Part 1 - General Safety Information
Part 3 - Prepare the Boiler for Installation
K. Technical Specifications
Table 7 - Technical Specifications
NOTES:
1
Listed Input and Output Ratings are at minimum vent lengths at an altitude of 0 - 2000 ft. Numbers will be lower with longer venting and/or altitudes
greater than 2000 ft.
2
Ratings based on standard test procedures prescribed by the US Department of Energy.
3
The FTVN requires a special venting system. Use only the vent materials and methods detailed in these installation instructions.
Model
FTVN085
FTVN110
FTVN150
FTVN199
FTVN110C
FTVN150C
FTVN199C
Type
Boiler
Boiler
Boiler
Boiler
Combi
Combi
Combi
Installation
Indoor, Wall Hung, Fully Condensing
Minimum / Maximum Input (Btu/Hr)
1
8,500 / 85,000
11,000 /
110,000
15,000 /
150,000
19,900 / 199,000
11,000 /
110,000
15,000 /
150,000
19,900 / 199,000
DOE AFUE
2
(%)
96
95
95
95
95
95
95
Heating Capacity
1, 2
(MBH)
79
101
138
184
101
138
184
Net AHRI Rating, Water (MBH)
2
69
88
120
160
88
120
160
Hot Water Capacity
35
o
F Rise
N/A
N/A
N/A
N/A
5.8
7.9
10.5
45
o
F Rise
4.5
6.1
8.2
77
o
F Rise
2.6
3.6
4.8
Flue System
Category IV, Sealed Combustion Direct Vent, Power Vent
Minimum - Maximum Exhaust Vent Run
3
2” (6 - 100 feet), 3” (6 - 150 feet)
3” (6 - 150 feet)
2” (6 - 100 feet), 3” (6 - 150 feet)
3” (6 - 150 feet)
Minimum - Maximum Intake Air Pipe Run
3
2” (0 - 100 feet), 3” (0 - 150 feet)
3” (0 - 150 feet)
2” (0 - 100 feet), 3” (0 - 150 feet)
3” (0 - 150 feet)
Approved Exhaust Vent Materials
3
PVC, CPVC, PP, Stainless Steel
Shipping Weight (lbs)
110
110
120
131
110
121
132
Gas Supply
Pressure
NG
3.5” to 10.5” WC
LP
8” to 13” WC
Power Supply
120V, 60 Hz, less than 12A
General Operating Conditions
Ambient Temperature Range: 33 – 104
o
F (0.6 – 40
o
C)
Product Approvals and Requirements: ANSI Z21.13 / CSA 4.9
Ignition System
Direct Electronic Spark Ignition / Flame Rectification
Burner System
Premixed Fuel Modulation / Stainless Steel Burner
Gas Valve System
Air Ratio Valve
Dimensions
(in Inches)
W
19.75
H
38.25
D
17
18.5
17
18.5
Approx. Full Boiler Weight (lbs)
107
107
122
139.5
107
128.5
140.5
Boiler Water Content (Gallons)
1.4
1.4
2.0
2.8
1.5
2.1
2.8
Boiler Setpoint Temperature Range
68 – 122
o
F Low Temperature / 86 - 179
o
F High Temperature
DHW Indirect Setpoint Temperature Range
104 – 149
o
F
DHW Setpoint Range (Combi Models)
97 – 149
o
F
Water Pressure
(PSI)
Heat Exchanger MAWP
50
Pressure Relief Valve
30
DHW Max Pressure
N/A
N/A
N/A
N/A
150
150
150
Control Panel / Main Controller
AristonThermo LCD Display / AristonThermo GALEVO2 Control
Connection
Sizes
CH Supply / Return
1 1/4” Male NPT
DHW Inlet / Outlet
3/4” Male NPT
Gas Inlet
3/4” Male NPT
Materials
Cabinet
Painted Steel
Heat Exchanger
SA-240-S43932 Stainless Steel Water Tube
Safety Devices
Flame Rectifier Probe, Temperature Limit Control (190
o
F), Water Pressure Switch (Min. 8 PSI), Freeze Protection,
Blocked Condensate Pressure Switch, Condensate Trap, Flue Temperature High Limit Sensor (210
o
F), Blocked
Vent Pressure Switch