Outdoor Humidity Sensor

Step

Procedure

1

Connect the white (+) wire from the sensor to Lingo SE’s
Terminal 23 (+) at the Humidity Sensor input connections.

2

Connect the black (–) wire from the sensor to Lingo SE’s
Terminal 22 (–) at the Humidity Sensor input connections.

Demand Pulse Input

Step

Procedure

1

Connect the isolated contacts of a pulse-type utility meter or watt 
transducer to Terminals 28 (–) and 29 (+), labeled Demand Pulse
Input.

Phase Loss Sensor

Step

Procedure

1

Connect the normally open, dry contact output of an electrical
phase loss monitor to Terminals 30 (–) and 31 (+), labeled Phase
Loss Sensor Input.

Emergency Status Input

Step

Procedure

1

Connect the normally open, dry contact output of an emergency
monitoring system to Terminals 32 (–) and 33 (+), labeled
Emergency Status Input.

System Fault Output

Under normal operating conditions, a normally open set of contacts will be held
closed.  When an alarm occurs, the contacts open momentarily.  This signal
indicates a Lingo SE fault alarm.

Module Communications

Lingo SE can accept connections from 128 modules in Novar’s module network
without using a Network Expander Module.  (The maximum number of modules
is subject to software limitations.)  

A maximum of 32 modules can be connected to each of the A, B, C, and D
Module terminals (Terminals 1–12).  

NOTE!

Modules with the same physical addresses must not be
connected to the same port.  For example, modules with
addresses 00 and 64 have the same physical address, so they 
cannot both reside on the same COM port (A, B, C, or D).

6

DOC. #569066200—C  8/17/06

Lingo

®

 SE Baseplate Installation Instructions

Содержание Lingo SE

Страница 1: ...ol to cut energy costs increase comfort and reduce equipment maintenance This document provides instructions for mounting and wiring the Lingo SE baseplate and checking the installation Lingo SE Speci...

Страница 2: ...f the transformer for this module Make sure that the Lingo SE power cannot be switched off accidentally The Lingo SE requires continuous power for proper operation Mounting the Lingo SE Baseplate to t...

Страница 3: ...baseplate 4 Drill holes in the places marked on the wall 5 Install the hollow wall or other appropriate fasteners 6 Turn appropriate screws into the fasteners until approximately one quarter inch rem...

Страница 4: ...round 4 Apply power and check voltage at the 24 VAC terminals Voltage should be approximately 24 to 28 VAC 5 Turn off the power until needed 4 DOC 569066200 C 8 17 06 Lingo SE Baseplate Installation I...

Страница 5: ...r equivalent wiring Step Procedure 1 Connect the white wire from the sensor to the Lingo SE at Terminal 25 at the Outdoor Light Sensor input connections 2 Connect the black wire from the sensor to the...

Страница 6: ...an emergency monitoring system to Terminals 32 and 33 labeled Emergency Status Input System Fault Output Under normal operating conditions a normally open set of contacts will be held closed When an a...

Страница 7: ...inals 19 21 Step Procedure 1 Connect the black wire from the INCOM cable to Terminal 21 INCOM 2 2 Connect the white wire from the INCOM cable to Terminal 20 INCOM 1 3 Connect the shield wire from the...

Страница 8: ...net Direct Connect Crossover Cable 770077000 Logic One and Lingo are registered trademarks of Novar INCOM is a trademark of Eaton Cutler Hammer Ethernet is a registered trademark of Xerox Corporation...

Отзывы: