Page 32 RHC 8000 EN April 2019 D301207 Issue C
8.2 Ignition Controller Lockout Indicator Light Repeatedly Comes “On”
WARNING
Fault finding may only be carried out by appropriately qualified persons
no
yes
no
yes
no
no
yes
no
yes
yes
no
yes
no
no
no
Remove corrosion
& scale from flame
sensing rod & clean
ceramic insulation
Check electronic
ignition control
Place in normal
operation
Spark visible, still
no flame
Is there 230V
between terminals
13 & 2 of the
electronic ignition
control
Check electronic
ignition control
Check flame signal. Is
it greater than 1,0
micro Amps?
Check flame signal
using micro amp
meter. Is signal greater
than 1,0 micro Amps?
Correct polarity
Check electronic
ignition control
Does the inlet gas
pressure agree with
the data badge
Is polarity of mains
correct?
Wait 15" and press
reset button
Is a spark visible ?
check
electronic
ignition
control
check multi
functional
gas valve
Correct the gas
supply pressure
During 5" trial for
ignition is a spark
visible?
Check spark gap
and ceramic &
check spark wire
& connector
During 5" trial for
ignition is a flame
visible in this view
port?