NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014
Installation
UL Power-limited Wiring Requirements
Some devices (such as ACM-8R and LDM-R32) are power-limited only when connected to power-
limited sources. When one of these devices is connected to a non-power-limited source, the power-
limited marking must be removed, and at the time of installation, each non-power-limited circuit
connected to these modules must be identified in the space provided on the cabinet door label.
NOTE:
Relays are power-limited only when connected to power-limited sources for the relay
outputs.