Novus N1200 Скачать руководство пользователя страница 8

Controller N1200  

NOVUS AUTOMATION 

8 / 13 

rskl 

Remote SP 

High Limit

 

REMOTE SETPOINT HIGH LIMIT: defines the full 
scale indication of the Remote Setpoint

.

 

Parameter displayed when remote SP is enabled.  

Spll 

Setpoint Low 

Limit

 

Defines the SP lower limit of SP.  
For  the  linear  analog  input  types  available  (0-20 
mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V), defines 
the minimum PV indication range, besides limiting 

the SP adjustment. 

Spxl 

Setpoint High 

Limit

 

Defines the upper limit for adjustment of SP.  
For  the  linear  analog  input  types  available  (0-20 
mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V), defines 
the maximum PV indication range, besides limiting 

the SP adjustment. 

rtll 

Retransmission

Low Limit

 

In association with the 

rtxl

 parameter, it defines 

the analog retransmission scale for PV or SP. The 

rtll

  represents  the.  minimum  scale  value  for 

the analog output 
This  parameter  is  displayed  only  if  the  analog 
retransmission  is  selected  in  the  I/O  5  parameter 
(I/O level). 

rtkl 

Retransmission 

High Limit

 

Defines  the  full  scale  value  for  the  analog 

retransmission of PV or SP.  
This parameter is displayed only when the analog 
retransmission  is  selected  in  the  I/O  5  parameter 
(I/O level). 

1eov 

 

Percentage output value that will be transfer to MV 
when  the  SAFE  output  function  is  enabled.  If 

1eov

  =  0,  the  SAFE  output  function  is  disabled 

and the outputs are turned off in the occurrence of 
a sensor fail. 

bavd 

Baud

 

Rate

 

Digital  communication 

Baud  Rate

  selection,  in 

kbps: 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 and 115.2  

prty 

Parity

 

Parity of the serial communication.  

 

none

  Without parity  

 

Ewem

  Even parity  

 

0dd

 

Odd parity  

Addr 

Address

 

SLAVE  ADDRESS  SELECTION:    Identifies  the 
controller  in  the  network.  The  possible  address 
numbers are from 1 to 247.  

CYCLE OF I/OS (INPUTS AND OUTPUTS)  

Io 1 

Function  of  the  channel  I/O  1:  Selection  of  the 
function used in the channel I/O 1, according to the 

Table 2

.  

Io 2 

Function  of  the  channel  I/O  2:  Selection  of  the 
function used in the channel I/O 2, according to the

 

Table 2

.  

Io 3 

Function  of  the  channel  I/O  3:  Selection  of  the 
function used in the channel I/O 3, according to the 

Table 2

.  

Io 4 

Function  of  the  channel  I/O  4:  Selection  of  the 
function used in the channel I/O 4, according to the 

Table 2

.  

Io 5 

Function  of  the  channel  I/O  5:  Selection  of  the 
function used in the channel I/O 5, according to the 

Table 2

.  

CALIBRATION CYCLE 
All of the input and output types are calibrated in the factory. If a 
recalibration  is  required,  this  should  be  carried  out  by  a 
experienced personnel. If this cycle is accidentally accessed, pass 
through all the parameters without pressing the   or   keys  

pass 

Password

 

Input of the Access Password.  
This  parameter  is  presented  before  the  protected 
cycles. See item 

Protection of Configuration

.  

inL( 

Input Low 

Calibration

 

See section MAINTENANCE / Input Calibration.  
Enter  the  value  corresponding  to  the  low  scale 
signal applied to the analog input.  

ink( 

Input High 

Calibration

 

See section MAINTENANCE / Input Calibration.  
Enter  the  value  corresponding  to  the  full  scale 
signal applied to the analog input.  

rsL( 

Remote SP Low 

Calibration

 

See section: MAINTENANCE / Input Calibration  
Enter  the  value  corresponding  to  the  low  scale 
signal applied to the remote SP input.  

rsk( 

Remote SP 

High Calibration

 

See section: MAINTENANCE / Input Calibration.  
Enter  the  value  corresponding  to  the  full  scale 
signal applied to the remote SP input. 

0vL( 

Output Low 

Calibration

 

See  section  MAINTENANCE  /  Analog  output 
Calibration.  Enter  the  analog  low  value  as 
measured at the analog output.  

0vk( 

Output High 

Calibration

 

See  section  MAINTENANCE  /  Analog  output 
Calibration.  Enter  the  analog  high  value  as 
measured at the analog output. 

rstr

 

Restore

 

Restores  the  factory  calibration  for  all  inputs  and 
outputs,  disregarding  modifications  carried  out  by 

the user. 

(j 

Adjusts the of cold junction temperature value.  

ktyp 

Hardware Type

 

Parameter  that  informs  the  controller  about  the 
hardware optionals installed. It should not be altered 
by the user, except when an accessory is introduced 
or removed.  

0

 – Basic model. Without optional items  

1

 – 485 

– 3R 

3

 – 3R + 485 

– DIO 

– DIO + 485 

– HBD 

– HDB + 485 

Note:

 The options 

6

 and 

7

 not are used. 

Pas.( 

Allows  defining  a  new  access  password,  always 
different from zero.  

Prot 

Sets up the Level of Protection. See 

Table 7.

  

Freq 

Mains  frequency.  This  parameter  is  important  for 
proper noise filtering. 

 
 
 
 

 
 
 
 

 
 
 
 

Содержание N1200

Страница 1: ...meters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments eac...

Страница 2: ...xecution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts freezes execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starti...

Страница 3: ...th this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal Available only for the inputs belonging to the group of linear analogic signals 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V ANALOG RETRANSMISSION OF PV AND SP The analog output when not used for control purposes is available for retransmitting the PV and SP value...

Страница 4: ... your supervisory software to conduct the MONITORING process Follow the procedure below to use the USB communication of the equipment Download the NConfig software from our website and install it on your computer The USB drivers necessary for operating the communication will be installed together with the software Connect the USB cable between the equipment and the computer The controller does not...

Страница 5: ... product specifications Figure 6a I O3 or I O4 with output pulse for SSR Figure 6b I O5 with output pulse for SSR I O3 I O4 and I O5 can also be configured as digital outputs I O3 and I O4 provide a 5 Vdc output signal whereas I O5 a 12 Vdc signal An example of usage is shown in Figure 6a for the I O3 and in Figure 6b for the I O5 I O5 is electrically isolated from the sensor input OPERATION The c...

Страница 6: ...ed 0 does not execute program 1 to 20 number of the program to be executed With enabled outputs RUN YES the program starts right after the program is selected p seg Screen for indication only When a ramp and soak program is active this parameter shows the number of the segment under execution from 1 to 9 t seg Screen for indication only When a ramp and soak program is in execution it shows the rem...

Страница 7: ...r up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 ALARM HYSTERESIS Defines the difference between the value of PV at which the alarm is xya2 xya3 xya4 triggered and the value at which it is turned off in engineering units A1t1 A2t1 A3t1 A4t1 Alarm Time t1 Defines the temporization time t1...

Страница 8: ...l I O 3 according to the Table 2 Io 4 Function of the channel I O 4 Selection of the function used in the channel I O 4 according to the Table 2 Io 5 Function of the channel I O 5 Selection of the function used in the channel I O 5 according to the Table 2 CALIBRATION CYCLE All of the input and output types are calibrated in the factory If a recalibration is required this should be carried out by ...

Страница 9: ...des the parameters on the protected levels If no password is entered the parameters of the protected cycles can only be visualized The Access Code is defined by the user in the parameter Password Change PAS present in the Calibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access...

Страница 10: ...itiated by the controller whenever the control performance is worse than the one found after the previous tuning In order to activate the performance supervision and auto adaptative tuning the parameter ATUN must be adjusted for SELF RSLF or TGHT The controller s behavior during the auto adaptative tuning will depend on the worsening of the present performance If the maladjustment is small the tun...

Страница 11: ...ignal that corresponds to a value a little lower than the upper limit of indication f Access the parameter inLC With the keys and adjust the display reading such as to match the applied signal Then press the P key Note When checking the controller calibration with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA e...

Страница 12: ...Vdc 24 Vac 10 20 Maximum consumption 9 VA ENVIRONMENTAL CONDITIONS Operation Temperature 5 to 50 C Relative Humidity 80 max 30 ºC For temperatures above 30 ºC reduce 3 for each ºC Internal Use Category of installation II Degree of pollution 2 altitude 2000 m INPUT T C Pt100 voltage and current according to Table 1 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 199...

Страница 13: ... Relay in I O3 DIO Digital I Os in I O3 and I O4 HBD Burnt Out Resistance detection C Digital Communication Blank basic version without serial communication 485 RS485 Modbus protocol D Power Supply Blank basic version 100 to 240 Vac dc input 24V 12 to 24 Vdc 24 Vac input voltage WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Отзывы: