3.6 The MMX-101 Monitor Module
Set the module address
with these switches.
IDC (-)
(White)
IDC (+)
(Violet)
SLC (+)
(Red)
SLC (-)
(Black)
mmx101
ADDRESS
LOOP
5
0
1
2
3
4
6
7
8
9
5
0
1
2
3
4
6
7
8
9
The MMX-101 monitor module is an addressable module that is functionally and electrically
identical to an MMX-1 monitor module (Style B circuits only), but offered in a smaller pack-
age for mounting directly in the electrical box of the contact-type device being monitored.
NFPA Style B Initiating Device Circuit
Terminate with an A2143-00 ELR (N-ELR in Canada).
MMX-1 and MMX-101 Monitor Module Technical Notes
1.
Initiating device circuit is supervised and current-limited to 210 microamps @ 24 VDC
(nominal).
2.
Initiating device circuit provides the following services (do not mix):
a)
Fire alarm service
b)
Automatic/manual waterflow alarm service with normally open contact devices
c)
Sprinkler supervision with normally open contact devices
3.
Maximum loop resistance due to wiring is 65 ohms.
Technical Manuals Online! - http://www.tech-man.com
Содержание AIM-200
Страница 2: ...2 Document 15949 Rev E 4 12 95 P N 15949 E Technical Manuals Online http www tech man com...
Страница 57: ...57 Document 15949 Rev E 4 12 95 P N 15949 E NOTES Technical Manuals Online http www tech man com...
Страница 58: ...58 Document 15949 Rev E 4 12 95 P N 15949 E NOTES Technical Manuals Online http www tech man com...
Страница 59: ...59 Document 15949 Rev E 4 12 95 P N 15949 E Technical Manuals Online http www tech man com...
Страница 60: ...60 Document 15949 Rev E 4 12 95 P N 15949 E BACK COVER Technical Manuals Online http www tech man com...