...al and horizontal position if needed Check that motor bracket is in 20 45 angle from horizontal line 9 Plate Heat Exchanger General inspection Check the damper performance 3 Clean the heat exchanger u...

Страница 13: ...her and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature...

Страница 14: ...14 22 04 21 Document Number 671506 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BESPOKE BOXER Installation Manual NOTES...

Страница 15: ...15 22 04 21 Document Number 671506 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BESPOKE BOXER Installation Manual NOTES...

Страница 16: ...16 22 04 21 Document Number 671506 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BESPOKE BOXER Installation Manual NOTES...

Отзывы: