22
PN 15037:D2 9/9/02
using the third switch position on the start annunciator address. A
RESET message is printed on the local printer.
*The Acknowledge, Silence, and Reset switch functions require
programming from the AM2020 or AFP-1010.
The Acknowledge, Silence and Reset switches will serve
no function if the LCD-80 has been set for Receive-Only
operation (DIP switch SW1-1 has been set ON)
Time Select Switch
This switch is used in conjunction with the TIME SET switch to set
the time and date on the LCD-80. This switch is ignored if the system
is in alarm. Under non-alarm conditions, the bottom display line will
show the present time and date when this switch is pressed.
When the TIME SELECT switch is pressed, the left-most field
(HOURS) will flash, indicating that it is ready to accept changes.
Press the TIME SET switch to step through all possible values for that
field. If the TIME SELECT switch is pressed again, the MINUTES
field will flash, ready for changes. This continues through all time and
date fields. If the switch is not pressed for one minute, or if the
DISPLAY STEP switch is pressed, the LCD-80 will exit time/date
select mode.
Time Set Switch
When used in conjunction with the TIME SELECT switch, this switch
sets the time and date into the LCD-80. This switch is ignored if the
system is in alarm.
Once the TIME SELECT switch has been pressed, the TIME SET
switch can be used to step through all possible values for that field.
The new value is stored into the clock chip upon depression of either
the Select or Display switch.
The Time Set switch can be used to adjust the contrast of the LCD-
80's display
Display Step/Lamp Test Switch
This switch may be used to step the display through multiple alarms or
troubles. If both alarms and troubles exist in the LCD-80, DISPLAY
STEP may be used to display the troubles (after first stepping through
all alarms). This is a local function and does not send an acknowledge
command to the control panel. If a trouble condition has turned off the
backlighting, it also causes the backlit display to illuminate for about
one minute, and while held, turns on all LCD segments (lamp test).
The printer interface is not affected.
!
Содержание LCD-80
Страница 1: ...PN 15037 D2 ECN 02 339 Liquid Crystal Display LCD 80 Installation Manual Document 15037 9 9 02 Rev D2...
Страница 4: ...4 PN 15037 D2 9 9 02 Notes...
Страница 6: ...6 PN 15037 D2 9 9 02 Notes...
Страница 10: ...10 PN 15037 D2 9 9 02 Notes...
Страница 49: ...PN 15037 D2 9 9 02 49 Notes...
Страница 50: ...50 PN 15037 D2 9 9 02 Notes...