The determination of the PID parameters (Pb, Ir and Dt) is described 
in the item DETERMINATION OF PID PARAMETERS of this manual. 

LBD - LOOP BREAK DETECTION ALARM 

The  parameter  defines  a  time  interval,  in  minutes,  within  which  the 
PV is expect to  react  to a control output signal. If the PV does not 
react  properly  within  the  time  interval  configured  in 

lbd.t

,  the 

controller  interprets  this  as  a  control  loop  break  and  signals  this 
occurrence in the display.  
A LBD event may be sent to any I/O channel. Simply configure the 

LDB

  function to the desired I/O channel: the selected output will be 

activated  when    a 

LDB

  condition  is  detected.  When  the 

lbd.t

 

parameter is programmed with 0 (zero), the 

LDB

 function is disabled. 

The 

LDB

 is useful in system supervision and troubleshooting, allowing 

early detection of problems in the actuator, power source or load. 

HBD - HEATER BREAK

 

DETECTION 

Available in the products identified with the suffix HBD. Visit our web 
site for further information 

www.novusautomation.com

SAFE OUTPUT VALUE WITH SENSOR FAILURE 

This function defines an output value (user defined) to be assigned to 
the control output in the event of a sensor failure. 
When the input sensor is identified as broken, the controller  forcing 
MV to assume the user configured value in the 

1E.ov

 parameter. 

When the parameter 

1E.ov

  is configured with 0.0 (zero) value, this 

function is disabled and the control output is simply turned off upon 
input sensor error. 

USB INTERFACE 

The USB interface is used for CONFIGURING or MONITORING the 
controller. The 

NConfig

 software must be used for the configuration. 

It  makes  it  possible  to  create,  view,  save  and  open  configurations 
from the equipment or files in your computer. The tool for saving and 
opening  configurations  in  files  makes  it  possible  to  transfer 
configurations  between  pieces  of  equipment  and  to  make  backup 
copies.  For  specific  models,  the 

NConfig

  software  also  makes  it 

possible  to  update  the  firmware  (internal  software)  of  the  controller 
through the USB. 

For MONITORING  purposes you can use any supervisory software 
(SCADA)  or  laboratory  software  that  supports  the  MODBUS  RTU 
communication on a serial communications port. When connected to 
the USB of a computer, the controller is recognized as a conventional 
serial  port  (COM  x).  Use  the 

NConfig

  software  or  consult  the 

DEVICE  MANAGER  in  the  Windows  CONTROL  PANEL  to  identify 
the  COM  port  that  was  assigned  to  the  controller.  Consult  the 
mapping of the MODBUS memory in the controller’s communications 
manual  and  the  documentation  of  your  supervisory  software  to 
conduct the MONITORING process. 

Follow  the  procedure  below  to  use  the  USB  communication  of  the 
equipment: 

 

Download the 

NConfig

 software from our website and install it on 

your  computer.  The  USB  drivers  necessary  for  operating  the 
communication will be installed together with the software. 

 

Connect  the  USB  cable  between  the  equipment  and  the 
computer.  The  controller  does  not  have  to  be  connected  to  a 
power supply. The USB will provide enough power to operate the 
communication (other equipment functions cannot operate). 

 

Open  the 

NConfig

  software,  configure  the  communication  and 

start recognition of the device. 

 

 

 

The  USB  interface  IS  NOT  SEPARATE  from  the 
signal input (PV) or the controller’s/indicator’s digital 
inputs and outputs. It is intended for temporary use 
during  CONFIGURATION  and  MONITORING 
periods.  For  the  safety  of  people  and  equipment,  it 
must  only  be  used  when  the  piece  of  equipment  is 
completely  disconnected  from  the  input/output 
signals.  Using  the  USB  in  any  other  type  of 
connection is possible but requires a careful analysis 
by  the  person  responsible  for  installing  it.  When 
MONITORING  for  long  periods  of  time  and  with 
connected inputs and outputs, we recommend using 
the RS485 interface, which is available or optional in 
most of our products. 

INSTALLATION / CONNECTIONS 

The controller must be fastened on a panel, following the sequence 

of steps described below: 

 

Prepare a panel cut-out of 45.5 x 45.5 mm; 

 

Remove the mounting clamps from the controller; 

 

Insert the controller into the panel cut-out; 

 

Slide  the  mounting  clamp  from  the  rear  to  a  firm  grip  at  the 
panel. 

RECOMMENDATIONS FOR THE INSTALLATION  

 

All electrical connections are made to the screw terminals at the 
rear of the controller. They accept wire sizes from 0.5 to 1.5 mm

2

 

(16 to 22 AWG).  The terminals should be tightened to a torque 

of 0.4 Nm (3.5 lb in) 

 

To minimize the pick-up of electrical noise, the low voltage DC 
connections and the sensor input wiring should be routed away 
from  high-current  power  conductors.  If  this  is  impractical,  use 

shielded cables. In general, keep cable lengths to a minimum. 

 

All  electronic  instruments  must  be  powered  by  a  clean  mains 

supply, proper for instrumentation.  

 

It  is  strongly  recommended  to  apply  RC'S  FILTERS  (noise 

suppressor) to contactor coils, solenoids, etc.  

 

In any application it is essential to consider what can happen when 
any part of the system fails. The controller features by themselves 
can not assure total protection.   

ELECTRICAL CONNECTIONS 

The controller's internal circuits can be removed without undoing the 
connections on the back panel.  
The  controller  complete  set  of  features  is  drawn  in 

Figure  1

.  The 

features loaded in a particular unit are shown on its label  

 

Figure 1

 - Connections of the back panel  

Содержание N1200

Страница 1: ...meters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments eac...

Страница 2: ...xecution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts freezes execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starti...

Страница 3: ...th this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal Available only for the inputs belonging to the group of linear analogic signals 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V ANALOG RETRANSMISSION OF PV AND SP The analog output when not used for control purposes is available for retransmitting the PV and SP value...

Страница 4: ... your supervisory software to conduct the MONITORING process Follow the procedure below to use the USB communication of the equipment Download the NConfig software from our website and install it on your computer The USB drivers necessary for operating the communication will be installed together with the software Connect the USB cable between the equipment and the computer The controller does not...

Страница 5: ... product specifications Figure 6a I O3 or I O4 with output pulse for SSR Figure 6b I O5 with output pulse for SSR I O3 I O4 and I O5 can also be configured as digital outputs I O3 and I O4 provide a 5 Vdc output signal whereas I O5 a 12 Vdc signal An example of usage is shown in Figure 6a for the I O3 and in Figure 6b for the I O5 I O5 is electrically isolated from the sensor input OPERATION The c...

Страница 6: ...ed 0 does not execute program 1 to 20 number of the program to be executed With enabled outputs RUN YES the program starts right after the program is selected p seg Screen for indication only When a ramp and soak program is active this parameter shows the number of the segment under execution from 1 to 9 t seg Screen for indication only When a ramp and soak program is in execution it shows the rem...

Страница 7: ...r up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 ALARM HYSTERESIS Defines the difference between the value of PV at which the alarm is xya2 xya3 xya4 triggered and the value at which it is turned off in engineering units A1t1 A2t1 A3t1 A4t1 Alarm Time t1 Defines the temporization time t1...

Страница 8: ...l I O 3 according to the Table 2 Io 4 Function of the channel I O 4 Selection of the function used in the channel I O 4 according to the Table 2 Io 5 Function of the channel I O 5 Selection of the function used in the channel I O 5 according to the Table 2 CALIBRATION CYCLE All of the input and output types are calibrated in the factory If a recalibration is required this should be carried out by ...

Страница 9: ...des the parameters on the protected levels If no password is entered the parameters of the protected cycles can only be visualized The Access Code is defined by the user in the parameter Password Change PAS present in the Calibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access...

Страница 10: ...itiated by the controller whenever the control performance is worse than the one found after the previous tuning In order to activate the performance supervision and auto adaptative tuning the parameter ATUN must be adjusted for SELF RSLF or TGHT The controller s behavior during the auto adaptative tuning will depend on the worsening of the present performance If the maladjustment is small the tun...

Страница 11: ...ignal that corresponds to a value a little lower than the upper limit of indication f Access the parameter inLC With the keys and adjust the display reading such as to match the applied signal Then press the P key Note When checking the controller calibration with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA e...

Страница 12: ...Vdc 24 Vac 10 20 Maximum consumption 9 VA ENVIRONMENTAL CONDITIONS Operation Temperature 5 to 50 C Relative Humidity 80 max 30 ºC For temperatures above 30 ºC reduce 3 for each ºC Internal Use Category of installation II Degree of pollution 2 altitude 2000 m INPUT T C Pt100 voltage and current according to Table 1 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 199...

Страница 13: ... Relay in I O3 DIO Digital I Os in I O3 and I O4 HBD Burnt Out Resistance detection C Digital Communication Blank basic version without serial communication 485 RS485 Modbus protocol D Power Supply Blank basic version 100 to 240 Vac dc input 24V 12 to 24 Vdc 24 Vac input voltage WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Отзывы: