Doc. No:
D000100-INS-03, Rev D
Page 32 of 36
2
Connect the negative (-) cable
to battery block no 1, using M8
bolt and washer. Tighten to a
torque of 8Nm.
Figure 21 Connecting Negative
Cable
3
Connect the positive (+) cable
to battery block no 4 using M8
bolt and washer. Tighten to a
torque of 8 Nm.
The battery string positive cable
is not to be connected until all
connections to the CF have
been made.
Figure 22 Connecting Positive
Cable
4 Fit the pole protections.
Figure 23 Fitting Pole Protections