6 Settings
PCS-9785 Satellite Synchronized-Clock
6-1
Date: 2019-07-05
6.1 Overview
Setting configuration is an important function of device. The device normal operation depends in
the correct setting configuration. Thus, only a qualified technician should be responsible for the
configuration. Furthermore, if the device is operating abnormally, please check the setting
configuration firstly.
NOTICE!
According to different applications for different engineering requirements, settings may
be different. This chapter describes as many settings as possible to make a reference
for user.
6.2 For PCS-9785 Clock Source
6.2.1 Device Settings
No.
Item
Range(Unit)
Default Value
1
Opt_DualDev
Slave or Master
Master
2
Opt_Src_InitClk
Internal or External
External
3
Opt_Parity_Send_IRIG-B
Odd or Even
Odd
4
t_PW_Send_Pulse
10~200(ms)
200
5
En_Meas_f_Grid
Disable or Enable
Disable
6
En_MDisk
Disable or Enable
Enable
Opt_DualDev
This is the device clock service mode option for the dual device redundancy strategy. It should
be "Slave" if the MON module NR1145A is selected. Otherwise, it should be "Master".
Opt_Src_InitClk
This is the device initialization mode option.
External
The device is initialized by external timing source. There will be no
output before the completion of initialization.
Internal
The device is initialized by its internal clock.
Opt_Parity_Send_IRIG-B
The parity check mode option for IRIG-B output signal.
t_PW_Send_Pulse
The pulse width setting for output signal PPS/PPM/PPH.
En_Meas_f_Grid
Logic enabling setting for time frequency measurement.
If this setting is enabled, the device LCD displays the measured grid frequency (under 220Vac)