background image

 

SD-8-EL / SD-8-EL-F1 Smoke Detector   

 
Introduction 

The SD-8-EL / SD-8-EL-F1 Smoke Detector is designed to be mounted on ceiling or top of stairwells where smoke would 
concentrate to raise alarm timely and protect your home from fire hazards.

 

 
Parts Identification 

1. Learn / Test Button 

The Learn / Test Button is pressed in the following situations: 

  Learning – In the Smoke Detector. 
  To test the radio communication range. 
  To test if the Smoke Detector is functioning normally. 
  To silence the alarm 

2. LED Indicator 

  Flash every 30 seconds –Low Battery 
  Flash when button is pressed – Transmit Signal 
  Continuous Flash – Warm Up or Calibration / Alarming / Alarm Silence Mode. 

3. Battery compartment   

 

 

 

 

 

 

4. Mounting Hole 

5. Mounting Bracket  

 

 

 

 

 

 

6. Hook 

 

Features 

 

Battery 

  The Smoke Detector uses 3 AA Alkaline batteries as power supply.   
  When using factory supplied batteries, the Smoke Detector has battery life expectancy of 4 years. 
  When  low  battery  voltage  is  detected,  a  low  battery  signal  will  be  transmitted  along  with  regular  signal 

transmissions. If the battery voltage is low, the LED will flash accompanied with a Low-volume beep every 30 
seconds.   

  When changing batteries, remove the old batteries and press the Test button twice to fully discharge before 

inserting new batteries. 

 

Learning / Getting Started 

Step 1. 

Insert the batteries into the battery compartment with correct polarity. 

Step 2. 

After all 3 batteries are inserted, the Smoke Detector will sound 2 short beeps, with LED starting to flash and 
begin a 6-minute warming period. 

Step 3. 

During the 6-minute warming period, the Smoke Detector can be learnt into the Panel. 
a.  Put the Control Panel into learning mode. Please refer to Control Panel manual for details. 
b.  Press the Learn/Test button on the Smoke Detector. The LED will light up briefly and the Smoke Detector 

will sound a 2-tone beep to indicate it is transmitting signal. 

c.  If the Control Panel successfully receives the signal, the panel will respond accordingly. Refer to Control 

Panel manual to complete learning process. 

Step 4. 

When the 6-minute warming period expires, the Smoke Detector will sound a short beep to indicate that the 
Smoke Detector is starting calibration process. 

 

The  process  will  be  repeated  every  100  secs  and  notified  by  a  short  beep  respectively.  The  completion  of 
calibration process will be notified by a 2-tone beep and the LED will be turned off. 

 

Normally it takes about 2 ~ 16 minutes to finish calibration. However, after 16 minutes, if the Smoke Detector 
gives  out  continuous  beeps  instead,  it  indicates  that  the  Smoke  Detector  has  failed  calibration  and  its 
batteries should be removed to silence the beeps. Then, please start from Step 1 to try again after a pause of 
at least 30 seconds. 

<NOTE> 

 

During the calibration period, learning is disabled. If you did not finish learning (Step 3) during the 6-minute 
warming period, you have to wait until the calibration has been completed (Step 4) to perform learning.   

Step 5. 

After  warming  up,  learning  and  calibration  are  completed,  you  should  test  the  Smoke  Detector’s  signal 
transmission  range.  Put  the  Control  Panel  into  Walk  Test  mode  and  place  the  Smoke  detector  at  desired 
mounting location, and then press the Learn/Test button to transmit signal to the Control Panel.   

 

If the panel can receive signal normally, proceed to mount the Smoke Detector. If signal could not be received, 

change mounting location. 

Отзывы: