background image

1. Complete housing base and cover assembly.
2. Two #10 sheet metal mounting screws.
3. Two sampling tube filters.
4. One test magnet.
5. Drilling template.
6. Two 5/16-inch O-rings.
7. Two rubber tube bushings seals.
8. Four #6 self-tapping mounting screws for the sampling tube.
9. One filter adapter.
10.One inlet tube end plug.
11.Four #6x7/10 cover mounting screws.
11.Two #10 speed nuts.

Note 1:The inlet sampling tube must be ordered separately. It must be the correct length for the width of the duct

where it will be installed. See Table 1 to determine the inlet tube required for different duct widths. Smoke
detector heads (CPX-551, ionization; SDX-551, photoelectronic) must be ordered separately.

WARNING

LIMITATIONS OF DUCT DETECTORS

The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A
SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a
substitute for early warning in a building’s regular fire detection system.

Notifier supports this position and strongly recommends that the user read NFPA Standards 90A, 72, and 101. The
DHX-502 is listed per CAN/ULC-S529.

WARNING: This device will not operate without electrical power. Frequently, fire situations may cause an

interruption of power to the detector. The system safeguards should be discussed with your local fire
protection specialist.

WARNING: This device will not sense smoke unless the ventilation system is operating.

WARNING: In order to function properly, this detector must be installed according to these instructions. Do not

exceed the electrical or ambient specifications or the detector will not function properly. This detector
must be protected from the elements.

INSTALLATION SEQUENCE

PAGE

Step 1. Verify duct air flow direction and velocity .......................................................................................................... 2
Step 2. Drill the mounting holes ...................................................................................................................................... 3
Step 3. Secure the housing base to the duct ................................................................................................................. 3
Step 4. Install the inlet sampling tube ............................................................................................................................ 3
Step 5. Field wiring .......................................................................................................................................................... 5
Step 6. Install the filters and check pressure differential .............................................................................................. 5
Step 7. Perform detector check ...................................................................................................................................... 7
Step 8. Install the cover ................................................................................................................................................... 8
Step 9. Perform the final system check (Testing) .......................................................................................................... 8

STEP 1. VERIFY DUCT AIR FLOW DIRECTION AND VELOCITY

The DHX-502 is designed to be used in air handling systems having air velocities of 500 to 4000 feet per minute. Be
sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. If
necessary, a velocity meter to check the air velocity in the duct.

N500-04-00

2

I56-507-06

N500-04-00

11

I56-507-06

NOTES

Содержание DHX-502

Страница 1: ...ectors in Duct Applications which provides detailed information on detector spacing placement zoning wiring and special applications Copies of this manual are available from NEMA National Electrical Manufacturers Association 2101 L Street NW Washington DC 20037 NFPA Standards 72 and 90A should also be referenced for detailed information NOTICE This manual should be left with the owner user of this...

Страница 2: ...s device will not operate without electrical power Frequently fire situations may cause an interruption of power to the detector The system safeguards should be discussed with your local fire protection specialist WARNING This device will not sense smoke unless the ventilation system is operating WARNING In order to function properly this detector must be installed according to these instructions ...

Страница 3: ...e bushing with the air inlet holes facing into the air flow To assure proper installation the tube mounting flange is marked with arrows Mount the inlet tube so that the arrows point into the air flow Figure 4 shows the various combinations of tube mounting configurations with respect to air flow INLET TUBE END PLUG AIR HOLES ARROWS MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE A78 2047 01 Fig...

Страница 4: ...rude through the duct on the side opposite the housing must be supported by other means NOTE An alternate method to using the ST 10 is to use two ST 5 inlet tubes Remove the flange from one of the tubes and install as described above After the installation use electrician s tape to close off some of the sampling holes so that there are a total of 12 holes spaced as evenly as possible across the wi...

Страница 5: ...l To install the sampling tube filters simply push the filter adapter into the exhaust tube and then push the filter onto the adapter tube on the left as shown in Figure 6 Then install the other filter over the end of the inlet sampling tube B RTS451 RTS451KEY REMOTE TEST STATION The RTS451 RTS451KEY Remote Test Station facilitates test of the alarm capability of the duct detector as indicated in ...

Страница 6: ...ometer to measure the differential pressure created from air flow across the sampling tubes The pressure should measure no less than 0 01 inches of water and no greater than 1 20 inches of water 2 To determine that smoke is capable of entering the sensing chamber a visual examination should be conducted to note any obscurations around the sensing chamber If a smoke test is required smoke such as c...

Отзывы: