50
Matrix Installation and Operation Instructions
14.0 SEQUENCE OF OPERATION
Boiler in
standby mode
Furnace Control
closes T-C circuit.
Furnace Control
closes A-C circuit.
Displays version
b1.0
120v Power
Applied
Awaiting Input
From Furnace Control
at Contacts A-C-T
Energizes Internal
Circulator (C1)
Sentry 2100
Sentry 2100
Open
Error
A S C
Closed
Sentry 2100
Combustion Blower
Starts, SFS (80)
VDC Signal
to Combustion
Blower
Sentry 2100
Error
A S O
Three
Retries
for Flame
Power to Ignitor
120V to S1
Checks Flame
Probe Signal
Less than
0.6 uAmp
Power to Gas Valve
Greater than 1.0 uAmp
Prepurge
Call for flame ends
Igniter warm-up
5 seconds
N/O
Open
Closed
Water Temperature Limit
&
Flue Gas Temperature Limit
&
Water Pressure Limit
Check
24 V
24 V
Furnace Control closes
A-C and T-C circuit.
Forced Air Demand
Hydronic Demand
DHW Demand
`
Sentry 2100
modulates combustion
blower based upon setpoint
and programing
Figure 14.1 Matrix Boiler Control Sequence Of Operation