Novus N1200 Скачать руководство пользователя страница 7

Controller N1200  

NOVUS AUTOMATION 

7 / 13 

ovkl 

Output High 

Limit 

Upper  limit  for  the  control  output  -  Maximum 
percentage  for  the  control  output  when  in 
automatic mode and in PID.   Typically configured 
with 

100 %

. Default value: 100 % 

sfst 

Softstart

 

SoftStart

 Function –

Time in seconds during which 

the  controller  limits  the  MV  value  progressively 
from 0 to 100 %. It is enabled at power up or when 
the control output is activated. If in doubt set zero 
(zero value disables the Soft start function). 

Sp.a1

 

Sp.a2 
Sp.a3 
Sp.a4 

ALARM SETPOINT: Tripping point for alarm 1, 2, 3 
and 4. Value that defines the point of activation for 
the programmed alarms with the functions “

Lo

” or 

ki

”. 

For  the  alarms  configured  with 

Differential

  type 

functions, this parameter defines deviation (band).  
Not used for the other alarm functions.  

CYCLE OF PROGRAMS  

Pr.tb 

Program time 

base 

Defines the time base that will be used by all Ramp 
& Soak programs.  

 

Se( 

- Time basis in seconds;  

 

Min 

  - Time basis in minutes;  

Pr n 

Program 

number

 

Selects  the  ramp  and  soak  profile  program  to  be 
edited/viewed.  The  sequence  of  parameters  that 
follows  refer  to  this  selected  program.    Total  of  20 

programs possible.  

Ptol 

Program 

Tolerance 

Maximum  admitted  deviation  of  PV  with  respect  to 
SP. If exceeded, the program execution is suspended 
(the  internal  timer  freezes)  until  the  deviation  be 

returns back within the defined tolerance. 
The  value  0  (zero)  disables  the  function  (the 
program  progresses  regardless  of  the  difference 

between PV and SP).  

Psp0

 

Psp9 

Program SP’s, 0 to 9: Group of 10 values of SP that 
define the Ramp and Soak profile segments.  

Pt1

 

Pt9 

Segments  durations,  1  to  9:  Defines  the  time  of 
duration, in second  or  minutes,  of the segments of 

the program being edited.  

Pe1

 

Pe9 

Program event

 

Alarms  of  Event,  1  to  9:  Parameters  that  define 
which  alarms  are  to  be  activated  during  the 
execution of a certain program segment. The alarms 
chosen  must  have  its  function  configured  as  “

rS

.” 

(See 

Table 3

Lp 

Link Program

 

Link Programs: Number of the next profile program 
to  be  linked  following  the  current  program.  Profiles 
can  be  linked  together  to  produce  larger  programs 
of up to 180 segments

.

  

 

0

 – do not link to any other program.  

CYCLE OF ALARMS: 

Fva1 
Fva2 
Fva3 
Fva4 

FUNCTIONS  OF  ALARMS  1  to  4.  Defines  the 
functions for the alarms among the  options of the 

Table 3

.  

bla1 
bla2 
bla3 
bla4 

BLOCK  ALARM  1  TO  4:  This  function  blocks  the 
alarms when the controller is energized. 

YES

 - enables initial blocking  

 

NO

  - inhibits initial blocking  

When  enabled,  the  alarm  will  not  be  active  at 
power-up,  waiting  for  PV  (Process  Variable)  to 
reach a non-alarm situation. From this point on the 
alarm  will  be  free  to  actuate  should  a  new  alarm 
situation occur. 

xya1 

ALARM  HYSTERESIS

Defines  the  difference 

between  the  value  of  PV  at  which  the  alarm  is 

xya2 
xya3 
xya4 

triggered and the value at which it is turned off (in 
engineering units). 

A1t1 
A2t1 
A3t1 
A4t1 

Alarm Time

 

t1

 

Defines the temporization time 

t1

, in seconds, for 

the  alarms.  Defines  the  temporization  time 

t1

,  in 

seconds, for the alarms time functions. The value 0 
(zero) disables the function.   
Refer  to 

Table  4

  for  configuring  this  parameter 

timed  functions.  The  value  0  (zero)  disables  the 
function.  
Refer to 

Table 4

 for configuring this parameter. 

A1t2 
A2t2 
A3t2 
A4t2 

Alarm Time 

t2. 

Defines the temporization time 

t2

in  seconds,  for  the  alarms  time  functions.  The 
value 0 (zero) disables the function. Refer to 

Table 

4

 for configuring this parameter 

flsh 

Flash

 

Allows visual signalization of an alarm occurrence 
by  flashing  the  indication  of  PV  in  the  operation 
level.  The  user  chooses  which  alarms  are  to  be 
associated with this feature. 

CYCLE OF SCALE  

Type 

Type

 

INPUT  TYPE:  Selects  the  input  signal  type  to  be 
connected  to  the  process  variable  input.  Refer  to 

Table 1

 for the available options. 

fltr 

Filter

 

Digital Input Filter - Used to improve the stability of 
the  measured  signal  (PV).  Adjustable  between  0 
and 20. In 0 (zero) it means filter turned off and 20 
means maximum filter. The higher the filter value, 
the slower is the response of the measured value.  

Dppo 

Decimal Point

 

Selects the decimal point position to be viewed in 
both PV and SP

.

  

vnI t 

Unit. 

Temperature indication in ºC or ºF:   

root 

Square Root

 

Square  Root  Function.  Applies  the  quadratic 
function  on  the  input  signal,  within  the  limits 
programmed in “

SPLl

” and “

spkL

.”  

 

YES 

  Enables the Function  

 

no

   

Does not enable the Function  

The indication assumes the lower limit value when 
the input signal is below 1 % of programmed span.  
Parameter available for lineal inputs only.  

0ffs 

Offset

 

SENSOR  OFFSET:  Offset  value  to  be  added  to 
the PV reading to compensate sensor error.  
Default value: zero.  

e.rsp 

Enable Remote 

SP

 

Enables remote SP.  

 

YES 

  Enables the Function  

 

no

   

Does not enable the Function  

This  parameter  is  not  displayed  when  the  remote 
SP selection is defined by a Digital Input.  

rsp 

Remote SP 

type

 

Defines the signal type for the remote SP.  

 

0-20

  current of 0-20 mA  

 

4-20

  current of 4-20 mA  

 

0-5

 

voltage of 0-5 V 

 

 

0-10

  voltage of 0-10 V  

Parameter displayed when remote SP is enabled.  

rsll 

Remote SP 

Low Limit

 

REMOTE  SETPOINT  LOW  LIMIT:  used  in 
conjunction with the 

rSxL

, scales the remote SP 

input  defining  the  initial  value  in  the  remote  SP 
indication range. 
Parameter displayed when remote SP is enabled.  

Содержание N1200

Страница 1: ...meters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments eac...

Страница 2: ...xecution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts freezes execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starti...

Страница 3: ...th this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal Available only for the inputs belonging to the group of linear analogic signals 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V ANALOG RETRANSMISSION OF PV AND SP The analog output when not used for control purposes is available for retransmitting the PV and SP value...

Страница 4: ... your supervisory software to conduct the MONITORING process Follow the procedure below to use the USB communication of the equipment Download the NConfig software from our website and install it on your computer The USB drivers necessary for operating the communication will be installed together with the software Connect the USB cable between the equipment and the computer The controller does not...

Страница 5: ... product specifications Figure 6a I O3 or I O4 with output pulse for SSR Figure 6b I O5 with output pulse for SSR I O3 I O4 and I O5 can also be configured as digital outputs I O3 and I O4 provide a 5 Vdc output signal whereas I O5 a 12 Vdc signal An example of usage is shown in Figure 6a for the I O3 and in Figure 6b for the I O5 I O5 is electrically isolated from the sensor input OPERATION The c...

Страница 6: ...ed 0 does not execute program 1 to 20 number of the program to be executed With enabled outputs RUN YES the program starts right after the program is selected p seg Screen for indication only When a ramp and soak program is active this parameter shows the number of the segment under execution from 1 to 9 t seg Screen for indication only When a ramp and soak program is in execution it shows the rem...

Страница 7: ...r up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 ALARM HYSTERESIS Defines the difference between the value of PV at which the alarm is xya2 xya3 xya4 triggered and the value at which it is turned off in engineering units A1t1 A2t1 A3t1 A4t1 Alarm Time t1 Defines the temporization time t1...

Страница 8: ...l I O 3 according to the Table 2 Io 4 Function of the channel I O 4 Selection of the function used in the channel I O 4 according to the Table 2 Io 5 Function of the channel I O 5 Selection of the function used in the channel I O 5 according to the Table 2 CALIBRATION CYCLE All of the input and output types are calibrated in the factory If a recalibration is required this should be carried out by ...

Страница 9: ...des the parameters on the protected levels If no password is entered the parameters of the protected cycles can only be visualized The Access Code is defined by the user in the parameter Password Change PAS present in the Calibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access...

Страница 10: ...itiated by the controller whenever the control performance is worse than the one found after the previous tuning In order to activate the performance supervision and auto adaptative tuning the parameter ATUN must be adjusted for SELF RSLF or TGHT The controller s behavior during the auto adaptative tuning will depend on the worsening of the present performance If the maladjustment is small the tun...

Страница 11: ...ignal that corresponds to a value a little lower than the upper limit of indication f Access the parameter inLC With the keys and adjust the display reading such as to match the applied signal Then press the P key Note When checking the controller calibration with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA e...

Страница 12: ...Vdc 24 Vac 10 20 Maximum consumption 9 VA ENVIRONMENTAL CONDITIONS Operation Temperature 5 to 50 C Relative Humidity 80 max 30 ºC For temperatures above 30 ºC reduce 3 for each ºC Internal Use Category of installation II Degree of pollution 2 altitude 2000 m INPUT T C Pt100 voltage and current according to Table 1 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 199...

Страница 13: ... Relay in I O3 DIO Digital I Os in I O3 and I O4 HBD Burnt Out Resistance detection C Digital Communication Blank basic version without serial communication 485 RS485 Modbus protocol D Power Supply Blank basic version 100 to 240 Vac dc input 24V 12 to 24 Vdc 24 Vac input voltage WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Отзывы: