39
Description
Vent
Size
Supplier
Part Number
Figure
Vent Material
Compatibility
Vent Option Availability
Roof
Wall
IPEX (or Equivalent) Low Profile
(Wall)
7
2”
196984 (NTI p/n 85062)
26, 30
PVC/CPVC
No
Yes
3”
196985 (NTI p/n 84357)
26, 30
IPEX (or Equivalent) Concentric
(Wall/Roof)
4, 5, 6, 7
2”
196125
27, 31, 38, 42
Yes
Yes
3”
196116 (NTI p/n 84634)
27, 31, 38, 42
196117
27, 31, 38, 42
Duravent Polypro® Concentric (Wall)
2 - 3”
2PPS-HK, 3PPS-HK
28, 32
Polypro®
Polypropylene
No
Yes
Duravent
Polypro® Concentric (Roof)
2 - 3”
2PPS-VK, 3PPS-VK
39, 43
Yes
No
InnoFlue® Flush Mount (Wall)
2 - 3”
ISLPT0202, ISLPT0303
26, 30
InnoFlue®
Polypropylene
No
Yes
InnoFlue® Concentric (Wall)
2 - 3”
ICRT2439, ICTC0224
28, 32
No
Yes
InnoFlue®
Concentric (Roof)
2 - 3”
ICRT3539, ICTC0335
39, 43
Yes
No
Z-DENS® Concentric (Wall)
2 - 3”
2ZDHK2, 2ZDHK3
Not Shown
Z-DENS®
Polypropylene
No
Yes
Z-DENS® Concentric (Roof)
2 - 3”
2ZDVK2, DZDVK3
Not Shown
Yes
No
NOTES:
1 Instructions included with termination kits contain detailed assembly and installation instructions.
2 Clearance requirements in this manual supersede those of the instructions included with the vent terminal.
3 Piping
MUST
be secured to the vent terminal during installation.
4 IPEX Concentric Terminal
MUST
be cemented together and to the vent pipes during installation.
5 Vent Screens provided with boiler may be used with the IPEX Concentric Vent Kits; otherwise use IPEX vent screens (2 in. vent screen p/n 196050; 3 in. vent
screen p/n 196051 - each sold separately).
6 IPEX Low Profile and Concentric kits (exluding p/n 197117) are constructed out of ULC-S636 approved PVC. Check with your local authority for the acceptance
of PVC as a venting material prior to use.
7 IPEX Concentric kits can be shortened to fit the requirements of the installation. See instructions included with the kit for more details.
Table 16 - Optional Vent Termination Kits
Part 5 - Venting