3. - CLEANING THE FIRE 

       Note: Marks on the Glass Panel are Not Covered by the Manufactures Warranty.  

a.

 

Important

 : Always Allow the fire to cool before carrying out any cleaning. 

b.  Please Note

: The glass panel surface within the room will be marked by air borne particles as air circulates through the fire  

      from the room, this is quite normal and cannot be prevented.  

 

      So the glass surface within the room can be cleaned with proprietary glass cleaners and any residue removed and dried afterwards.  
      

No 

Abrasive Cleaners Must be used. 

c.

  Within the fire it is quite normal for soot and stains to build-up on the inside of the glass panel, this is why we advise that the glass  

     panel must be fully cleaned during the Annual Service, however you can remove the glass panel for cleaning as follows:  

i. Remove the Case by opening the Control Door and using the screw driver provided remove the 2 screws as shown. Now lift the Case 
at the back clear of the fire and lay it down in a safe area.  
ii.  Using the Screw Driver provided remove the 5 Special Countersunk Screws then Ease the Glass/Frame Assembly outward slightly  
     at the base then Pull down and remove.  
iii.  To clean the glass panel use proprietary glass cleaners, however for stubborn stains use ‘T Cut Original’ and following treatment  
     remove all residue and polish with a dry cloth.  
Note: The glass is etched with the Nu-Flame logo ensure it is at the bottom right hand corner when refitting the glass panel. 
 

Note: It is Very Important to lay the Case down on its back as it can easily Fall Over and be damaged. 

 

d. 

The outer surfaces of the stove case can be cleaned with a damp cloth and lightly polished with a duster, do 

not

 use abrasive cleaners. 

 

 

 

    ! IMPORTANT NOTE !    

The Fire 

MUST NEVER

 be used without the Glass Panel in place or if it is in any way damaged.

 

 

4. - SERVICING 

a.

  The fire should be Serviced Annually in accordance with the Gas Safety & Uses Regulations. 

b.

  This fire contains no User Serviceable Parts apart from batteries (only used with the Thermatronic Control System option). 

c.

  Servicing must be carried out by a Registered Installer. 

d.

  For Servicing or Spare Parts contact your Installer quoting the Fire Name, Model and Serial Number, which can be found on the Data 

Badge. To find the Data Badge/Plate; with the fire cool remove the Ash Pan, the Data Badge can be found at the base next to the  

      Control Knob. 

e.

  In the event that the fire shuts down due to any reason, attempt to restart it. If there is a continuing problem, call in a properly qualified 

specialist engineer. 

f.

 

Under No Circumstances

 must this fire be used without the Glass Panel or if it is broken damaged or cracked. 

g.

  The Matrix in the fire is a Moulded Ceramic Fibre component incorporating Silicone Binders and you may notice that it develops  

      cracks during operation.  This is natural shrinkage caused by exposure to high temperatures and is quite normal for the material and will 
      in no way affect the operation of the fire.

 

h.

  The fire is fitted with a Safety Pressure Relief System and if the fires ignition should ever become delayed, or noisy then the fire 

MUST 

NOT 

be used until checked by a Qualified Engineer/Installer.  

 

i.  

 If at any time fumes are found to be emitting from the fire immediately turn the fire off.    

     Do not use and contact a Qualified Engineer/Installer.  
 
 
 
 
 
 

 

RECORD DATA TO BE COMPLETED & KEPT BY USER:

 

 

IMPORTANT : THE FENTON BALANCED FLUE MUST ONLY BE REPAIED WITH Nu-Flame’s  CE APPROVED PARTS 

 

PLACE OF PURCHASE 

..................................................................……………………

        DATE

 ……....................

 

 

 

ADDRESS & TEL. NO.

 …………….......................................….................................................................................. 

 

 

.................................................................................................................................………………………..........….....

 

 

 

.................................................................................................................................………………………..........….....

 

 

 

APPLIANCE SERIAL NO. 

..............................................  

 

 

INSTALLED BY 

........................................…………………………………

      GAS SAFE REG. NO. 

......................... 

 

 
 
 
 
 
 

THE FENTON BALANCED FLUE 

 

INSTALLATION & SERVICING INSTRUCTIONS  

Содержание Fenton Balanced Flue

Страница 1: ...be placed close to or on the fire We recommend that a Fireguard conforming to BS8423 should be used for protection of Young Children the Elderly Infirm and Pets ALL INSTRUCTIONS MUST BE LEFT WITH THE...

Страница 2: ...rmity 32 23 Diagram of Infrared Control System 33 Guarantee 34 BOX CONTENTS The Fire comes in a number of boxes Box 1 Large box contains the Fire the Matrix Tray chosen Control System plus Fitting Kit...

Страница 3: ...mm copper pipe gas supply to the burner via the isolation elbow 1 2 050mm length of 5mm x 4mm self adhesive silicone sealing strip for around the frame and base of the fire 1 1 820mm length of 5mm x 4...

Страница 4: ...no nearer than 300mm to an opening in the building fabric formed for the purpose of accommodating a built in element such as a window frame The reference to external corners does not apply to building...

Страница 5: ...a Safety Pressure Relief System and if the fires ignition should ever become delayed or noisy then the fire MUST NOT be used until checked by a Qualified Engineer Installer t In the event that the fi...

Страница 6: ...y law and CE approval Commands are accepted by the microprocessor when buttons are pressed An audible beep means that the command has been received and the push button should immediately be released t...

Страница 7: ...l Flame button to set the Minute Press Off or simply wait to return to the manual screen IMPORTANT For the following modes of controlling the fire automatically for Temperature or Timer Programs the F...

Страница 8: ...ty alkaline e To change the Handset battery slide open the plastic panel on the back of the Handset f To change the Receiver Batteries remove the Ash Pan Cover and locate the electronic receiver box u...

Страница 9: ...ners IMPORTANT NOTE The Fire MUST NEVER be used without the Glass Panel in place or if it is in any way damaged 4 SERVICING a The fire should be Serviced Annually in accordance with the Gas Safety Use...

Страница 10: ...to comply with the above could leave the Installer Liable to Prosecution and Invalidate the Warranty IMPORTANT BEFORE PROCEEDING WITH THE INSTALLATION READ THESE INSTRUCTIONS CAREFULLY THESE INSTRUCT...

Страница 11: ...he left of the centre of the fire and 39mm up from the base of the Fireplace Builders opening An isolation elbow is provided at the control inlet Your 8mm gas supply pipe needs to protrude through the...

Страница 12: ...Construction Shelf Details Sections 11 12 13 are for the various Installation Applications for Traditionally Built Houses Only one will apply For Timber Frame Houses refer to Section 13 IMPORTANT NOTE...

Страница 13: ...nd high humidity so it is very important that any rendering building work is allowed to thoroughly dry out before installation NOTE Take Care Not To Use Materials That Will Give Off An Odour When Hot...

Страница 14: ...E INTERNAL WALLS e g Timber Wood Stud With or Without a Standard Rebated Fire Surrounds Back Panel or Slips 700mm Min 300 mm Min Flue Hole 160mm Dia Plaster Board Cut Back 25mm Around Flue Hole 454mm...

Страница 15: ...t is very important that any rendering building work is allowed to thoroughly dry out before installation NOTE Take Care Not To Use Materials That Will Give Off An Odour When Hot As This Issue Is Know...

Страница 16: ...Installation d Installation MUST take account of the Outer Wall Cladding be it Brick or Weather Boards the latter being combustible will require different Installation Requirements We recommend seeki...

Страница 17: ...STIBLE MATERIALS AND SHELVES a A non combustible shelf can be fitted above the fire and should be positioned at least 95mm above the builders opening We recommend the depth of the shelf should be a ma...

Страница 18: ...terial from inside the Flue d With the flue at the correct length and when the fire is fitted there should be 130mm of Flue Terminal Outside The Wall and the screw holes for fixing the Wall Plate shou...

Страница 19: ...e drill the lower holes 27mm up from the base and drill the higher holes 510mm up from the base see Cable Fixing Diagrams on next page Secure the 4 Eyebolts supplied with the Rawl Plugs to the back of...

Страница 20: ...t the Burner Assembly and secure with 4 screws reposition the Thermatronic Receiver Box and Infrared Sensor or for High Level Control the Battery Box onto their Velcro Pads if applicable Reposition Re...

Страница 21: ...ear Matrix on top of the Matrix Tray Ensure it is sat up against the back and with TOP facing you c Slide the Front Matrix in front of the burner as shown with FRONT facing you Health Safety Advice Re...

Страница 22: ...shown b Fit the Front Coal Cluster on top of the Front Matrix as shown c Fit 3off C coals up against the Rear of the fire as shown Set the C indent facing the back d Fit 2off B coals in the pocket in...

Страница 23: ...ls to ensure they are located correctly stable and not overhanging the pockets Also ensure non of the identification letters stamped on the coals are visible j Before fitting the glass panel with the...

Страница 24: ...Wood Coal Cluster on top of the Rear Matrix as shown b Fit the Front Wood Coal Cluster on top of the Rear Matrix as shown c Fit the Far Left Wood Piece into the Recessed area as shown d Fit the Far R...

Страница 25: ...e Underside of the Wood into the Recesses as shown Finally adjust the Wood Pieces to ensure they are located correctly and stable h Before fitting the glass panel with the 5 special countersunk screws...

Страница 26: ...d For Customers who have purchased the Thermatronic or High Level Controls explain and demonstrate that the batteries in the receiver and handset Thermatronic or Battery Box High Level should be repl...

Страница 27: ...5 special countersunk screws p With the 2 Remote Control Systems Always exchange the Batteries in both the Handset and Receiver q With the 2 Remote Control Systems ensure they are operational with th...

Страница 28: ...Disconnect the push on wire connections at the control Remove the switch and wires and replace with a new component in reverse order g All Control Systems have a Pressure Test Point to allow the Burne...

Страница 29: ...portant Note in Section 18 under Testing Commissioning Use d Fumes can be coming specifically from inferior Fire Surround materials e g resins from conglomerate materials which we do not recommend rat...

Страница 30: ...be Installed serviced by a properly qualified in accordance with Local National Codes Installation Engineer and in accordance with these Installation Instructions Supplier Nu Flame Limited Model Fent...

Страница 31: ...must be Installed serviced by a properly qualified in accordance with Local National Codes Installation Engineer and in accordance with these Installation Instructions Supplier Nu Flame Limited Model...

Страница 32: ...ton Balanced Flue Certificate Number 19GR0277 00 The object of the declaration described above is in conformity with relevant harmonized legislation Gas Appliance Regulation EU 2016 426 The following...

Страница 33: ...33 23 DIAGRAM OF RADIO FREQUENCY CONTROL SYSTEM...

Страница 34: ...uring the return delivery to us We will not be liable for any such breakages Under no circumstances should any attempt be made to repair the burner on site without our express knowledge and approval d...

Отзывы: