background image

2

PN 15037:D2  9/9/02

Fire Alarm System Limitations

While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!

An automatic fire alarm system

—typically made up of 

smoke detectors, heat detectors, manual pull stations, 
audible warning devices, and a fire alarm control with 
remote notification capability—can provide early warn-
ing of a developing fire. Such a system, however, does 
not assure protection against property damage or loss 
of life resulting from a fire. 
The Manufacturer recommends that smoke and/or heat 
detectors be located throughout a protected premise fol-
lowing the recommendations of the current edition of the 
National Fire Protection Association Standard 72 (NFPA 
72), manufacturer's recommendations, State and local 
codes, and the recommendations contained in the 
Guide for Proper Use of System Smoke Detectors, 
which is made available at no charge to all installing 
dealers. A study by the Federal Emergency Manage-
ment Agency (an agency of the United States govern-
ment) indicated that smoke detectors may not go off in 
as many as 35% of all fires. While fire alarm systems 
are designed to provide early warning against fire, they 
do not guarantee warning or protection against fire. A 
fire alarm system may not provide timely or adequate 
warning, or simply may not function, for a variety of rea-
sons: 

Smoke detectors

 may not sense fire where smoke can-

not reach the detectors such as in chimneys, in or 
behind walls, on roofs, or on the other side of closed 
doors. Smoke detectors also may not sense a fire on 
another level or floor of a building. A second-floor detec-
tor, for example, may not sense a first-floor or basement 
fire. 

Particles of combustion or “smoke”

 from a develop-

ing fire may not reach the sensing chambers of smoke 
detectors because:
• Barriers such as closed or partially closed doors, 

walls, or chimneys may inhibit particle or smoke flow.

• Smoke particles may become “cold,” stratify, and not

reach the ceiling or upper walls where detectors are 
located. 

• Smoke particles may be blown away from detectors

by air outlets. 

• Smoke particles may be drawn into air returns before 

reaching the detector. 

The amount of “smoke” present may be insufficient to 
alarm smoke detectors. Smoke detectors are designed 
to alarm at various levels of smoke density. If such den-
sity levels are not created by a developing fire at the 
location of detectors, the detectors will not go into alarm. 
Smoke detectors, even when working properly, have 
sensing limitations. Detectors that have photoelectronic 
sensing chambers tend to detect smoldering fires better 
than flaming fires, which have little visible smoke. 
Detectors that have ionizing-type sensing chambers 
tend to detect fast-flaming fires better than smoldering 
fires. Because fires develop in different ways and are 
often unpredictable in their growth, neither type of 
detector is necessarily best and a given type of detector 
may not provide adequate warning of a fire. 
Smoke detectors cannot be expected to provide ade-
quate warning of fires caused by arson, children playing 
with matches (especially in bedrooms), smoking in bed, 
and violent explosions (caused by escaping gas, 
improper storage of flammable materials, etc.). 

Heat detectors

 do not sense particles of combustion 

and alarm only when heat on their sensors increases at 
a predetermined rate or reaches a predetermined level. 
Rate-of-rise heat detectors may be subject to reduced 
sensitivity over time. For this reason, the rate-of-rise 
feature of each detector should be tested at least once 
per year by a qualified fire protection specialist. Heat 
detectors are designed to protect property, not life. 

IMPORTANT! Smoke detectors

 must be installed in 

the same room as the control panel and in rooms used 
by the system for the connection of alarm transmission 
wiring, communications, signaling, and/or power. If 
detectors are not so located, a developing fire may dam-
age the alarm system, crippling its ability to report a fire. 

Audible warning devices

 such as bells may not alert 

people if these devices are located on the other side of 
closed or partly open doors or are located on another 
floor of a building. Any warning device may fail to alert 
people with a disability or those who have recently con-
sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause sei-

zures in people with conditions such as epilepsy. 

• Studies have shown that certain people, even when 

they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property 
owner's responsibility to conduct fire drills and other 
training exercise to make people aware of fire alarm 
signals and instruct them on the proper reaction to 
alarm signals. 

• In rare instances, the sounding of a warning device 

can cause temporary or permanent hearing loss. 

A fire alarm system

 will not operate without any electri-

cal power. If AC power fails, the system will operate 
from standby batteries only for a specified time and only 
if the batteries have been properly maintained and 
replaced regularly. 

Equipment used in the system

 may not be technically 

compatible with the control. It is essential to use only 
equipment listed for service with your control panel. 

Telephone lines

 needed to transmit alarm signals from 

a premise to a central monitoring station may be out of 
service or temporarily disabled. For added protection 
against telephone line failure, backup radio transmis-
sion systems are recommended. 

The most common cause

 of fire alarm malfunction is 

inadequate maintenance. To keep the entire fire alarm 
system in excellent working order, ongoing maintenance 
is required per the manufacturer's recommendations, 
and UL and NFPA standards. At a minimum, the 
requirements of Chapter 7 of NFPA 72 shall be followed. 
Environments with large amounts of dust, dirt or high air 
velocity require more frequent maintenance. A mainte-
nance agreement should be arranged through the local 
manufacturer's representative. Maintenance should be 
scheduled monthly or as required by National and/or 
local fire codes and should be performed by authorized 
professional fire alarm installers only. Adequate written 
records of all inspections should be kept. 

Precau-S-4-2002.fm

Содержание LCD-80

Страница 1: ...PN 15037 D2 ECN 02 339 Liquid Crystal Display LCD 80 Installation Manual Document 15037 9 9 02 Rev D2...

Страница 2: ...e warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat de...

Страница 3: ...y drilling filing reaming or punching of the enclosure When pos sible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transfo...

Страница 4: ...4 PN 15037 D2 9 9 02 Notes...

Страница 5: ...26 2 6 6 Remote Printer Operation 26 2 6 7 Display Illumination 27 2 7 Interface Operation 27 2 7 1 EIA 485 Interface 27 2 7 2 EIA 232 Interface 28 2 7 3 Programming the LCD 80 ACS Mode 28 2 7 4 Prog...

Страница 6: ...6 PN 15037 D2 9 9 02 Notes...

Страница 7: ...te display field ABF 1 B package with key switch option Mounts up to 6000 feet from the panel Local piezo sounder with alarm trouble resound 1 2 ACS Mode When operated in ACS mode the LCD 80 provides...

Страница 8: ...ode In Terminal Mode the LCD 80 is a simplified version of the display for AFP 200 AFP 300 AFP 400 AFC 600 AM2020 AFP 1010 NCA and NFS 640 but does not support a remote printer Up to 32 of these termi...

Страница 9: ...ils PK 1 Programming Key connector When the key is inserted the LCD 80 enters program mode When the key is removed the LCD 80 automatically returns to normal operations AKS 1 Keyswitch connector For c...

Страница 10: ...10 PN 15037 D2 9 9 02 Notes...

Страница 11: ...32 devices This figure includes the LCD 80 as well as AMG 1 ACS and LDM series modules On the System 5000 all but two devices must be Receive Only On the System 500 and AFP 200 all but one device mus...

Страница 12: ...l Silence and Reset switches SW1 5 Size see Table 2 1 below SW1 6 Size see Table 2 1 below SW1 7 Set OFF in this mode SW1 8 Not used Operating Mode Switches Set both switches in the UP position for AC...

Страница 13: ...200 systems DIP Switch EIA 485 addresses Number of points Size of display labels Max LCD 80s per system Max LCD 80s per AFP 200 5 6 OFF OFF one 64 40 characters 32 2 OFF ON two 128 40 characters 16 1...

Страница 14: ...01 and 02 DIP SW3 1 DIP SW3 2 Rotary SW2 Start Address OFF OFF 0 n a OFF OFF 01 09 01 09 ON OFF 0 09 19 19 OFF ON 0 09 20 29 ON ON 0 02 30 32 ON ON 03 09 n a Table 2 2 Setting the LCD 80 Address in A...

Страница 15: ...ed pair cable with a characteristic impedance of approximately 120 ohms EIA 485 5 5 VDC max 60 mA max A UL listed 120 ohm terminating resistor R 120 must be installed on the last device on the EIA 485...

Страница 16: ...for EIA 232 applications This interface is intended for use with UL listed printers such as the PRN that do not connect the EIA 232 Reference line to chassis ground This is required to avoid creating...

Страница 17: ...tion Diagram ACS Mode Shield connect to chassis common on printer no connection at LCD 80 4 3 2 1 7 6 5 4 3 2 1 P1 P2 Twisted shielded pair Plug this DB 25 connector into the EIA 232 port of the print...

Страница 18: ...BIDIRECTIONAL COPY ON CG TAB GRAPHIC COUNTRY E USA ASCII AUTO CR OFF LANGUAGE ENGLISH AUTO TEAR 1S COLOR OPTION NOT INSTALLED FORMLEN LINES 6 LPI 60 STANDARD EXECUTIVE 10 5 CPI 10 CPI SKIP 0 5 EMULATE...

Страница 19: ...oss of power is inherently supervised through communication loss Maximum LCD 80 current draw from power supply is 100 mA Maximum current draw from the control panel s secondary power source batteries...

Страница 20: ...er Supply Common 24 VDC Power To next LCD 80 LCD 80 24 VDC Common MPS 24A TB3 3 TB3 4 MPS 24B TB2 1 TB2 2 AFP 200 TB1 3 TB1 4 AFP 300 AFP 400 MPS 6 TB2 1 TB2 2 APS 6R TB2 TB2 FCPS 24 TB4 TB4 NCA TB1 2...

Страница 21: ...ovided by mounting the LCD 80 in 1 A locked Fire Alarm Cabinet OR 2 Annunciator Backbox model ABF 1 B or ABS 1T B with AKS 1 key switch option Acknowledge Switch When the ACKNOWLEDGE switch is activat...

Страница 22: ...gh all time and date fields If the switch is not pressed for one minute or if the DISPLAY STEP switch is pressed the LCD 80 will exit time date select mode Time Set Switch When used in conjunction wit...

Страница 23: ...7890123456789 ROW 1 CUSTOM ROW 2 MESSAGE 1 ROW 3 CUSTOM MESSAGE 2 ROW 4 HH MMA MM DD YY Where CUSTOM MESSAGE 1 is a 40 character user defined message CUSTOM MESSAGE 2 is a 20 character user defined me...

Страница 24: ...hich is either the LCD 80 start address or the next higher address YY is the annunciator point number within this annunciator from 01 to 64 The AXXPYY field will match FACP prompts XXALARMS is a count...

Страница 25: ...number of troubles or new alarms block acknowledge When all alarms and troubles restore the LCD 80 automatically restores to ALL SYSTEMS NORMAL without requiring ACK self restore 01234567890123456789...

Страница 26: ...ey occur If several alarms and or troubles are reported at once the LCD 80 prints out a line for each in address order all alarms will be printed before any troubles 2 The alarm trouble count field li...

Страница 27: ...Display Illumination The LCD 80 display is backlit under normal conditions Backlighting is shut off for all System 5000 System 500 panel trouble other than Point Trouble or for any trouble on the AM2...

Страница 28: ...ode Program mode is used to enter custom messages and labels for annunciator points Due to the nonvolatile memory onboard the LCD 80 this unit can be programmed anywhere then removed for installation...

Страница 29: ...Monitor Programming the LCD 80 from the CRT requires a custom cable and a male DB 25 connector for connection to the display s EIA port The CRT must also be configured as outlined on the next page Fig...

Страница 30: ...imultaneously Press Function Keys F1 through F13 to view the 13 separate groups of parameters Use the arrow keys to move through each parameter within a group and use the space bar to view and select...

Страница 31: ...ith a DB 25 connector use DB9M to DB25F adapter P N 46029 Figure 2 7 LCD 80 IBM compatible Connection 4 3 2 1 7 6 5 4 3 2 1 P1 P2 EIA 232 TX EIA 232 Reference EIA 232 RX Female DB 9 connector for conn...

Страница 32: ...default messages that can be restored en masse at any time These messages can also be edited as needed Note that any custom messages or labels that were previously entered will be overwritten by the...

Страница 33: ...on Push TIME SET to restore 20 character default point labels Push TIME SELECT to restore 40 character default point labels Push ACK to restore 20 character default point labels for AIM 200 mode in th...

Страница 34: ...ssage has been edited press ENTER to store the message The screen will return to the display READY FOR PROGRAMMING These custom messages have various character widths and are displayed under different...

Страница 35: ...ted to 128 points AFP 200 uses Zones 1 to 99 only Once a point number has been entered the LCD 80 screen will display either the custom zone message illustrated below or the last stored point message...

Страница 36: ...the message has been changed or entered satisfactorily press ENTER to store the message The LCD 80 screen will retain the previous point label information while the monitor display will return to the...

Страница 37: ...control panel s battery calculations Note When powered by the AFP 200 a maximum of four LCD 80s may be connected to this circuit Between each LCD 80 are four wires A twisted shielded pair for data com...

Страница 38: ...80s in terminal mode without the need for a CCM 1 converter module provided no CRT is installed on the SIB The EIA 485 terminal interface does not support the use of RPT 485 repeaters The RPT 485 rep...

Страница 39: ...onnector compatible with PK 1 program key AKS 1 Keyswitch Interface Connect to optional keyswitch Operation mode Slide Switches Set both switches in the DOWN position RAA 2020 for Terminal Mode SW2 No...

Страница 40: ...riod of over one minute it will activate its local sounder and display the following message Printer Operation The LCD 80 does not support a remote printer when operating in Terminal Mode 3 1 2 Switch...

Страница 41: ...P1010 Note This feature requires Revision 5 software or greater Contrast Adjust Repeatedly press this switch until the display s contrast is acceptable Local Silence Lamp Test Switch If the backlit LC...

Страница 42: ...s as shown in Figure 3 2 Set SW2 on the AFP 200 to the Term position left hand position Set SW4 and 5 on the LCD 80 to the Term position SW1 7 On The LCD 80s require connection of operating power Conn...

Страница 43: ...in the preceding text Refer to Appendix A for shield termination instructions Last LCD 80 must set DIP Switch SW3 1 and SW3 2 ON First LCD 80 set DIP Switch SW3 1 and SW3 2 Off on all LCD 80s except...

Страница 44: ...M2020 AFP1010 AFP 200 DIA AM2020 AFP1010 NFS 640 AFP 300 AFP 400 AFC 600 OUT P3 4 TB5 2 TB1 4 TB12 TB3 4 RET P3 3 TB5 4 TB1 3 TB12 TB3 2 OUT P3 2 TB5 1 TB1 2 TB12 TB3 3 RET P3 1 TB5 3 TB1 1 TB12 TB3 1...

Страница 45: ...not allow the shield to enter or even touch the cabinet Between LCD 80s wire nut multiple shields together outside of the respective enclosures Note on remote power supplies When the LCD 80 is powere...

Страница 46: ...losure except the first on the loop terminate the shield coming in from the previous LCD 80 at system common Let the shield going out to next LCD 80 shield float no connection Shield termination betwe...

Страница 47: ...ligent AIM 200 points only standard System 5000 zones The option provides annunciation of up to 256 points for the System 5000 broken down as follows Annunciator Address 1 8 CPU points CPU point shift...

Страница 48: ...CPU 5000 The System 5000 Programming Manual Document 15584 provides programming instructions for this option Refer to program choice AIM 256 Note AIM 200 detector and module addresses 97 98 and 99 ma...

Страница 49: ...PN 15037 D2 9 9 02 49 Notes...

Страница 50: ...50 PN 15037 D2 9 9 02 Notes...

Страница 51: ...OTIFIER 12 Clintonville Road Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products wil...

Страница 52: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www notifier com NOTIFIER is a company...

Страница 53: ...ut Terminal Mode Labels ACS Mode Labels TIME SELECT GLOBAL ACKNOWLEDGE GLOBAL ACKNOWLEDGE ACS Mode Label left ACS Mode Label right Terminal Mode Label left Terminal Mode Label right TIME SET SILENCE S...

Отзывы: