Supplying the Lingo SE
with Power

The Lingo SE is powered by a 24-VAC, 40 VA, Class 2 transformer (not
included—the transformer kit must be purchased separately).  The transformer
must be installed not more than 50 feet from the Lingo SE using minimum
18-gauge wire or mounted directly to the Lingo SE baseplate through the
knockouts on the sides of the assembly.  

Refer to Figure 2, as necessary, when installing the 24 VAC, Class 2 transformer.

Step

Procedure

1

Connect the blue and yellow leads from the transformer
secondary to the screw terminals labeled 24 VAC, Class 2, 40
VA, located on the Lingo SE terminal board.

2

Connect the transformer primary leads (white/black) to a
120-VAC source.

3

Connect the ground terminal (Terminal 36) to a suitable earth
ground.

4

Apply power and check voltage at the 24 VAC terminals.  

§

Voltage should be approximately 24 to 28 VAC.

5

Turn off the power until needed.

4

DOC. #569066200—C  8/17/06

Lingo

®

 SE Baseplate Installation Instructions

GND

24VAC

STATUS

FAULT

LOSS

TEMP

PULSE

HUMIDITY

INCOM

LIGHT

AUX

LAN

B MODULE

C MODULE

D MODULE

A MODULE

1

-

4

-

2

3

+

S

H

LD

8

S

H

LD

5

6

+

S

H

LD

7

-

11

S

H

LD

9

10

-

+

P1

15

+

12

13

+

S

H

LD

-

14

18

+

16

17

-

S

H

LD

33

+

26

22

-

19

20

1

S

H

LD

21

2

25

+

23

24

+

-

29

+

27

-

+

-

28

-

30

31

+

-

32

P2

P3

36

34

35

1A

24V

37

38

40VA

MAX ALLOWABLE AMBIENT TEMP: 60 C (140 F)

REFER TO INSTRUCTION MANUAL FOR SETUP AND INSTALLATION.

ETHERNET

10/100

COMMUNICATION NETWORKS

R

635205000 REV 0

RS-232 PORT

EMERGENCY

PN 750110000

LINGO/2 BPL

OUTDOOR

ALL INPUTS AND OUTPUTS ARE CLASS 2.

OUTDOOR

DEMAND

SYSTEM INPUTS

PHASE

SYSTEM

POWER

PHONE LINE

LISTED ENERGY

SUBASSEMBLY

MANAGEMENT
EQUIPMENT

US

L

U

C

20M1

Ground 
Terminal 36.

24-VAC, Class 2, 
40 VA screw terminal.

Figure 2.

  Lingo SE baseplate wiring connections

Содержание Lingo SE

Страница 1: ...ol to cut energy costs increase comfort and reduce equipment maintenance This document provides instructions for mounting and wiring the Lingo SE baseplate and checking the installation Lingo SE Speci...

Страница 2: ...f the transformer for this module Make sure that the Lingo SE power cannot be switched off accidentally The Lingo SE requires continuous power for proper operation Mounting the Lingo SE Baseplate to t...

Страница 3: ...baseplate 4 Drill holes in the places marked on the wall 5 Install the hollow wall or other appropriate fasteners 6 Turn appropriate screws into the fasteners until approximately one quarter inch rem...

Страница 4: ...round 4 Apply power and check voltage at the 24 VAC terminals Voltage should be approximately 24 to 28 VAC 5 Turn off the power until needed 4 DOC 569066200 C 8 17 06 Lingo SE Baseplate Installation I...

Страница 5: ...r equivalent wiring Step Procedure 1 Connect the white wire from the sensor to the Lingo SE at Terminal 25 at the Outdoor Light Sensor input connections 2 Connect the black wire from the sensor to the...

Страница 6: ...an emergency monitoring system to Terminals 32 and 33 labeled Emergency Status Input System Fault Output Under normal operating conditions a normally open set of contacts will be held closed When an a...

Страница 7: ...inals 19 21 Step Procedure 1 Connect the black wire from the INCOM cable to Terminal 21 INCOM 2 2 Connect the white wire from the INCOM cable to Terminal 20 INCOM 1 3 Connect the shield wire from the...

Страница 8: ...net Direct Connect Crossover Cable 770077000 Logic One and Lingo are registered trademarks of Novar INCOM is a trademark of Eaton Cutler Hammer Ethernet is a registered trademark of Xerox Corporation...

Отзывы: