Page 20
INERTIA-2464
Technical & Programming Manual
Copyright (c) 1996,
INERTIA FIRE SYSTEMS
ACF ISOLATE
ACF
ISOL
Depressing the "ACF ISOL" key, will isolate the ACF (Ancillary output). The ACF isolated LED will illuminate
and the ancillary output will not operate until the ancillary output is de-isolated. Pressing "ACF ISOL" for a
second time will de-isolate the ancillary output.
If the ancillary output has already been tripped and is programmed as latching, isolating the ACF will not effect
the existing ancillary output. If the ACF is isolated prior to the alarm, it will prevent the ancillary output from
tripping.
Note: If the ACF output is programmed as normally energised then isolating the output prevents it from de-
energising.
ACF RESET
ACF
RESET
Resetting of the ancillary output (ACF) is only required if the ancillary output was programmed as latching.
The ancillary alarm will remain latched until manually reset. Pressing the "ACF RESET" button will extinguish
the 'ACF Activated' LED and de-energise the ancillary output. Pressing "ACF RESET" when the ACF is not
tripped will have no effect.