background image

(+)

(-)

RA400

REMOTE ALARM

LED OPTION

1 PER UNIT

8mA CURRENT DRAW

RA400Z (+)

RA400Z or (-)
RTS451/
RTS451KEY

EXTERNAL

(-) POWER (+)

SUPPLY

*

RTS451/RTS451KEY

REMOTE TEST STATION

LED OPTION

1 PER UNIT

8mA CURRENT DRAW

TEST COIL OPTION

1 PER UNIT

95mA CURRENT DRAW

4

5

3

2

1

Unused

Remote

Test

(+)

(-)

(+)

(+)

(-)

(-)

(+)

RA400Z

RTS451/RTS451KEY

RA400Z or
RTS451/RTS451KEY

Comm.
Line

Comm. Line (+)

Alarm
Initiation
Loop

Comm.
Line (-)

UL Listed
Control Panel

1st
Detector
in Loop

2nd
Detector
in Loop

The RTS451/RTS451KEY test coil circuit requires an external 24VDC
power supply which must be UL listed

*

Figure 5C. System wiring diagram

for duct detectors using a UL listed

control panel.

Figure 5A.

Figure 5B.

Caution:

Filters require periodic cleaning or replacement, depending on the amount of dust and dirt accumulated.
Visually inspect the filters at least quarterly; inspect them more often if the dust accumulation warrants
it. Replacement filters can be ordered from Notifier (exhaust tube/intake tube filter P/N F36-05-00).

The filters do not substantially affect smoke performance under normal conditions. There is very little restriction of
smoke entry even when up to 90% of the filter is clogged. Visual inspection is usually adequate to determine whether
the filters should be replaced because such a high percentage of contamination is required to affect performance.

STEP 7. PERFORM DETECTOR CHECK

7.1 AIR FLOW

1. To verify sufficient sampling of ducted air, use a manometer to measure the differential pressure created from air

flow across the sampling tubes. The pressure should measure no less than 0.01 inches of water and no greater
than 1.20 inches of water.

2. To determine that smoke is capable of entering the sensing chamber, a visual examination should be conducted

to note any obscurations around the sensing chamber. If a smoke test is required, smoke such as cigarette, cotton
wick, or punk smoke may be blown directly at the smoke detector head. It is important to plug the exhaust and
sampling tube hole to prevent ducted air from blowing smoke away from the smoke detector head. Record all test
records in the Detector Test Log (page 12).

CAUTION:

REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT SENSE
SMOKE IN THE AIR DUCT.

7.2 ALARM TESTS

Before replacing the duct housing cover, the detector interconnections should be checked. The DHX-502A may be
checked as follows:

A. M02-04-00 MAGNET TEST

1. Make sure power is applied to the detector.
2. Place the painted surface of the test magnet against the housing next to the rib molded onto the outside of the

housing (see Figure 7).

3. The LEDs on the detector should latch on as should any accessories (i.e. RA400ZA, RTS451), and the alarm

condition should be verified at the control panel.

MOLDED RIB

TEST
MAGNET

PAINTED SIDE

TOWARD HOUSING

DUCT
DETECTOR
HOUSING

DETECTOR

HEAD

TWIST
COUNTERCLOCKWISE
TO REMOVE

DUCT
HOUSING

TWIST
CLOCKWISE
TO INSTALL

DETECTOR
HEAD

A78-1812-05

A78-1812-02

Figure 7. Testing Detector Alarm

Figure 8. Detector Head Removal

A78-2095-02

N500-04-00

6

I56-507-06

N500-04-00

7

I56-507-06

Содержание DHX-502

Страница 1: ...ectors in Duct Applications which provides detailed information on detector spacing placement zoning wiring and special applications Copies of this manual are available from NEMA National Electrical Manufacturers Association 2101 L Street NW Washington DC 20037 NFPA Standards 72 and 90A should also be referenced for detailed information NOTICE This manual should be left with the owner user of this...

Страница 2: ...s device will not operate without electrical power Frequently fire situations may cause an interruption of power to the detector The system safeguards should be discussed with your local fire protection specialist WARNING This device will not sense smoke unless the ventilation system is operating WARNING In order to function properly this detector must be installed according to these instructions ...

Страница 3: ...e bushing with the air inlet holes facing into the air flow To assure proper installation the tube mounting flange is marked with arrows Mount the inlet tube so that the arrows point into the air flow Figure 4 shows the various combinations of tube mounting configurations with respect to air flow INLET TUBE END PLUG AIR HOLES ARROWS MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE A78 2047 01 Fig...

Страница 4: ...rude through the duct on the side opposite the housing must be supported by other means NOTE An alternate method to using the ST 10 is to use two ST 5 inlet tubes Remove the flange from one of the tubes and install as described above After the installation use electrician s tape to close off some of the sampling holes so that there are a total of 12 holes spaced as evenly as possible across the wi...

Страница 5: ...l To install the sampling tube filters simply push the filter adapter into the exhaust tube and then push the filter onto the adapter tube on the left as shown in Figure 6 Then install the other filter over the end of the inlet sampling tube B RTS451 RTS451KEY REMOTE TEST STATION The RTS451 RTS451KEY Remote Test Station facilitates test of the alarm capability of the duct detector as indicated in ...

Страница 6: ...ometer to measure the differential pressure created from air flow across the sampling tubes The pressure should measure no less than 0 01 inches of water and no greater than 1 20 inches of water 2 To determine that smoke is capable of entering the sensing chamber a visual examination should be conducted to note any obscurations around the sensing chamber If a smoke test is required smoke such as c...

Отзывы: