Using the Alarm 1 as example. 

 

 

difk

  

– Alarm of Maximum Differential Value

 

 

Triggers when the value of PV is 

above

 the defined point by:  

(SP + SPA1) 

Using the Alarm 1 as example.

 

SCREEN 

TYPE 

ACTUATION  

Off 

Inoperative  

Output is not used as alarm.  

Ierr 

Open sensor  

(

i

nput 

Err

or) 

Activated  when  the  input  signal  of  PV  is 

interrupted, out of the range limits or Pt100 
in short-circuit.  

Rs 

Event (

r

amp and 

S

oak)  

Activated in a specific segment of program.  

rfail 

 

Resist. burnt out 

(resistance 

fail

)  

Signals a failure in the heating element.   

Lo 

 Minimum value 

(

Lo

w)  

 

SPAn 

PV 

 

Ki 

Maximum value 

(

Hi

gh)  

 

SPAn 

PV 

 

Dif 

Differential 

(

diF

erential) 

 

SV 

PV 

SV + SPAn 

alarme 

SV - SPAn 

alarme 

 

 

SV 

PV 

SV - SPAn 

alarme 

SV + SPAn 

alarme 

 

Positive SPAn    

Negative SPAn    

Difl 

Minimum 

Differential 

(

diF

erential 

L

ow)  

Positive SPAn       Negative SPAn  

 

SV 

PV 

SV - SPAn 

   

 

SV 

PV 

SV - SPAn 

 

Difk 

Maximum 

differential 

(

diF

erential 

H

igh)  

 

SV 

PV 

SV + SPAn 

 

 

SV 

PV 

SV + SPAn 

 

Positive SPAn    

Negative SPAn    

Table 3

 – Alarm Functions  

Where  SPAn  refers  to  Setpoints  of  Alarm  “

SPA1

”,  “

SPA2

”, 

SPA3

” and “

SPA4

”. 

ALARM TIMER MODES 

The controller alarms can be configured to perform 3 timer modes:  

 

One pulse with defined duration; 

 

Delayed  activation; 

 

Repetitive pulses; 

The illustrations in 

Table 4

 show the behavior of the alarm output for 

various combinations of times t1 and t2. The timer functions can be 
configured in parameters 

A1t1

A1t2

A2t1

A2t2

A3t1

A3t2

A4t1

 and 

A4t2

OPERATION 

T 1 

T 2 

ACTION  

Normal 

Operation 

 

Alarm Event 

Alarm 

Output 

 

Activation for 

a defined time  1 to 6500 s 

Alarm Event

Alarm

Output

T1

 

Activation with 

delay  

1 to 6500 s 

Alarm Event

Alarm

Output

T2

 

Intermittent 

Activation   1 to 6500 s  1 to 6500 s 

Alarm Event

Alarm

Output
alarme

T1

T2

T1

 

Table 4

 – Temporization Functions for the Alarms 

 

 

The  LEDs  associated  to  the  alarms  will  light  when  the  alarm 
condition is recognized, not following the actual state of the output, 
which may be temporarily OFF because of the temporization. 

 

 

INITIAL BLOCKING OF ALARM  

The initial blocking option inhibits the alarm from being recognized if 
an alarm condition is present when the controller is first energized (or 
after  a  transition  from  run  YES 

NO).  The  alarm  will  be  enabled 

only after the occurrence of a non-alarm condition followed by a new 
occurrence for the alarm. 
The initial blocking is useful, for instance, when one of the alarms is 
configured as a minimum value alarm, causing the activation of the 
alarm  soon  upon  the  process  start-up,  an  occurrence  that  may  be 
undesirable.  
The initial blocking is disabled for the sensor break alarm function. 

EXTRACTION OF THE SQUARE ROOT 

With this feature enabled the controller uses for display and control a 
value that corresponds to the square root of the applied input signal.  
Available only for the inputs belonging to the group of linear analogic 
signals: 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V. 

ANALOG RETRANSMISSION OF PV AND SP  

The analog output, when not used for control purposes, is available 
for  retransmitting  the  PV  and  SP  values  in  0-20  or  4-20  mA.  This 
analog output is electrically isolated from other inputs and outputs. 
The analog output signal is scalable, with the output range defined by 
the values programmed in the parameters “

rtLL

” and “

rtkL

”. 

To obtain a voltage output, the user must install a resistor shunt (550 



max.)  to  the  current  output  terminals  (terminals  7  and  8).  The 

actual resistor value depends on the desired output voltage span. 
There  is 

no  electrical  isolation

  between  serial  communication 

(RS485) and channel I/O5. 

SOFT-START 

The soft-start feature avoids abrupt variations in the power delivered 
to the load regardless of the system power demand. .  
This is accomplished by defining a limiting ramp for the control output. 
The output is allowed to reach maximum value (100 %) only after the 
time programmed in the soft-start  parameter  has  elapsed.   The Soft-
start function is generally used in processes that require slow start-up, 
where the instantaneous application of 100 % of the available power to 
the load may cause damages to parts of the system.  
In  order  to  disable  this  function,  the  soft-start  parameter  must  be 
configured with 0 (zero). 

REMOTE SETPOINT  

The  controller  can  have  its  Setpoint  value  defined  by  an  analog, 
remotely  generated  signal.  This  feature  is  enabled  through  the 
channels  I/O3,  I/O4  or  I/O5  when  configured  as  digital  inputs  and 
configured  with the function 

rsp

 (Remote SP selection) or through 

the parameter 

E.rsp

. The remote setpoint input accepts the signals 

0-20 mA, 4-20 mA, 0-5 V and 0-10 V.  
For  the  signals  of  0-20  and  4-20  mA,  a  shunt  resistor  of 

100 

  is 

required between terminals 9 and 10, as shown in 

Figure 4c

.  

CONTROL MODE 

The controller can operate in two different manners: Automatic mode 
or Manual mode. In automatic mode the controller defines the amount 
of power to be applied on the process, based on defined parameters 
(SP, PID, etc.).  
In  the  manual  mode  the  user  himself  defines  this  amount  of  power. 
The parameter 

(trl

” defines the control mode to be adopted.  

PID AUTOMATIC MODE  

For the Automatic mode, there are two different strategies of control: 
PID control and ON/OFF control.  
PID control has its action based on a control algorithm that takes into 
account the deviation of PV with respect to SP, the rate of change of 
PV and the steady state error.   
On  the  other  hand,  the  ON/OFF  control  (obtained  when  Pb=0) 
operates with 0 % or 100 % of power, when PV deviates from SP.  

Содержание N1200

Страница 1: ...meters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments eac...

Страница 2: ...xecution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts freezes execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starti...

Страница 3: ...th this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal Available only for the inputs belonging to the group of linear analogic signals 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V ANALOG RETRANSMISSION OF PV AND SP The analog output when not used for control purposes is available for retransmitting the PV and SP value...

Страница 4: ... your supervisory software to conduct the MONITORING process Follow the procedure below to use the USB communication of the equipment Download the NConfig software from our website and install it on your computer The USB drivers necessary for operating the communication will be installed together with the software Connect the USB cable between the equipment and the computer The controller does not...

Страница 5: ... product specifications Figure 6a I O3 or I O4 with output pulse for SSR Figure 6b I O5 with output pulse for SSR I O3 I O4 and I O5 can also be configured as digital outputs I O3 and I O4 provide a 5 Vdc output signal whereas I O5 a 12 Vdc signal An example of usage is shown in Figure 6a for the I O3 and in Figure 6b for the I O5 I O5 is electrically isolated from the sensor input OPERATION The c...

Страница 6: ...ed 0 does not execute program 1 to 20 number of the program to be executed With enabled outputs RUN YES the program starts right after the program is selected p seg Screen for indication only When a ramp and soak program is active this parameter shows the number of the segment under execution from 1 to 9 t seg Screen for indication only When a ramp and soak program is in execution it shows the rem...

Страница 7: ...r up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 ALARM HYSTERESIS Defines the difference between the value of PV at which the alarm is xya2 xya3 xya4 triggered and the value at which it is turned off in engineering units A1t1 A2t1 A3t1 A4t1 Alarm Time t1 Defines the temporization time t1...

Страница 8: ...l I O 3 according to the Table 2 Io 4 Function of the channel I O 4 Selection of the function used in the channel I O 4 according to the Table 2 Io 5 Function of the channel I O 5 Selection of the function used in the channel I O 5 according to the Table 2 CALIBRATION CYCLE All of the input and output types are calibrated in the factory If a recalibration is required this should be carried out by ...

Страница 9: ...des the parameters on the protected levels If no password is entered the parameters of the protected cycles can only be visualized The Access Code is defined by the user in the parameter Password Change PAS present in the Calibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access...

Страница 10: ...itiated by the controller whenever the control performance is worse than the one found after the previous tuning In order to activate the performance supervision and auto adaptative tuning the parameter ATUN must be adjusted for SELF RSLF or TGHT The controller s behavior during the auto adaptative tuning will depend on the worsening of the present performance If the maladjustment is small the tun...

Страница 11: ...ignal that corresponds to a value a little lower than the upper limit of indication f Access the parameter inLC With the keys and adjust the display reading such as to match the applied signal Then press the P key Note When checking the controller calibration with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA e...

Страница 12: ...Vdc 24 Vac 10 20 Maximum consumption 9 VA ENVIRONMENTAL CONDITIONS Operation Temperature 5 to 50 C Relative Humidity 80 max 30 ºC For temperatures above 30 ºC reduce 3 for each ºC Internal Use Category of installation II Degree of pollution 2 altitude 2000 m INPUT T C Pt100 voltage and current according to Table 1 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 199...

Страница 13: ... Relay in I O3 DIO Digital I Os in I O3 and I O4 HBD Burnt Out Resistance detection C Digital Communication Blank basic version without serial communication 485 RS485 Modbus protocol D Power Supply Blank basic version 100 to 240 Vac dc input 24V 12 to 24 Vdc 24 Vac input voltage WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Отзывы: