N1040 Controller  

NOVUS AUTOMATION   

6/7 

CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION 
Two parameters must be configured for using the serial type: 

bavd

:  Communication speed. 

addr

:  Communication address for the controller. 

REDUCED REGISTERS TABLE  

FOR SERIAL COMMUNICATION

 

Communication Protocol 
The MOSBUS RTU slave is implemented. All configurable 

parameters can be accessed for reading or writing through the 

communication port. Broadcast commands are supported as well 

(address 0). 
The available Modbus commands are: 

03 - 

Read Holding Register

 

06 - 

Preset Single Register

 

                          05 - 

Force Single Coil

 

Holding Registers Table 
Follows a description of the usual communication registers. For full 

documentation download the Registers Table for Serial 

Communication in the N1040 section of our website – 

www.novusautomation.com

All registers are 16 bit signed integers.  

Address  Parameter 

Register Description 

0000 

Active SP   Read: Active control SP (main SP, from 

ramp and soak or from remote SP). 
Write: To main SP. 
Range: from 

spll

 to 

spkl

0001 

PV 

Read: Process Variable. 
Write: Not allowed. 
Range: Minimum value is the one 

configured in 

spll

  and the maximum 

value is the one configured in 

spkl

Decimal point position depends on 

dppo

 

value. 
In case of temperature reading, the value 

read is always multiplied by 10, 

independently of 

dppo

 value. 

0002 

MV 

Read: Output Power in automatic or 

manual mode. 
Write: Not allowed. See address 29. 
Range: 0 to 1000 (0.0 to 100.0 %). 

IDENTIFICATION 

N1040 -  

A -  

B - 

C 

A:  Outputs Features 
  PR:   OUT1= Pulse / OUT2= Relay 
  PRR:  OUT1= Pulse / OUT2=OUT3= Relay 
  PRRR:  OUT1= Pulse / OUT2=OUT3= OUT4= Relay 
B:  Digital Communication 
  485: Available RS485 digital communication 
C:  Power Supply electric 
  (Blank):   100~240 Vac / 48~240 Vdc; 50~60 Hz 
  24V:     12~24 Vdc / 24 Vac 

SPECIFICATIONS 

DIMENSIONS: ............................................................ 48 x 48 x 80 mm 

Cut-out in the panel: ..................... 45.5 x 45.5 mm (+0.5 -0.0 mm) 
Approximate Weight: ...............................................................75 g 

POWER SUPPLY
  Model standard: ....................... 100 to 240 Vac (±10 %), 50/60 Hz 
   ................................................................... 48 to 240 Vdc (±10 %)  
  Model 24 V: ......................  12 to 24 Vdc / 24 Vac (-10 % / +20 %) 
  Maximum consumption: ........................................................  6 VA 
ENVIRONMENTAL CONDITIONS

Operation Temperature: ...............................................  0 to 50 °C 
Relative Humidity:................................................... 80 % @ 30 °C 
For temperatures above 30 °C, reduce 3 % for each °C 
Internal use; Category of installation II, Degree of pollution 2;  

altitude < 2000 meters 

INPUT ...... Thermocouples JKT and Pt100 (according of Table 01

Internal Resolution:...................................... 32767 levels (15 bits) 
Resolution of Display: ......... 12000 levels (from -1999 up to 9999) 
Rate of Input Reading: .................................. up 10 per second (*) 
Precision:  . Thermocouples J, K, T: 0,25 % of the span 

±

1 °C (**) 

 ................................................................ Pt100: 0,2 % of the 

span 

Input Impedance: .................. Pt100 and thermocouples: > 10 M

 

Measurement of Pt100: ......................... 3-wire type, (

α

=0.00385) 

With compensation for cable length, excitation current of 0.170 mA. 
(*) Value adopted when the Digital Filter parameter is set to 0 

(zero) value. For Digital Filter values other than 0, the Input 

Reading Rate value is 5 samples per second. 
(**) The use of thermocouples requires a minimum time interval 

of 15 minutes for stabilization. 

OUTPUTS:  

OUT1: .................................................. Voltage pulse, 5 V / 25 mA 
OUT2: ................................ Relay SPST; 1.5 A / 240 Vac / 30 Vdc 
OUT3: ................................ Relay SPST; 1.5 A / 240 Vac / 30 Vdc 
OUT4: ................................... Relay SPDT; 3 A / 240 Vac / 30 Vdc 

FRONT PANEL:  ......................... IP65, Polycarbonate (PC) UL94 V-2 
ENCLOSURE
: .............................................. IP20, ABS+PC UL94 V-0 
ELECTROMAGNETIC COMPATIBILITY: ............... EN 61326-1:1997  

and EN 61326-1/A1:1998 
EMISSION: ............................................................ CISPR11/EN55011 
IMMUNITY: ...................... EN61000-4-2, EN61000-4-3, EN61000-4-4,  

EN61000-4-5, EN61000-4-6, EN61000-4-8 and EN61000-4-11 
SAFETY: .......................... EN61010-1:1993 and EN61010-1/A2:1995 
SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS; 
PROGRAMMABLE CYCLE OF PWM: 
From 0.5 up 100 seconds. 
STARTS UP OPERATION: 
After 3 seconds connected to the power 

supply. 
CERTIFICATION:      
and   

 

SAFETY INFORMATION 

Any control system design should take into account that any part of 

the system has the potential to fail. This product is not a protection or 

safety device and its alarms are not intended to protect against 

product failures. Independent safety devices should be always 

provided if personnel or property are at risk. 
Product performance and specifications may be affected by its 

environment and installation. It’s user’s responsibility to assure 

proper grounding, shielding, cable routing and electrical noise 

filtering, in accordance with local regulations, EMC standards and 

good installation practices. 

Содержание N1040

Страница 1: ...ted away from high current power conductors If this is impractical use shielded cables In general keep cable lengths to a minimum All electronic instruments must be powered by a clean mains supply pro...

Страница 2: ...l in minutes within which the PV is expect to react to a control output signal If the PV does not react properly within the time interval configured in lbd t the controller interprets this as a contro...

Страница 3: ...he parameter PASS precedes the first parameter in the level where the protection becomes active See section Configuration Protection DESCRIPTION OF THE PARAMETERS OPERATION CYCLE PV SP PV Indication s...

Страница 4: ...a recalibration is required it shall be carried out by a specialized professional In case this cycle is accidentally accessed do not perform alteration in its parameters pass Password This parameter...

Страница 5: ...ntenance service CALIBRATION OF THE INPUT All inputs are factory calibrated and recalibration should only be done by qualified personnel If you are not familiar with these procedures do not attempt to...

Страница 6: ...tion 6 VA ENVIRONMENTAL CONDITIONS Operation Temperature 0 to 50 C Relative Humidity 80 30 C For temperatures above 30 C reduce 3 for each C Internal use Category of installation II Degree of pollutio...

Страница 7: ...under normal use and service within one 1 year from the date of shipment from factory or from its official sales channel to the original purchaser NOVUS liability under this warranty shall not in any...

Отзывы: