Page 36
INERTIA-2464
Technical & Programming Manual
Copyright (c) 1996,
INERTIA FIRE SYSTEMS
APPENDIX A
DESCRIPTION OF ALARM ZONE TYPES
Different zone types can be selected using the programming mode. Each zone can be selected as any one of
following:
Type
Description
Input Delay
1
Standard Latching
2 seconds
2
Standard Latching
2 seconds with AVF
3
Non Latching
2 seconds
4
Non Latching
20 seconds
5
Time Delay
10 seconds
6
Time Delay
20 seconds
7
Time Delay
30 seconds
8
Time Delay
40 seconds
9
Time Delay
50 seconds
10
Time Delay
60 seconds
LATCHING TYPE
Once a signal is received from the detector the alarm zone will start a timer, if after 2 seconds the detector is
still activated the alarm zone will register an alarm condition. Indicators will illuminate and alarm functions are
initiated immediately, unless zone is set as AVF - refer Appendix C. The alarm zone will remain in alarm until
manually reset.
A reset is performed by interrupting the power to the detector for 0.5 seconds and returning the alarm zone
back to its quiescent state. If an alarm is still present in the detector area, the detector will re-activate and the
2-second timer will be re-initiated.
NON LATCHING TYPE
A temporary actuation device (eg. Flow Switch) is usually connected to this type of alarm zone. Once a signal
has been received CONTINUOUSLY for 2 seconds or 20 seconds (dependant on programming) an alarm will
be registered causing the alarm LED to flash and alarm functions will be performed as programmed.
The alarm group will remain in alarm until the actuating device no longer reports a signal. When actuating
device signal is clear, the alarm is cleared, causing the zone to power down for 0.5 seconds and return back to
normal state.