Page No 8 of 52 Reznor, Photon, Installation Manual, EN 2021-04, D301310 Iss 0
TD
Technical Data
Model
PHOTON
10
20
25
35
45
55
65
70
100
120
Combustion Air and Flue Type
1
B23 / B53 / C13 / C33 / C53
Heat Input High Fire (HS)
2
kW
11.28
22.50
32.40
38.80
51.60
64.80
77.40
86.00
119.00 144.00
Heat Input Low Fire (HS)
2
kW
5.64
10.85
17.82
19.20
26.83
29.16
42.57
47.30
59.50
73.80
Heat Input High Fire (HI)
3
kW
10.16
20.27
29.19
34.95
46.49
58.38
69.73
77.48
107.21 129.73
Heat Input Low Fire (HI)
3
kW
5.08
9.77
16.05
17.30
24.17
26.27
38.35
42.61
53.60
66.49
Heat Output High Fire
kW
9.34
18.39
26.54
31.68
42.24
53.46
63.59
71.25
97.87
120.16
Heat Output Low Fire
kW
4.90
9.39
15.37
16.65
23.18
25.18
36.74
40.84
51.52
64.21
Gas Consumption High Fire (HS) G20
4
m
3
/h
1.07
2.14
3.08
3.69
4.91
6.17
7.37
8.19
11.33
13.71
Gas Consumption Low Fire (HS) G20
4
m
3
/h
0.54
1.03
1.70
1.83
2.56
2.78
4.05
4.50
5.67
7.03
Gas Consumption High Fire (HS) G25
4
m
3
/h
1.25
2.49
3.59
4.30
5.71
7.17
8.57
9.52
13.18
15.94
Gas Consumption Low Fire (HS) G25
4
m
3
/h
0.62
1.20
1.97
2.13
2.97
3.23
4.71
5.24
6.59
8.17
Gas Consumption High Fire (HS) G25.3
4
m
3
/h
1.22
2.44
3.51
4.20
5.59
7.02
8.39
9.32
12.89
15.60
Gas Consumption Low Fire (HS) G25.3
4
m
3
/h
0.61
1.18
1.93
2.08
2.91
3.16
4.61
5.13
6.45
8.00
Thermal Efficiency High Fire G20 (NCV)
%
91.9
90.7
90.9
90.6
90.9
91.6
91.2
92.0
91.3
92.6
Thermal Efficiency High Fire G25 (NCV)
%
91.0
91.0
90.5
90.7
90.8
91.5
91.0
92.1
90.8
92.1
Thermal Efficiency High Fire G25.3 (NCV)
%
90.6
90.7
90.7
90.5
90.8
91.4
91.1
91.8
90.9
91.8
Gas Connection
5
BSP
½"
¾"
1"
Flue and Combustion Air Connection
Collars (Indoor)
Ø mm
80
100
130
Maximum Flue Length
m
9.0
Airflow
m
3
/h
1223
2533
3035
4120
4562
5877
7125
8681
10350
17552
Motor Speed
rpm
1443
1436
934
1328
1320
925
1335
1384
1332
1206
Temperature Rise at Maximum Airflow
K
23
22
26
23
28
27
27
24
28
20
Horizontal Throw
m
10
16
26
27
26
32
32
36
36
36
Noise Level
6
dBA
46
48
49
51
51
51
56
59
60
62
Minimum mounting height
7
m
2.5
Total Electrical Rating
W
145
150
256
550
550
690
820
1000
1040
1900
Electrical Connection
230V / 1N / 50Hz
Protection Grade
IP
IP20
Net weight
Kg
43
63
58
89
99
121
122
135
168
258
1
.
Gas appliance classifications for approved venting methods are based on EN 1749:2020
2
.
Refers to gross calorific value of fuel
3.
Refers to net calorific value of fuel
4
.
Natural gas: G20 Hs 37.78 MJ/m³, G25 Hs 32.49 MJ/m³, G25.3 Hs 33.2 MJ/m³ @ 15°C and 1013.25 mbar
5
.
There is a difference between the gas connection diameter and the diameter of the supply line. Always use the most adequate diameter of the supply
line to minimize the pressure drop through the gas pipes. If necessary, reduce the diameter of the supply line at the inlet of the unit
6
.
Sound pressure measured in dB(A) : at 5m distance of the heater with A=160m² & Q=2
7
.
Minimum height from floor to bottom surface of heater for safe use of heater. Positioning of unit heaters for proper performance is application
dependent. Operation is affected by other air moving equipment in the space, obstructions to the airflow, draughts and/or close proximity to doors
or windows, etc. Care should be taken to avoid mounting the heaters higher than these recommendations, unless downturn nozzle options are used,
as significant stratification may occur resulting in poor floor coverage and higher energy losses through the roof structure. Isothermal cond/-
20°C ambient air temperature, discharge louvres zero deflection, v = 0.5m/s. The air throw will be influenced by the height of the building, mounting
height of the unit, ambient temperature & adjustment of the louvres.