6 Settings
PCS-9785 Satellite Synchronized-Clock
6-8
Date: 2019-07-05
Ethernet port 1
Setting
Value
Bit0
Ethernet port 2
Bit2
3
Bonding
Bit1
Bit3
1
1
0
0
Ethernet port 1
Setting
Value
Bit0
Ethernet port 3
Bit2
5
Bonding
Bit1
Bit3
1
0
1
0
Ethernet port 1
Setting
Value
Bit0
Ethernet port 4
Bit2
9
Bonding
Bit1
Bit3
1
0
0
1
Ethernet port 2
Setting
Value
Bit0
Ethernet port 3
Bit2
6
Bonding
Bit1
Bit3
0
1
1
0
Ethernet port 2
Setting
Value
Bit0
Ethernet port 4
Bit2
10
Bonding
Bit1
Bit3
0
1
0
1
Ethernet port 3
Setting
Value
Bit0
Ethernet port 4
Bit2
12
Bonding
Bit1
Bit3
0
0
1
1
Ethernet port 1: Bit0, Ethernet port 2: Bit1, Ethernet port 3: Bit2, Ethernet port 4: Bit3
The Active-Standby mode switching logic is:
Take the device Ethernet ports 1 & 2 for example and assume that P1 is connected to NET1
while P2 is connected to NET2.
After the device is powered on, only P1 is activated when both NET1 and NET2 are
normal.
If NET1 is abnormal, P2 will be activated if NET2 is normal.
If NET1 is abnormal, P2 cannot be activated if NET2 is also abnormal. The device will
keep trying on P1.
If P2 is working, the device will maintain this state even if NET1 has been restored to
normal. It will be switched to P1 only if NET2 is abnormal.
Gateway
IP address of local gateway (router)
Destination_1, Destination_2, Destination_3, Destination_4
Network segment of opposite router 1, 2, 3, 4
Genmask_1, Genmask_2, Genmask_3, Genmask_4
Subnet mask of local router 1, 2, 3, 4
Gateway_1, Gateway_2, Gateway_3, Gateway_4
IP address of local gateway (router) 1, 2, 3, 4
IP_FE1, IP_FE2, IP_FE3, IP_FE4
IP address of front-end 1, 2, 3, 4 in Substation Automation System (SAS)
08020
08020
08020
08020
08020
08020
08020
08020
08020