28
Part 1 - General Safety Information
Cap this fitting
when not in use
Figure 17 - Boiler with Multiple Central Heating Circulators
Part 4 - Water Piping
Primary/Secondary Piping Shown - See
Note 2
NOTE:
In piping applications utilizing a single zone, it is recommended
that the installer use flow / check valves with weighted seats at or near
the appliance to prevent gravity circulation.
NOTES:
1. This drawing is meant to show system piping concept only.
Installer is responsible for all equipment and detailing required by
local codes.
2. Primary / Secondary Loop: All closely spaced tees shall be within 4
pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed
upstream and downstream of all closely spaced tees.
4. The minimum pipe size of DHW piping should be ¾” diameter and
CH piping should be 1” in diameter.
5. Circulators are shown with isolation flanges. The alternative is
standard flanges with full port ball valves. Purge valves can be used
with circulator flanges as an alternative.
6. Piping shown is Primary/Secondary.
7. Install a minimum of 12 diameters of straight pipe upstream of all
circulators.
8.
VERY IMPORTANT
– Minimum flow rates outlined in this manual
(2 gpm) must be maintained through the heat exchanger to
minimize short cycling.
9. In a valve-based system, each heating zone has a zone valve which
opens when that zone calls for heat. Each zone thermostat is
wired to its corresponding zone valve. Contacts in the zone valves
provide a signal to the boiler to operate when there is a call for
heat.
10.
Unit is equipped with built-in primary pump.
This pump is sized
to ensure proper flow rate through the boiler heat exchanger and
related piping.
11. IWH Applications - a mixing valve is recommended if the DHW
temperature is set above 119
o
F.
The piping will not support the weight of the circulators. Refer to
the circulator manufacturer’s instructions to properly support the
circulator. Failure to comply with these instructions could result in
property damage, severe personal injury, or death.
Figure illustrates the basic plumbing requirements for a FTVN085 /
FTVN110 / FTVN150 / FTVN199 boiler installation utilizing Primary/
Secondary piping when the boiler circulator will not provide adequate
flow for the system. Primary / Secondary is required to provide
adequate flow for the secondary circuits.
On FTVN085 / FTVN110 / FTVN150 / FTVN199 Models Only.
If the boiler’s DHW connection is not used, cap the fitting as indicated
above. A cap is included with the boiler. Further, the electrical
connection of the 3-way valve motor MUST BE DISCONNECTED while
the boiler is operating in central heating mode. This will lock the valve
motor in central heating mode and ensure freeze protection operates
properly. Failure to disconnect the valve may disable boiler freeze
protection and result in property damage.
WARNING
CAUTION
NOTICE
In mixed temperature applications, mixing valves are required for the
protection of low temperature loops.
CAUTION