43
Matrix Installation and Operation Instructions
Menu
Item
Description
Sample HRV
Ventilation
Rates
Installed
Ventilation
Rates
Installed
Fan
Speed
EOH
HRV
Exhaust
at
Override
(high ventilation) rate, balanced during
High
air
circulation rate (800/1000/1200CFM).
120cfm
(55 L/s)
SOH
HRV
Supply
at
Override
(high ventilation) rate, balanced during
High
air
circulation rate (800/1000/1200CFM).
120cfm
(55 L/s)
EOL
HRV
Exhaust
at
Override
(high ventilation) rate, balanced during
Low
air
circulation rate (300/400/500CFM).
120cfm
(55 L/s)
SOL
HRV
Supply
at
Override
(high ventilation) rate, balanced during
Low
air
circulation rate (300/400/500CFM).
120cfm
(55 L/s)
ECH
HRV
Exhaust
at
Continuous
(low ventilation) rate, balanced during
High
air
circulation rate (800/1000/1200CFM).
70cfm
(30 L/s)
SCH
HRV
Supply
at
Continuous
(low ventilation) rate, balanced during
High
air
circulation rate (800/1000/1200CFM).
70cfm
(30 L/s)
ECL
HRV
Exhaust
at
Continuous
(low ventilation) rate, balanced during
Low
air
circulation rate (300/400/500CFM).
70cfm
(30 L/s)
SCL
HRV
Supply
at
Continuous
(low ventilation) rate, balanced during
Low
air
circulation rate (300/400/500CFM).
70cfm
(30 L/s)
Table 11.1 HRV Balancing Table
Magnehelic (0-.25 inwg)
or Digital Manometer
Figure 11.1 Sample Balancing Setup
6” Flow Measurement Station,
Averaging Pitot Tube, or
Pitot TransferTube
Fresh
Supply
Stale
Exhaust