Lingo SE without Touchscreen
Operating temperature: 32° to 140°F (0° to 60°C)
0–80% RH, noncondensing
Storage:
–40
°
to 158
°
F (–40
°
to 70
°
C)
0–90% RH, noncondensing
Physical Dimensions (Baseplate only)
Height:
19.25 inches
Width:
13.25 inches
Depth:
2.5 inches
Weight:
8 lb (All aluminum enclosure)
Precautions
Take the following precautions during installation:
§
Observe national and local electrical codes.
§
Connect 24 VAC power wiring to the terminals marked as 24 VAC
only
.
Connection to other terminals will damage them.
§
Do not use the Lingo SE as a final safety device.
§
Make sure that the 24-VAC power wiring is connected to a dedicated 40 VA
transformer. No other devices should be powered by the transformer
connected to the Lingo SE.
§
Do not ground the secondary side of the transformer for this module.
§
Make sure that the Lingo SE power cannot be switched off accidentally. The
Lingo SE requires continuous power for proper operation.
Mounting the Lingo SE
Baseplate to the Wall
The following items are needed to mount the Lingo SE baseplate to the wall:
§
The Lingo SE baseplate
§
The hex wrench (included with the baseplate)
§
Four screws (ap appropriate for mounting surface; not provided)
NOTE!
The baseplate assembly should be mounted in an
accessible location with the top of the assembly not more
than 6 feet from the floor. The wall should have a flat and
smooth surface to prevent the baseplate from being bent.
When the baseplate is mounted to paneling or drywall,
hollow-wall anchors should be used to insure that the
assembly remains secure.
Use the following procedure and refer to Figure 1, as necessary, to mount the
Lingo SE baseplate to the wall.
2
DOC. #569066200—C 8/17/06
Lingo
®
SE Baseplate Installation Instructions