background image

28 

e.

  Check that gas is flowing from the pilot during the ignition sequence. Clean or Replace as required. 

f.

  For the Remote Control Systems only, listen to the control to hear if the pilot gas solenoid is opening. Change the receiver, and the hand-

set at the same time and/or gas control. Refer to Section 22 for Cable connections diagram.  

      Also see Important Note at the beginning of this Section 20, concerning possibly returning parts as the cheaper option. 

 
20.3 - PILOT GOES OUT AFTER FIRST LIGHTING 

a.

  Check there is no debris blocking the flame to the thermocouple. 

b.

  Check there is nothing covering the terminal guard/flue on the outside. 

c.

  Check the thermocouple is in the correct position because although the fixing nut may seem tight and secure, the Thermocouple 

      may have slipped down. Slacken the fixing nut, reposition then retighten. With the Thermatronic System check all connections in 
      the Thermocouple circuit., from the valve, interrupter and wiring connections to the Receiver.  

d.

  If the Pilot Flame seems small the Injector may be slightly blocked, replace.  

e.

  For the Remote Control Systems only, listen to the control to hear if the pilot gas solenoid is opening.  

      Change the receiver and at the same time and/or the gas control. Refer to Diagram for Cable connections in Section 22. 

f.

  Also see Section 21.5. 

g.   

Specific to new installations and by far the highest cause of this type of fault. Typically the pilot and main burner lights  

      with the door open but goes out when the door is closed.  
      Possibly part or all of the cutting aid has been left in the flue after cutting.  

 
20.4 - PILOT LIGHTS BUT MAIN BURNER DOES NOT LIGHT 

a.

  With All Control Systems listen to hear if gas is flowing into the main burner. 

b. 

Check there is no dust or debris blocking the flame from the pilot to the main burner.   

c.

   With the 2 Remote Control Systems check that both Control Knobs are in the on position, fully turned anti clockwise.  

      Also check 

‘e’ 

before determining the action required.    

d. 

With the 2 Remote Control Systems check if the main control knob on the control is turning to the high setting and  

      listen to hear if the valve is opening. If not change the Handset & Switch (which ever applies) and at the same time the gas control.  
      For removal of the systems refer to the Diagram for Cable connections in Section 22.  
      Also check 

‘g’ 

(below) before considering replacing any parts. You should also consider the 

Important 

note in 21.1. 

e. 

With the 2 Button High Level Control it is possible for the Main Burner to light when first lit after lighting the Pilot but then the Push  

     Buttons do not operate the control. Operate the bottom button and listen to see if the Control Knob turns. If it does not then   
     change the batteries, if still a problem change the Switch Assembly as detailed in 

‘f’

.  

f. 

For removal/replacement of the 2 & 3 Button Switches first remove the 2 screws retaining the Switch Shield, remove the 2  

      screws retaining the Switch Assembly. Disconnect the push on wire connections at the control. Remove the switch and wires and  
      replace with a new component in reverse order.        

g. 

All Control Systems have a Pressure Test Point to allow the Burner Pressure to be checked to confirm if gas is flowing from the  

      control. On the Manual Control it is visible at the front left of the control. On the 2 Remote Control Controls it is the left pressure test point  
      facing the front. Ensure the pressure test point screw is fully closed after checking. 

h. 

Check if the main injector is blocked. Clean or Replace. 

i.

  Also see Section 21.3.g. 

 

20.5 - PILOT FLAME SHORTENS, OR GOES OUT WHEN MAIN BURNER IS SELECTED 

a.

   Monitor the supply pressure at the isolation elbow as the main burner lights. If pressure drops significantly, check gas pipe sizing and  

     quality of pipe bending. Check for debris in the gas supply and or gas filter if fitted. 

b.

   Check that another appliance is not affecting the gas supply pressure.  

c.   

Check the points raised in Sections 21.3 and 21.4.

 

 

 

 

20.6 - POOR FLAME PICTURE 

a.

  Check the supply pressure is correct at the isolation elbow. If the pressure is low, check gas pipe sizing, quality of pipe bending. Check for 

debris in the gas supply and or gas filter if fitted. 

b.

  All Control Systems have a pressure point to allow the Burner Pressure to be checked. On the Manual Control it is visible at the front left of 

      the control. On the 2 Remote Control Controls it is the left pressure test point facing the front. Ensure the pressure test point screw is fully  
      closed after checking. You may wish to check ‘c’ first. 

c.

  Check that another appliance is not affecting the gas supply pressure.  

d. 

Check that the Flue Terminal and Guard are not damaged or covered in any way. 

e.

  Check the Fuel bed layout is as detailed in Section 16. 

f.

  Check that none of the fuel cutting aid as not been accidently left in the flue.

 

g.  

Check that the flue pipe as not be forced into the flue spigot too far, (over 40mm) and past its stop blocking off the flue flow. 

 
20.7 - FIRE OPERATES FOR A WHILE THEN GOES OUT 

a.

  Check the supply pressure is correct at the isolation elbow with all other gas appliances working. If the pressure is low or fluctuating up 

and down check gas pipe sizing, quality of pipe bending. Check for debris in the gas supply, pilot pipe and or gas filter if fitted. 

b.

  Check the points raised in Sections 21.2 and 21.3.

 

c.

  For the Manual Control check that the Thermocouple Electrical Connections is tight and check the pilot flame size. 

d.

  For the 2 Remote Control Systems check that the Control is functioning correctly as detailed in Section 2.4 and also specifically check the  

      Thermocouple Electrical Connections and Pilot Flame size. 

e. 

Check that the Fuel Bed Matrix’s and the Rear Matrix Support are fitted correctly. 

f. 

Check that the Flue Terminal and Guard are not damaged or covered in any way. 

g.

  Also see Section 21.3.g. 

h. 

See 21.6 g. 

 

20.8 - THE RADIO FREQUENCY CONTROL SYSTEM DOES NOT OPERATE 

a.

  Check  the control is being correctly operated - see Section 2.4 

b.

  Check for error messages and check batteries - see Section 2.5 

c.

  Reset the Mertik Maxitrol Logic Circuits  - see Section 2.6 

 
 

Содержание Fenton Balanced Flue

Страница 1: ...be placed close to or on the fire We recommend that a Fireguard conforming to BS8423 should be used for protection of Young Children the Elderly Infirm and Pets ALL INSTRUCTIONS MUST BE LEFT WITH THE...

Страница 2: ...rmity 32 23 Diagram of Infrared Control System 33 Guarantee 34 BOX CONTENTS The Fire comes in a number of boxes Box 1 Large box contains the Fire the Matrix Tray chosen Control System plus Fitting Kit...

Страница 3: ...mm copper pipe gas supply to the burner via the isolation elbow 1 2 050mm length of 5mm x 4mm self adhesive silicone sealing strip for around the frame and base of the fire 1 1 820mm length of 5mm x 4...

Страница 4: ...no nearer than 300mm to an opening in the building fabric formed for the purpose of accommodating a built in element such as a window frame The reference to external corners does not apply to building...

Страница 5: ...a Safety Pressure Relief System and if the fires ignition should ever become delayed or noisy then the fire MUST NOT be used until checked by a Qualified Engineer Installer t In the event that the fi...

Страница 6: ...y law and CE approval Commands are accepted by the microprocessor when buttons are pressed An audible beep means that the command has been received and the push button should immediately be released t...

Страница 7: ...l Flame button to set the Minute Press Off or simply wait to return to the manual screen IMPORTANT For the following modes of controlling the fire automatically for Temperature or Timer Programs the F...

Страница 8: ...ty alkaline e To change the Handset battery slide open the plastic panel on the back of the Handset f To change the Receiver Batteries remove the Ash Pan Cover and locate the electronic receiver box u...

Страница 9: ...ners IMPORTANT NOTE The Fire MUST NEVER be used without the Glass Panel in place or if it is in any way damaged 4 SERVICING a The fire should be Serviced Annually in accordance with the Gas Safety Use...

Страница 10: ...to comply with the above could leave the Installer Liable to Prosecution and Invalidate the Warranty IMPORTANT BEFORE PROCEEDING WITH THE INSTALLATION READ THESE INSTRUCTIONS CAREFULLY THESE INSTRUCT...

Страница 11: ...he left of the centre of the fire and 39mm up from the base of the Fireplace Builders opening An isolation elbow is provided at the control inlet Your 8mm gas supply pipe needs to protrude through the...

Страница 12: ...Construction Shelf Details Sections 11 12 13 are for the various Installation Applications for Traditionally Built Houses Only one will apply For Timber Frame Houses refer to Section 13 IMPORTANT NOTE...

Страница 13: ...nd high humidity so it is very important that any rendering building work is allowed to thoroughly dry out before installation NOTE Take Care Not To Use Materials That Will Give Off An Odour When Hot...

Страница 14: ...E INTERNAL WALLS e g Timber Wood Stud With or Without a Standard Rebated Fire Surrounds Back Panel or Slips 700mm Min 300 mm Min Flue Hole 160mm Dia Plaster Board Cut Back 25mm Around Flue Hole 454mm...

Страница 15: ...t is very important that any rendering building work is allowed to thoroughly dry out before installation NOTE Take Care Not To Use Materials That Will Give Off An Odour When Hot As This Issue Is Know...

Страница 16: ...Installation d Installation MUST take account of the Outer Wall Cladding be it Brick or Weather Boards the latter being combustible will require different Installation Requirements We recommend seeki...

Страница 17: ...STIBLE MATERIALS AND SHELVES a A non combustible shelf can be fitted above the fire and should be positioned at least 95mm above the builders opening We recommend the depth of the shelf should be a ma...

Страница 18: ...terial from inside the Flue d With the flue at the correct length and when the fire is fitted there should be 130mm of Flue Terminal Outside The Wall and the screw holes for fixing the Wall Plate shou...

Страница 19: ...e drill the lower holes 27mm up from the base and drill the higher holes 510mm up from the base see Cable Fixing Diagrams on next page Secure the 4 Eyebolts supplied with the Rawl Plugs to the back of...

Страница 20: ...t the Burner Assembly and secure with 4 screws reposition the Thermatronic Receiver Box and Infrared Sensor or for High Level Control the Battery Box onto their Velcro Pads if applicable Reposition Re...

Страница 21: ...ear Matrix on top of the Matrix Tray Ensure it is sat up against the back and with TOP facing you c Slide the Front Matrix in front of the burner as shown with FRONT facing you Health Safety Advice Re...

Страница 22: ...shown b Fit the Front Coal Cluster on top of the Front Matrix as shown c Fit 3off C coals up against the Rear of the fire as shown Set the C indent facing the back d Fit 2off B coals in the pocket in...

Страница 23: ...ls to ensure they are located correctly stable and not overhanging the pockets Also ensure non of the identification letters stamped on the coals are visible j Before fitting the glass panel with the...

Страница 24: ...Wood Coal Cluster on top of the Rear Matrix as shown b Fit the Front Wood Coal Cluster on top of the Rear Matrix as shown c Fit the Far Left Wood Piece into the Recessed area as shown d Fit the Far R...

Страница 25: ...e Underside of the Wood into the Recesses as shown Finally adjust the Wood Pieces to ensure they are located correctly and stable h Before fitting the glass panel with the 5 special countersunk screws...

Страница 26: ...d For Customers who have purchased the Thermatronic or High Level Controls explain and demonstrate that the batteries in the receiver and handset Thermatronic or Battery Box High Level should be repl...

Страница 27: ...5 special countersunk screws p With the 2 Remote Control Systems Always exchange the Batteries in both the Handset and Receiver q With the 2 Remote Control Systems ensure they are operational with th...

Страница 28: ...Disconnect the push on wire connections at the control Remove the switch and wires and replace with a new component in reverse order g All Control Systems have a Pressure Test Point to allow the Burne...

Страница 29: ...portant Note in Section 18 under Testing Commissioning Use d Fumes can be coming specifically from inferior Fire Surround materials e g resins from conglomerate materials which we do not recommend rat...

Страница 30: ...be Installed serviced by a properly qualified in accordance with Local National Codes Installation Engineer and in accordance with these Installation Instructions Supplier Nu Flame Limited Model Fent...

Страница 31: ...must be Installed serviced by a properly qualified in accordance with Local National Codes Installation Engineer and in accordance with these Installation Instructions Supplier Nu Flame Limited Model...

Страница 32: ...ton Balanced Flue Certificate Number 19GR0277 00 The object of the declaration described above is in conformity with relevant harmonized legislation Gas Appliance Regulation EU 2016 426 The following...

Страница 33: ...33 23 DIAGRAM OF RADIO FREQUENCY CONTROL SYSTEM...

Страница 34: ...uring the return delivery to us We will not be liable for any such breakages Under no circumstances should any attempt be made to repair the burner on site without our express knowledge and approval d...

Отзывы: