background image

N1040 Controller  

NOVUS AUTOMATION   

3/7 

OPERATION 

The controller’s front panel, with its parts, can be seen in the Fig. 02

 

Fig. 02 - Identification of the parts referring to the front panel 

Display:  Displays the measured variable, symbols of the 

configuration parameters and their respective values/conditions. 
COM Indicator: Flashes to indicate communication activity in the 

RS485 interface. 
TUNE Indicator: Stays ON while the controller is in tuning process. 
OUT Indicator: For relay or pulse control output; it reflects the actual 

state of the output. 
A1 and A2 Indicators: Signalize the occurrence of alarm situation. 
P Key: Used to walk through the menu parameters. 

 

  Increment key and 

 

  Decrement key: Allow altering the 

values of the parameters. 

 

 Back key: Used to retrocede parameters. 

STARTUP 
When the controller is powered up, it displays its firmware version for 

3 seconds, after which the controller starts normal operation. The 

value of PV and SP is then displayed and the outputs are enabled. 
In order for the controller to operate properly in a process, its 

parameters need to be configured first, such that it can perform 

accordingly to the system requirements. The user must be aware of 

the importance of each parameter and for each one determine a valid 

condition. 
The parameters are grouped in levels according to their functionality 

and operation easiness. The 5 levels of parameters are: 

1 – Operation / 2 – Tuning / 3 – Alarms / 4 – Input / 5 – Calibration 

The “P” key is used for accessing the parameters within a level. 
Keeping the “P” key pressed, at every 2 seconds the controller jumps 

to the next level of parameters, showing the first parameter of each 

level: 

PV  >>  

atvn

  >>  

fva1

  >>  

type

  >>  

pass

  >>  PV  … 

To enter a particular level, simply release the “P” key when the first 

parameter in that level is displayed. To walk through the parameters 

in a level, press the “P” key with short strokes. To go back to the 

previous parameter in a cycle, press 

 

Each parameter is displayed with its prompt in the upper display and 

value/condition in the lower display. Depending on the level of 

parameter protection adopted, the parameter PASS  precedes the 

first parameter in the level where the protection becomes active. See 

section Configuration Protection

DESCRIPTION OF THE PARAMETERS 

OPERATION CYCLE 

PV + SP 

PV Indication screen. On the higher display (red) the 

value of the measured variable (PV) temperature is 

shown. On the lower display (green), the control 

setpoint (SP) is shown.

 

Sp.a1

  

Sp.a2                             

Alarm  SP.  Value that defines the alarm activation 

point. For the alarms set up with the functions of the 

type Differential, these parameters define deviations. 
For the alarm function 

ierr

, this parameter is not used. 

Parameters shown in this level only when enabled in 

the parameters 

sp1.E

 and 

sp2.E

TUNING CYCLE 

Atvn 

 

AUTO-TUNE. Enables the auto-tuning function for the 

PID parameters (

pb

,

ir

dt

). Defines the control 

strategy to be taken:  

off

    - Turned off (no PID tuning);    

Fast 

- Automatic tuning; 

Full 

- More accurate automatic tuning.  

PB 

 

Proportional Band. Value of the term P of the control 

mode PID, in percentage of the maximum span of the 

input type. Adjust of between 0 and 500.0 %. 
When set to zero (0), control action is ON/OFF.  

ir 

 

Integral Rate. Value of the term I of the PID algorithm, 

in repetitions per minute (Reset). Adjustable between 0 

and 24.00. Displayed only if proportional band 

 0.  

dt 

 

Derivative Time. Value of the term D of the control mode 

PID, in seconds. Adjustable between 0 and 250.0 

seconds. Displayed only if proportional band 

 0. 

(t

 

 

Cycle time. Pulse Width Modulation (PWM) period in 

seconds. Adjustable between 0.5 and 100.0 seconds. 
Displayed only if proportional band 

 0. 

kyst 

 

Hysteresis. Is the hysteresis for ON/OFF control (set in 

temperature units). This parameter is only used when 

the controller is in ON/OFF mode (Pb=0). 

A(t 

 

Action Control: 

re

  Control with Reverse Action. Appropriate for 

heating. Turns control output on when PV is 

below SP. 

dir

  Control with Direct Action. Appropriate for 

cooling. Turns control output on when PV is 

above SP. 

sfst 

 

SoftStart Function. Time interval, in seconds, while the 

controller limits the control output (MV) rising rate

(Zero value disables the Soft Start function). 

0vt1 
0vt2 
0vt3 
0vt4 

Assign functions to the Output channels OUT1, OUT2, 

OUT3 and OUT4: 

Off

    - Not used; 

(trl 

- Control output; 

A1

    - Alarm 1 output; 

A2

    - Alarm 2 output; 

A1a2

   - Alarm 1 + Alarm2 (OR logic); 

Lbd

     - Loop Break Detect Alarm. 

Содержание N1040

Страница 1: ...ted away from high current power conductors If this is impractical use shielded cables In general keep cable lengths to a minimum All electronic instruments must be powered by a clean mains supply pro...

Страница 2: ...l in minutes within which the PV is expect to react to a control output signal If the PV does not react properly within the time interval configured in lbd t the controller interprets this as a contro...

Страница 3: ...he parameter PASS precedes the first parameter in the level where the protection becomes active See section Configuration Protection DESCRIPTION OF THE PARAMETERS OPERATION CYCLE PV SP PV Indication s...

Страница 4: ...a recalibration is required it shall be carried out by a specialized professional In case this cycle is accidentally accessed do not perform alteration in its parameters pass Password This parameter...

Страница 5: ...ntenance service CALIBRATION OF THE INPUT All inputs are factory calibrated and recalibration should only be done by qualified personnel If you are not familiar with these procedures do not attempt to...

Страница 6: ...tion 6 VA ENVIRONMENTAL CONDITIONS Operation Temperature 0 to 50 C Relative Humidity 80 30 C For temperatures above 30 C reduce 3 for each C Internal use Category of installation II Degree of pollutio...

Страница 7: ...under normal use and service within one 1 year from the date of shipment from factory or from its official sales channel to the original purchaser NOVUS liability under this warranty shall not in any...

Отзывы: