Connecting the Loop Control and Expander Modules
3.8.5 Installing a Multi-layer Module into the Chassis
Follow the instructions illustrated in Figure 3.13 to install a pair of loop control/expander modules
into CHS-4N or CHS-M3. See Figure 3.14 to install loop control/expander modules in CHS-4L.
1.
Angle the module into the chassis so that the upper end of the rear board (or boards) fits into
the top slot.
2.
Bring the module back down so that the lower board edges slip into the bottom slots.
3.
Secure the module to the chassis with the two module screws. Tighten securely.
4.
Connect the ribbon cable to the module.
SW1 Set to assign a unique
SLC loop number
J3 Data Out to
next LCM-320
J1 Data In from control panel
or from previous LCM-320
Ground Fault LEDs:
D32 Loop Expander
Module Ground Fault
D28 Loop Control Module
Ground Fault
J2 LEM-320 Connection
TB1 SLC
Loop
Connection
LCM-320
Connection
LCM-320
LEM-320
Note: Do not cut any jumpers on the LCM-320 or LEM-320.