24
PN 15037:D2 9/9/02
2.6.2 Alarm Message
When one or more alarms are reported to the LCD-80, the following
display format is used. If more than one alarm occurs, the LCD-80
shows the first alarm that occurred in time.
01234567890123456789
ROW 1
<<<<ALARMBANNER>>>>
ROW 2
<<<<<<<<CUSTOMPOINT
ROW 3
LABEL>>>>>>>>>>>>>>>
ROW 4
XXALARM YYTROUBLES
Where the “ALARM BANNER” is a user programmable 20-character
field with a default value of “FIRE ALARM IN SYSTEM.”
Note:
When the LCD-80 is used in conjunction with a combination
fire and security panel, the “fire” in the default banner must be
removed.
ZONE NNN
(AXXPYY)”
“NNN” is the number of the point starting at 001 and continuing in
decimal sequence to 128. “XX” is the annunciator number, which is
either the LCD-80 start address, or the next higher address. “YY” is
the annunciator point number within this annunciator, from 01 to 64.
The AXXPYY field will match FACP prompts.
“XXALARMS” is a count of the alarms to this LCD-80.
“XXTROUBLES” is a count of the troubles to this LCD-80.
Note: If trouble conditions exist along with alarms, they are shown in
the trouble count, but not otherwise displayed. If supervisory
condition occurs, it is reported to the LCD-80 as both an alarm and a
trouble from the same point (custom labels must be used to distinguish
supervisories). The LCD-80 will ignore ON/OFF output status, but
will report output device trouble conditions.
As a display example:
2.6.3 20-Character Alarm Messages
When the LCD-80 DIP switch is set for 20 character labels (256
points), use the following display format.
FIRE ALARM INSYSTEM
ROOM 314 FLOOR 3
SMOKE DETECTOR
2 ALARMS 5 TROUBLES
Содержание LCD-80
Страница 1: ...PN 15037 D2 ECN 02 339 Liquid Crystal Display LCD 80 Installation Manual Document 15037 9 9 02 Rev D2...
Страница 4: ...4 PN 15037 D2 9 9 02 Notes...
Страница 6: ...6 PN 15037 D2 9 9 02 Notes...
Страница 10: ...10 PN 15037 D2 9 9 02 Notes...
Страница 49: ...PN 15037 D2 9 9 02 49 Notes...
Страница 50: ...50 PN 15037 D2 9 9 02 Notes...