NOVUS AUTOMATION 

1 / 13 

 

 

Controller N1200 

UNIVERSAL CONTROLLER - INSTRUCTIONS MANUAL – V2.0x C 

SAFETY ALERTS 

The symbols below are used on the equipment and throughout this 
document  to  draw  the  user’s  attention  to  important  operational  and 
safety information. 

 

 

CAUTION: 

Read the manual thoroughly 

before installing and operating the 

equipment.  

CAUTION OR DANGER:  

Electrical Shock Hazard 

All  safety  related  instructions  that  appear  in  the  manual  must  be 
observed to ensure personal safety and to prevent damage to either 
the instrument or the system. 

If the instrument is used in a manner 

not  specified  by  the  manufacturer,  the  protection  provided  by  the 
equipment may be impaired. 

INTRODUCTION 

The N1200 is an extraordinarily versatile process controller. It holds 
in  one  single  instrument  all  the  main  features  needed  for  the  vast 
majority of industrial processes. It accepts in a single model virtually 
all  the  sensors  and  signals  used  in  the  industry  and  provides  the 
main output types required for the operation of diverse processes.  
The  configuration  can  be  performed  directly  on  the  controller  or 
through  the  USB  interface.  The 

NConfig

  software  (free)  is  the 

configuration management tool. Connected to the USB of a Windows 
computer,  the  controller  is  recognized  as  a  serial  communications 
port (COM) running with a Modbus RTU protocol. 
Through  the  USB  interface,  even  if  disconnected  from  the  power 
supply, the configuration performed in a piece of equipment can be 
can be saved in a file and repeated in other pieces of equipment that 
require the same configuration. 
It is important that the users read carefully this manual before using 
the  controller.  Verify  if  the  release  of  this  manual  matches  the 
instrument version (the firmware version is shown when the controller 
is energized). The N1200 main characteristics are: 

 

Multi-sensor universal input; 

 

Protection for open sensor in any condition; 

 

Relay,  4-20  mA  and  logic  pulse  control  outputs  all  available  in 

the standard model; 

 

Self-tuning of PID parameters; 

 

Automatic / Manual function with “

bumpless”  

transfer; 

 

  Four modes of independents alarms, with functions of minimum, 

  maximum, differential (deviation), open sensor and event; 

 

Timer functions that can be associated to the alarms; 

 

Retransmission of PV or SP in 0-20 mA or 4-20 mA; 

 

Input for remote 

setpoint

 

Digital input with 5 functions; 

 

Programmable 

soft-start

 

20  setpoint  profile  programs  with  9  segments  each,  with  the 

ability to be linked together for a total of 180 segments; 

 

Password for parameters protection; 

 

Universal power supply. 

CONFIGURATION / FEATURES  

INPUT TYPE SELECTION 

Select the input type (in parameter “

tYPE

”) from 

Table 1

 below. 

TYPE 

CODE 

RANGE OF MEASUREMENT  

Tc j 

Range: -110 to 950 ºC (-166 to 1742 ºF) 

Tc k 

Range: -150 to 1370 ºC (-238 to 2498 ºF) 

Tc t 

Range: -160 to 400 ºC (-256 to 752 ºF) 

Tc n 

Range: -270 to 1300 ºC (-454 to 2372 ºF) 

Tc r 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc s 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc b 

Range: 400 to 1800 ºC (752 to 3272 ºF) 

Tc e 

Range: -90 to 730 ºC (-130 to 1346 ºF) 

Pt100 

Pt 

Range: -200 to 850 ºC (-328 to 1562 ºF) 

0-20 mA 

L0.20 

Linear Signals  

Programmable indication from -1999 to 9999. 

4-20 mA 

L4.20 

0–50 mV 

L0.50 

0-5 Vdc 

L0.5 

0-10 Vdc 

L0.10 

4-20 mA 

NON 

LINEAR 

ln j 

Non Linear Analog Signals  

Indication range depends on the selected sensor 

Ln k 

ln t 

ln n 

ln r 

ln s 

ln b 

ln E 

Ln.Pt 

Table 1

 - Input types 

Note:

 All input types are factory calibrated. 

CONFIGURATION OF OUTPUTS, ALARMS AND DIGITAL INPUTS  

The controller input and output channels (I / O) can assume multiple 
functions:  control  output,  digital  input,  digital  output,  alarm  output, 
retransmission of PV and SP. These channels are identified as 

I / O 

1, I / O 2, I / O 3, I / O 4 

and

 I / O 5

The basic controller model comes loaded with the following features: 
 

I / O 1-  output to Relay SPST-NA; 

 

I / O 2-  output to Relay SPST-NA; 
I / O 5-  current output, digital output, digital input; 

Optionally

, other features can  be added, as shown  under the item 

“Identification” in this manual: 

3R

I / O3 with output to SPDT relay; 

DIO

:   I / O3 and I / O4 as digital input and output channels; 

HBD

:   Heater break detect; 

485

:  Serial Communication; 

The function to be used in each channel of I/O is defined by the user 
in accordance with the options shown in the 

Table 2

 

 

 

Содержание N1200

Страница 1: ...meters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments eac...

Страница 2: ...xecution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts freezes execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starti...

Страница 3: ...th this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal Available only for the inputs belonging to the group of linear analogic signals 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V ANALOG RETRANSMISSION OF PV AND SP The analog output when not used for control purposes is available for retransmitting the PV and SP value...

Страница 4: ... your supervisory software to conduct the MONITORING process Follow the procedure below to use the USB communication of the equipment Download the NConfig software from our website and install it on your computer The USB drivers necessary for operating the communication will be installed together with the software Connect the USB cable between the equipment and the computer The controller does not...

Страница 5: ... product specifications Figure 6a I O3 or I O4 with output pulse for SSR Figure 6b I O5 with output pulse for SSR I O3 I O4 and I O5 can also be configured as digital outputs I O3 and I O4 provide a 5 Vdc output signal whereas I O5 a 12 Vdc signal An example of usage is shown in Figure 6a for the I O3 and in Figure 6b for the I O5 I O5 is electrically isolated from the sensor input OPERATION The c...

Страница 6: ...ed 0 does not execute program 1 to 20 number of the program to be executed With enabled outputs RUN YES the program starts right after the program is selected p seg Screen for indication only When a ramp and soak program is active this parameter shows the number of the segment under execution from 1 to 9 t seg Screen for indication only When a ramp and soak program is in execution it shows the rem...

Страница 7: ...r up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 ALARM HYSTERESIS Defines the difference between the value of PV at which the alarm is xya2 xya3 xya4 triggered and the value at which it is turned off in engineering units A1t1 A2t1 A3t1 A4t1 Alarm Time t1 Defines the temporization time t1...

Страница 8: ...l I O 3 according to the Table 2 Io 4 Function of the channel I O 4 Selection of the function used in the channel I O 4 according to the Table 2 Io 5 Function of the channel I O 5 Selection of the function used in the channel I O 5 according to the Table 2 CALIBRATION CYCLE All of the input and output types are calibrated in the factory If a recalibration is required this should be carried out by ...

Страница 9: ...des the parameters on the protected levels If no password is entered the parameters of the protected cycles can only be visualized The Access Code is defined by the user in the parameter Password Change PAS present in the Calibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access...

Страница 10: ...itiated by the controller whenever the control performance is worse than the one found after the previous tuning In order to activate the performance supervision and auto adaptative tuning the parameter ATUN must be adjusted for SELF RSLF or TGHT The controller s behavior during the auto adaptative tuning will depend on the worsening of the present performance If the maladjustment is small the tun...

Страница 11: ...ignal that corresponds to a value a little lower than the upper limit of indication f Access the parameter inLC With the keys and adjust the display reading such as to match the applied signal Then press the P key Note When checking the controller calibration with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA e...

Страница 12: ...Vdc 24 Vac 10 20 Maximum consumption 9 VA ENVIRONMENTAL CONDITIONS Operation Temperature 5 to 50 C Relative Humidity 80 max 30 ºC For temperatures above 30 ºC reduce 3 for each ºC Internal Use Category of installation II Degree of pollution 2 altitude 2000 m INPUT T C Pt100 voltage and current according to Table 1 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 199...

Страница 13: ... Relay in I O3 DIO Digital I Os in I O3 and I O4 HBD Burnt Out Resistance detection C Digital Communication Blank basic version without serial communication 485 RS485 Modbus protocol D Power Supply Blank basic version 100 to 240 Vac dc input 24V 12 to 24 Vdc 24 Vac input voltage WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Отзывы: