Outdoor Humidity Sensor
Step
Procedure
1
Connect the white (+) wire from the sensor to Lingo SE’s
Terminal 23 (+) at the Humidity Sensor input connections.
2
Connect the black (–) wire from the sensor to Lingo SE’s
Terminal 22 (–) at the Humidity Sensor input connections.
Demand Pulse Input
Step
Procedure
1
Connect the isolated contacts of a pulse-type utility meter or watt
transducer to Terminals 28 (–) and 29 (+), labeled Demand Pulse
Input.
Phase Loss Sensor
Step
Procedure
1
Connect the normally open, dry contact output of an electrical
phase loss monitor to Terminals 30 (–) and 31 (+), labeled Phase
Loss Sensor Input.
Emergency Status Input
Step
Procedure
1
Connect the normally open, dry contact output of an emergency
monitoring system to Terminals 32 (–) and 33 (+), labeled
Emergency Status Input.
System Fault Output
Under normal operating conditions, a normally open set of contacts will be held
closed. When an alarm occurs, the contacts open momentarily. This signal
indicates a Lingo SE fault alarm.
Module Communications
Lingo SE can accept connections from 128 modules in Novar’s module network
without using a Network Expander Module. (The maximum number of modules
is subject to software limitations.)
A maximum of 32 modules can be connected to each of the A, B, C, and D
Module terminals (Terminals 1–12).
NOTE!
Modules with the same physical addresses must not be
connected to the same port. For example, modules with
addresses 00 and 64 have the same physical address, so they
cannot both reside on the same COM port (A, B, C, or D).
6
DOC. #569066200—C 8/17/06
Lingo
®
SE Baseplate Installation Instructions