22. 04. 21. Document Number  671506

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BESPOKE BOXER

Installation Manual

Units With Weatherproof Roofs

Above Left: Horizontal unit with weather kit.

Above Right: Vertical (Stacked) unit with weather kit.

Below: Roof assembly detail. 

 

3.5 Thermal Wheel Transport Packing

Thermal wheel modules can be delivered with transport packing blocks, 
ensure any transport blocks are removed prior to operation of the 
thermal wheel. 

The thermal wheel belt is unhooked to prevent the thermal wheel belt 
from stretching during transportation. 

The thermal wheel motor is attached via a hanging motor bracket. To 
install the belt lift the spring motor upwards, hook the belt onto the 
pulley and slowly release the motor. 

Ensure that the rotation sensor is aligned with the sensing studs, 
as this can become misaligned during transport/installation thus 
causing a fault signal.

3.6 Connections

3.6.1 Ductwork

Nuaire do not provide ductwork connections with units, instead 
the open ended framework should be utilised. Spigots are available 
as an option; refer to technical documents for information relating 
specifically to the manufactured unit.

3.6.2 Coils

When connecting coils, special care is needed to allow for expansion 
and contractions. Prior to any equalising connection, ensure that the 
thermostatic expansion valve for the DX coil is securely fitted.

Each coil section should be trapped and special care should be taken to 
ensure that there are no vertical rising condense lines, unless pumped.

If a frost coil is not fitted then appropriate control methods must 
be taken to prevent the coils, filters and other equipment from 
freezing (by others).

3.6.3 Pipework

Care should be taken to ensure that all pipework is adequately 
supported, therefore ensuring that no additional weight is added to the 
unit. Extra precaution should be taken to prevent pipe damage on site, 
as the fragile pipework will protrude from the side of the unit.

3.6.4 Condensate Drains

Modules that incorporate heat recovery, cooling coils or humidifiers 
may produce condensation during use. An insulated drip tray and drain 
connection is provided, and should be connected to a suitable drainage 
point.

Where plate heat exchangers are in use, condensate drainage points are 
provided. It is the installers’ responsibility to ensure connection to the 
appropriate trap and drainage. Due to the bespoke nature of these units 
condensate connection locations can vary during the design process 
and should be confirmed on an individual basis.

Horizontal plate heat exchangers have 2x 22mm drain connections. 
Connections are typically located on the underside of the PHX module 
at the extract inlet and extract outlet (Figure 5).

Vertical plate heat exchangers have 2x 22mm drain connections. 
Connections are typically located at the bottom of the access side of 
the PHX module (Figure 6).

Provision may be required, and if so, should be made, for the fitting of a 
correctly sized cleanable trap to each drain connection.

 

Condensate Connections For Horizontal Units With PHX

jjjj

Side View

End View

1x 22mm Condensate Connection

1x 22mm Condensate Connection

Condensate Connections For Vertical Units With PHX

2 x 22mm Condensate Connections

Access Side View

Содержание BESPOKE BOXER

Страница 1: ...uipment will contain sharp edges on the internal and external surfaces Care should be taken to ensure that all personnel are aware of this and precautions are implemented to ensure no wounding is caus...

Страница 2: ...vant protective equipment and attire is worn by each relevant member of staff That the unit Nuaire have supplied meets the standards written in the technical specification The necessary lifting gear a...

Страница 3: ...a flattening or settlement of the shaft in the bearing housing The conditions above will apply and any deviation from them could nullify the warranty 2 2 Handling Of Equipment The images in Figure 1 s...

Страница 4: ...sms may also have to be adjusted Nuaire cannot be held responsible for the units failing a site leakage test if the above have not been carried out correctly 3 3 Modular Unit Section Joints All sectio...

Страница 5: ...ess pumped If a frost coil is not fitted then appropriate control methods must be taken to prevent the coils filters and other equipment from freezing by others 3 6 3 Pipework Care should be taken to...

Страница 6: ...and number of transit brackets varies by unit Check the unit drawing for the location and number of blowers Before use ensure the transit brackets have been removed from each blower within the unit Fi...

Страница 7: ...ssignment KL1 1 L1 Mains supply connection supply voltage 3 380 480 VAC 50 60 Hz KL1 2 L2 Mains supply connection supply voltage 3 380 480 VAC 50 60 Hz KL1 3 L3 Mains supply connection supply voltage...

Страница 8: ...ver temperature switch which will disconnect the heater supply if a temperature of 80 C is reached Once the elements cool the switch will reset but a power cycle is required to reset the heater supply...

Страница 9: ...rrect direction The electrical current being drawn by motors should not exceed the manufacturers recommendations specified on the motor plate If the current exceeds this check the fan volume flow rate...

Страница 10: ...he suction header connection and the equalising line The recommendations of the TE valve manufacturer should be referred to when locating the phial and adjusting the superheat In all cases settings sh...

Страница 11: ...ear warranty starts from the day of delivery and includes parts and labour for the first year This warranty is void if the equipment is modified without authorisation is incorrectly applied misused di...

Страница 12: ...al and horizontal position if needed Check that motor bracket is in 20 45 angle from horizontal line 9 Plate Heat Exchanger General inspection Check the damper performance 3 Clean the heat exchanger u...

Страница 13: ...her and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature...

Страница 14: ...14 22 04 21 Document Number 671506 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BESPOKE BOXER Installation Manual NOTES...

Страница 15: ...15 22 04 21 Document Number 671506 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BESPOKE BOXER Installation Manual NOTES...

Страница 16: ...16 22 04 21 Document Number 671506 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BESPOKE BOXER Installation Manual NOTES...

Отзывы: