Doc. No:
D000100-INS-03, Rev D
Page 22 of 36
8
R
ECONFIGURING THE
E
XTERNAL
A
LARM
The controller is by factory default configured for individual alarms on
alarm outputs K1, K2, and K3. The controller also supports sending
summary alarm, NO or NC on alarm output K1.
Do as follows to reconfigure from individual to summary alarm:
1.
Disconnect power.
2.
Remove the CCU Front Plate.
a)
Loosen the five screws holding the CCU Front Plate, No 1 in the
figure below.
b)
Lean the CCU Front Plate forward, No 2 in the figure below.
Figure 7
Removing CCU Front Plate
3.
Locate configuration connector P16.
4.
Remove the configuration jumper as shown in Figure 8.