35
Document 15949 Rev. E 4/12/95 P/N 15949:E
Section Four: Programming the AIM-200
Programming the AIM-200 involves two modes of operation: Auto-Program, (password
231-1332) and Program Edit (password 231-3112). A third function, Display Status, allows
the programmer to review the entire AIM-200 program. Program Clear (password 231-5678),
allows the clearing of an existing program from non-volatile memory.
4.1 The Programming Display
Device Type
Green LEDs indicate whether the device is a detector or a module.
code3
DETECTOR
ADDRESS
MODULE
FORWARD
STEP
REVERSE
G ree n L ED s
Device
The device’s type and address are alternately displayed on the 2-digit 7-segment display.
Left Digit
Right Digit
P = Photo Detector
Blank = Normal Sensitivity (for
detectors), or Indicating Circuit
Selected (for CMXs)
I = Ion Detector
L = Low Sensitivity (detectors only)
H = Heat Detector
H = High Sensitivity (detectors only)
G = Monitor Module or Pull Station
d = Disabled
C = Control Module
O = Form-C Selected (CMXs)
E = No response from a device (the
AIM-200 is programmed for a device
which is in trouble or not physically
installed on the loop).
code4
Address
(01-99)
Address
(01-99)
Technical Manuals Online! - http://www.tech-man.com
Содержание AIM-200
Страница 2: ...2 Document 15949 Rev E 4 12 95 P N 15949 E Technical Manuals Online http www tech man com...
Страница 57: ...57 Document 15949 Rev E 4 12 95 P N 15949 E NOTES Technical Manuals Online http www tech man com...
Страница 58: ...58 Document 15949 Rev E 4 12 95 P N 15949 E NOTES Technical Manuals Online http www tech man com...
Страница 59: ...59 Document 15949 Rev E 4 12 95 P N 15949 E Technical Manuals Online http www tech man com...
Страница 60: ...60 Document 15949 Rev E 4 12 95 P N 15949 E BACK COVER Technical Manuals Online http www tech man com...