22. 04. 21. Document Number  671506

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BESPOKE BOXER

Installation Manual

Under Negative Pressure

If the condensate tray is located at the inlet side of the fan (i.e. under 
negative pressure) then calculate the values of A & B as shown below 
(Figure 7).

10Pa = 1mm H2O

A = Fan inlet pressure (mm H2O) +25mm (minimum). Allow 100mm 
for these units if pressure is unknown.

B = A/2 (minimum).

Under Positive Pressure

If the condensate tray is located at the outlet side of the fan (i.e. under 
positive pressure) then calculate the values of A & B as shown below 
(Figure 7).

A = 25mm (minimum).

B = Fan outlet pressure (mm H2O) + 25mm (minimum). 
Allow 100mm for these units if pressure is unknown.

Condensate Trap Dimensions

Hand tight plug 

B

A

condensate

From 

drain pan 

Hand tight plug 

Connect to 

ventilated 

downpipe 

to drain 

3.7 Fan Transit Brackets (AC Motors)

Transit brackets are factory fitted to prevent the blowers moving during 
transport and must be removed to prevent excessive vibration during 
operation. The specific location and number of transit brackets varies by 
unit. Check the unit drawing for the location and number of blowers.

Before use ensure the transit brackets have been removed from each 
blower within the unit (Figure 8). 

Loosen and remove the transit bracket bolt.

Remove the transit bracket away from the anti-vibration mount. 
Repeat for each bolt.

Store the transit brackets and bolts in a safe location if required for 
future use.

 

Transit Bracket

Transit 
Bracket 
Bolt

Fan Transit Brackets (AC Fans)

3.8 Filters

Filters will be provided in banks on suitable slide rails, so that they 
can be withdrawn. Magnehelic gauges are offered as standard unless 
otherwise instructed.

3.8.1 Spare Filters

If specified with order, spare sets of filters will be provided and should 
be stored in a clean, dry environment. Should you require spare filter 
media, please contact Nuaire.

3.8.2 Panel & Bag Filters with Side Withdrawal

Insert the filters by sliding them into the railing provided. If specified, 
blanking filters are fitted at the end of the railing. 
 
 
 

Side Withdrawal Filters

Capping strip

 

3.8.3 Panel & Bag Filters with Front Withdrawal

Insert filters squarely into the frames and retain using retaining P-clips.

10 

Front Withdrawal Panel Filters

11 

Front Withdrawal Bag Filters

Содержание BESPOKE BOXER

Страница 1: ...uipment will contain sharp edges on the internal and external surfaces Care should be taken to ensure that all personnel are aware of this and precautions are implemented to ensure no wounding is caus...

Страница 2: ...vant protective equipment and attire is worn by each relevant member of staff That the unit Nuaire have supplied meets the standards written in the technical specification The necessary lifting gear a...

Страница 3: ...a flattening or settlement of the shaft in the bearing housing The conditions above will apply and any deviation from them could nullify the warranty 2 2 Handling Of Equipment The images in Figure 1 s...

Страница 4: ...sms may also have to be adjusted Nuaire cannot be held responsible for the units failing a site leakage test if the above have not been carried out correctly 3 3 Modular Unit Section Joints All sectio...

Страница 5: ...ess pumped If a frost coil is not fitted then appropriate control methods must be taken to prevent the coils filters and other equipment from freezing by others 3 6 3 Pipework Care should be taken to...

Страница 6: ...and number of transit brackets varies by unit Check the unit drawing for the location and number of blowers Before use ensure the transit brackets have been removed from each blower within the unit Fi...

Страница 7: ...ssignment KL1 1 L1 Mains supply connection supply voltage 3 380 480 VAC 50 60 Hz KL1 2 L2 Mains supply connection supply voltage 3 380 480 VAC 50 60 Hz KL1 3 L3 Mains supply connection supply voltage...

Страница 8: ...ver temperature switch which will disconnect the heater supply if a temperature of 80 C is reached Once the elements cool the switch will reset but a power cycle is required to reset the heater supply...

Страница 9: ...rrect direction The electrical current being drawn by motors should not exceed the manufacturers recommendations specified on the motor plate If the current exceeds this check the fan volume flow rate...

Страница 10: ...he suction header connection and the equalising line The recommendations of the TE valve manufacturer should be referred to when locating the phial and adjusting the superheat In all cases settings sh...

Страница 11: ...ear warranty starts from the day of delivery and includes parts and labour for the first year This warranty is void if the equipment is modified without authorisation is incorrectly applied misused di...

Страница 12: ...al and horizontal position if needed Check that motor bracket is in 20 45 angle from horizontal line 9 Plate Heat Exchanger General inspection Check the damper performance 3 Clean the heat exchanger u...

Страница 13: ...her and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature...

Страница 14: ...14 22 04 21 Document Number 671506 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BESPOKE BOXER Installation Manual NOTES...

Страница 15: ...15 22 04 21 Document Number 671506 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BESPOKE BOXER Installation Manual NOTES...

Страница 16: ...16 22 04 21 Document Number 671506 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BESPOKE BOXER Installation Manual NOTES...

Отзывы: