PN 15037:D2 9/9/02
11
Section 2 The LCD-80 and ACS Mode
System 5000/System 500:
Use of the LCD-80 with Remote Command
Inputs is not recommended.
AM2020/AFP1010:
Security points must have “security” as part of its
custom label on the LCD-80 to differentiate between a fire alarm and
a security alarm condition.
The primary application for the LCD-80 in ACS Mode is to add
digital display and printer options to the System 5000, System 500
and AFP-200. It also provides an Alarm and Trouble Count option.
The power-limited EIA-485 interface provided by the control panels
will support the installation of up to 32 devices. This figure includes
the LCD-80, as well as AMG-1, ACS and LDM-series modules. On
the System 5000, all but two devices must be “Receive Only.” On the
System 500 and AFP-200, all but one device must be set for “Receive
Only” operation.
The LCD-80 can be mounted in ABF-1/1B, ABS-1T/1TB, or ABS-1D
backbox (not the ABS-1) or can mount on one slot of the CHS-4
chassis. The ABF-1/1B may include an AKS-1 keyswitch and APJ-1
phone jack. In addition, the LCD-80 contains an EIA-232 remote
printer interface. This interface allows for connection of the UL Fire
Alarm System-listed PRN printer.
EIA-485: Maximum of 6,000 feet total wire length
to
PRN
FACP
LCD8
0
-CA
B4
-A
CS
mo
de
.c
d
r
to
PRN
to
PRN
LCD-80
mounted in cabinet
EIA-232: Maximum of 50 feet total wire length from
LCD-80 to remote printer.
(unsupervised)
Printer
Содержание LCD-80
Страница 1: ...PN 15037 D2 ECN 02 339 Liquid Crystal Display LCD 80 Installation Manual Document 15037 9 9 02 Rev D2...
Страница 4: ...4 PN 15037 D2 9 9 02 Notes...
Страница 6: ...6 PN 15037 D2 9 9 02 Notes...
Страница 10: ...10 PN 15037 D2 9 9 02 Notes...
Страница 49: ...PN 15037 D2 9 9 02 49 Notes...
Страница 50: ...50 PN 15037 D2 9 9 02 Notes...