Connecting Battery Cables
Warning!
To avoid battery thermal runaway, the batteries must be connected to an
external PSU with thermal compensated charging. Furthermore, the
external PSU must shut off the battery system if the temperature
reaches 50°C inside the cabinet.
Note:
Improper handling when connecting batteries can result in short-
circuiting, which can result in serious injury due to high energy
levels. Exercise the necessary care when working with batteries.
Secure that not connected cable lugs are insulated.
Connect the battery blocks into a battery string according to the following:
1
Attach the three inter-block
connectors between battery
block no 1 and no 2, between
battery block no 2 and no 3 and
between battery block no 3 and
no 4, using M8 bolts and
washers. Tighten to a torque of
8Nm.
Figure 20 Attach Inter-block
Connectors