Operating temperature: 32° to 140°F  (0° to 60°C)

0–80% RH, noncondensing

Storage:

–40

°

 to 158

°

F  (–40

°

 to 70

°

C)

0–90% RH, noncondensing

Physical Dimensions (Baseplate only)

Height:

19.25 inches

Width:

13.25 inches

Depth:

2.5 inches

Weight:

8 lb  (All aluminum enclosure)

Precautions

Take the following precautions during installation:

§

Observe national and local electrical codes.

§

Connect 24 VAC power wiring to the terminals marked as 24 VAC 

only

Connection to other terminals will damage them.

§

Do not use the Lingo SE as a final safety device.

§

Make sure that the 24-VAC power wiring is connected to a dedicated 40 VA
transformer.  No other devices should be powered by the transformer
connected to the Lingo SE.

§

Do not ground the secondary side of the transformer for this module.

§

Make sure that the Lingo SE power cannot be switched off accidentally.  The
Lingo SE requires continuous power for proper operation.

Mounting the Lingo SE
Baseplate to the Wall

The following items are needed to mount the Lingo SE baseplate to the wall:

§

The Lingo SE baseplate

§

The hex wrench (included with the baseplate)

§

Four screws (ap appropriate for mounting surface; not provided)

NOTE!

The baseplate assembly should be mounted in an
accessible location with the top of the assembly not more
than 6 feet from the floor.  The wall should have a flat and 
smooth surface to prevent the baseplate from being bent. 
When the baseplate is mounted to paneling or drywall,
hollow-wall anchors should be used to insure that the
assembly remains secure.

Use the following procedure and refer to Figure 1, as necessary, to mount the
Lingo SE baseplate to the wall.

2

DOC. #569066200—C  8/17/06

Lingo

®

 SE Baseplate Installation Instructions

Содержание Lingo SE

Страница 1: ...ol to cut energy costs increase comfort and reduce equipment maintenance This document provides instructions for mounting and wiring the Lingo SE baseplate and checking the installation Lingo SE Speci...

Страница 2: ...f the transformer for this module Make sure that the Lingo SE power cannot be switched off accidentally The Lingo SE requires continuous power for proper operation Mounting the Lingo SE Baseplate to t...

Страница 3: ...baseplate 4 Drill holes in the places marked on the wall 5 Install the hollow wall or other appropriate fasteners 6 Turn appropriate screws into the fasteners until approximately one quarter inch rem...

Страница 4: ...round 4 Apply power and check voltage at the 24 VAC terminals Voltage should be approximately 24 to 28 VAC 5 Turn off the power until needed 4 DOC 569066200 C 8 17 06 Lingo SE Baseplate Installation I...

Страница 5: ...r equivalent wiring Step Procedure 1 Connect the white wire from the sensor to the Lingo SE at Terminal 25 at the Outdoor Light Sensor input connections 2 Connect the black wire from the sensor to the...

Страница 6: ...an emergency monitoring system to Terminals 32 and 33 labeled Emergency Status Input System Fault Output Under normal operating conditions a normally open set of contacts will be held closed When an a...

Страница 7: ...inals 19 21 Step Procedure 1 Connect the black wire from the INCOM cable to Terminal 21 INCOM 2 2 Connect the white wire from the INCOM cable to Terminal 20 INCOM 1 3 Connect the shield wire from the...

Страница 8: ...net Direct Connect Crossover Cable 770077000 Logic One and Lingo are registered trademarks of Novar INCOM is a trademark of Eaton Cutler Hammer Ethernet is a registered trademark of Xerox Corporation...

Отзывы: