12.1 - FIRE SURROUND APPLICATIONS
If a fire surround is being used we supply a Cable Fixing System as Drill Fixing may result in cracking of the back panel, which may not
show until the fire has got hot and then cooled down over a number of operations.
If the fire is being fitted against a Masonry Wall then the Fires Fixing Brackets with Drill/ Rawlplug Fixing Must be used and Not the Cable
Fixing System. See the Wall Fixing and Cable Fixing Diagrams on Page 20.
Nu-Flame does not recommend the use of a 1 piece back panel as cracking can occur.
Nu-Flame will not accept responsibility for Cracked Back Panels due to Drill Fixing.
12. - TRADITIONAL PROPERTY WITH COMBUSTIBLE INTERNAL WALLS (e. g. Timber/Wood/ Stud )
With or Without a Standard & Rebated Fire Surrounds, Back Panel or Slips.
700mm
Min
300 mm
Min
Flue Hole 160mm Dia
Plaster Board
Cut Back 25mm
Around Flue Hole
454mm to
Hole Centre
655mm Min to
Underside Of
Studding & Lined
400mm Min
to Studding
Lining of
Non Combustible
Board On Inside &
Back Faces
Of Studding
Dry Lined Internal
Walls with Cavity
Combustible Shelf
Minimum Height
Non Combustible
Minimum Height
Plaster Board Cut
Back 25mm
Around Flue
Cavity Sealed Off
100mm away from
Flue
160mm Min
Dia Flue Hole.
3 Piece
Fire Surround Back
Panel.
MINIMUM CLEARANCES FOR COMBUSTIBLE MATERIALS
WITH FLUE HOLE POSITION & SIZE
3 PIECE FIRE SURROUND BACK PANEL
Standard Fireplace Construction & Shelf Details
MINIMUM FLAT AREA AROUND THE FLUE WITH
HEARTH & UPSTAND REQUIREMENTS
635mm
Min
160mm Min
Dia Flue Hole.
630mm
Min
Upstand 15mm Max
Hearth