Novar Lingo SE Скачать руководство пользователя страница 5

NOTE!

The Lingo SE requires continuous power for proper
operation.  Make sure the Lingo SE power cannot be
switched off accidentally.

NOTE!

The Lingo SE requires a dedicated transformer for the
electronics.  A separate transformer must be provided for
its control outputs.

Wiring the Lingo SE
Inputs and Outputs

Refer to Figure 2, as necessary, and use the procedure provided below to wire the 
Lingo SE input/output connections.

NOTE!

All digital inputs should be dry contact closures.

Outdoor Light Sensor

Novar’s 4-mA to 20-mA Analog Light Sensor (ALS) should be connected to the
Lingo SE with two-conductor, shielded cable (Novar WIR-1010, Belden 8761, or 
equivalent) wiring.

Step

Procedure

1

Connect the white (+) wire from the sensor to the Lingo SE at
Terminal 25 (+) at the Outdoor Light Sensor input connections.

2

Connect the black (–) wire from the sensor to the Lingo SE at
Terminal 24 (–) at the Outdoor Light Sensor Input connections.

Outdoor Temperature Sensor

For outdoor temperature sensing, Lingo SE uses the 4- to 20-mA Outdoor
Temperature Sensor (OTS/2).  Two-conductor, shielded cable (Novar WIR-1010, 
Belden 8761, or equivalent) should be used to connect the sensor to the Lingo
SE.

Step

Procedure

1

Connect the white (+) wire from the sensor to Lingo SE’s
Terminal 27 (+) at the Outdoor Temperature Sensor input
connections.

2

Connect the black (–) wire from the sensor to Lingo SE’s
Terminal 26 (–) at the Outdoor Temperature Sensor input
connections.

DOC. #569066200—C  8/17/06

5

Lingo

®

 SE Baseplate Installation Instructions

Содержание Lingo SE

Страница 1: ...ol to cut energy costs increase comfort and reduce equipment maintenance This document provides instructions for mounting and wiring the Lingo SE baseplate and checking the installation Lingo SE Speci...

Страница 2: ...f the transformer for this module Make sure that the Lingo SE power cannot be switched off accidentally The Lingo SE requires continuous power for proper operation Mounting the Lingo SE Baseplate to t...

Страница 3: ...baseplate 4 Drill holes in the places marked on the wall 5 Install the hollow wall or other appropriate fasteners 6 Turn appropriate screws into the fasteners until approximately one quarter inch rem...

Страница 4: ...round 4 Apply power and check voltage at the 24 VAC terminals Voltage should be approximately 24 to 28 VAC 5 Turn off the power until needed 4 DOC 569066200 C 8 17 06 Lingo SE Baseplate Installation I...

Страница 5: ...r equivalent wiring Step Procedure 1 Connect the white wire from the sensor to the Lingo SE at Terminal 25 at the Outdoor Light Sensor input connections 2 Connect the black wire from the sensor to the...

Страница 6: ...an emergency monitoring system to Terminals 32 and 33 labeled Emergency Status Input System Fault Output Under normal operating conditions a normally open set of contacts will be held closed When an a...

Страница 7: ...inals 19 21 Step Procedure 1 Connect the black wire from the INCOM cable to Terminal 21 INCOM 2 2 Connect the white wire from the INCOM cable to Terminal 20 INCOM 1 3 Connect the shield wire from the...

Страница 8: ...net Direct Connect Crossover Cable 770077000 Logic One and Lingo are registered trademarks of Novar INCOM is a trademark of Eaton Cutler Hammer Ethernet is a registered trademark of Xerox Corporation...

Отзывы: