Nortek REZNOR PHOTON 10 Скачать руководство пользователя страница 4

Page No 4 of 52 Reznor, Photon, Installation Manual,  EN 2021-04, D301310 Iss 0

G

PHOTON Range 

General product information

PHOTON is the latest generation of gas 
fired unit heaters, CE and UKCA certified to 
EN17082 for use in non domestic installations. 

All models and sizes are available for use with 
natural gas (G20, G25 or G25.3). The type of 
gas, the input rate and the electrical supply 
requirement is shown on the heater rating 
plate. Check the rating plate to determine 
if the heater is appropriate for the intended 
installation.

This installation manual is shipped with the 
unit. Verify that the literature is correct for 
the model being installed. If the manual is 
incorrect for the heater, contact the supplier 
before beginning installation.

The instructions in this manual apply only to 
the models listed.

Installation should be carried out by a 
suitably qualified installer in accordance with 
these instructions and the current rules and 
regulations in force. The installer is responsible 
for the safe installation of the heater.

Using this manual 

The symbols for ‘Caution’ and ‘Warning’ are 
used to highlight certain points throughout 
this manual.

Caution is used when failure 
to follow or implement the 
instruction(s) can lead to 
premature failure or damage to   
the heater or its component parts.

Warning is used when failure 
to heed or implement the 
instruction(s) can lead to not only 
component damage, but also to a  
hazardous situation being created 
where there is a risk of personal 
injury.

Warranty 

This equipment comes as standard with a 
manufacturers two year warranty (2 years 
parts, 1 year labour) unless agreed otherwise 
at the time of order. The warranty is void if: 

1.  The installation is not in accordance with 

these instructions.

2.  Wiring is not in accordance with the 

diagram furnished with the heater.

3.  The unit is installed without proper 

clearances wherever clearances are 
required regardless of the material being 
combustible.

4.  The unit is installed without proper 

ventilation and air for combustion.

5.  The equipment is used in atmospheres 

containing flammable vapours or 
chlorinated or halogenated hydrocarbons 
or any contaminant (silicon, aluminium 
oxide, etc.).

6.  The unit has not been serviced and 

maintained in accordance with the 
information contained within these 
instructions.

7.  An appliance is connected to a duct system 

or the air delivery system is modified in any 
way.

Ignoring the warning and caution 
notices and the advice from the 
manufacturer on installation, 
commissioning, servicing or use, 
will jeopardise any applicable 
warranty. This could also 
compromise the safe and efficient 
running of the appliance itself and 
thereby constitute a hazard.

The electrical isolator should only 
be used for maintenance purposes 
or in an emergency. It should 
not be used for closing down the 
main burner as it switches off the 
fan prematurely and may damage 
the heat exchanger, invalidating 
the warranty.

Содержание REZNOR PHOTON 10

Страница 1: ...roperty damage injury or death All work must be carried out by appropriately qualified persons The manufacturer does not take any responsibility in the event of non observance of the regulations conce...

Страница 2: ......

Страница 3: ...ce and Servicing MS Model 10 20 component layout 29 Model 25 70 component layout 30 Model 100 component layout 31 Model 120 component layout 32 Maintenance schedule 33 Heat exchanger maintenance 33 Re...

Страница 4: ...tion s can lead to not only component damage but also to a hazardous situation being created where there is a risk of personal injury Warranty This equipment comes as standard with a manufacturers two...

Страница 5: ...carefully read these instructions and follow the processes explained by the manufacturer These instructions are only valid for appliances designed to operate in Europe If the country code and gas cate...

Страница 6: ...nce before shutting off the electrical supply Gas fired appliances are not designed for use in hazardous atmospheres containing flammable vapours or combustible dust in atmospheres containing chlorina...

Страница 7: ...with the installation requirements of your unit Check if the local distribution conditions of electricity supply type of gas and pressure of the appliance are compatible with the data plate The appli...

Страница 8: ...5877 7125 8681 10350 17552 Motor Speed rpm 1443 1436 934 1328 1320 925 1335 1384 1332 1206 Temperature Rise at Maximum Airflow K 23 22 26 23 28 27 27 24 28 20 Horizontal Throw m 10 16 26 27 26 32 32 3...

Страница 9: ...Manual EN 2021 04 D301310 Iss 0 Page No 9 of 52 TD Dimension Diagrams Front View Photon 10 100 B A Front View Photon 120 A B A Plan View Photon 10 120 K L Side View Photon 10 70 C Side View Photon 10...

Страница 10: ...Page No 10 of 52 Reznor Photon Installation Manual EN 2021 04 D301310 Iss 0 TD Rear View Photon 10 70 D E G J H F Rear View Photon 100 Rear View Photon 120 H F H F E G J E G J D D...

Страница 11: ...5 385 385 492 583 616 760 895 Top Suspension Centres K mm 350 350 600 600 600 600 600 600 600 600 Top Suspension Centres L mm 413 413 623 623 623 623 623 623 623 623 Combustion air flue and gas connec...

Страница 12: ...th extra units provided to discharge air in toward the centre of the area For optimum results heaters are best used in conjunction with recirculating air fans suspended at high level Contact the manuf...

Страница 13: ...B forced draught heater where the combustion air is taken from the room space the heater is installed in and which requires only a flue pipe exhausting to outdoors Type B23 or B53 only All products of...

Страница 14: ...er is installed Single wall seamless aluminium or stainless steel flue pipes are required All joints must be sealed to prevent the products of combustion from leaking into the building If the flue pas...

Страница 15: ...ustible element of the building it must be enclosed by a sleeve of non combustible material and separated from the sleeve by a minimum of 25 mm air break The temperature of any combustible material ne...

Страница 16: ...7 Mass Flow Rate Flue Gases High Fire G25 kg h 9 12 15 45 25 47 29 01 39 73 55 64 55 72 62 18 97 41 126 10 Mass Flow Rate Flue Gases High Fire G25 3 kg h 9 61 15 38 24 84 28 29 30 73 52 83 57 64 64 86...

Страница 17: ...that is to be tested Cap or plug the supply line All sealing products must be resistant to the action of liquefied petroleum gas or any other chemical constituents of the gas being supplied Install a...

Страница 18: ...als L and N remain live at all times even when the unit is switched off to ensure correct operation of the unit and to let the fan operate independent of the heating control Never incorporate controls...

Страница 19: ...ngle thermostat or control panel unless a properly wired relay is fitted Follow the instructions supplied with such panels The location of the room thermostat or sensor is very important It should not...

Страница 20: ...s Notes 1 Link wires MUST be fitted where shown solid 2 Terminals shown may not be in numerical order Unused terminals may not be shown at all 3 1 Phase supply cable 2 5mm minimum 4 Controls cables 0...

Страница 21: ...Check that no combustibles are near to the unit Requirements are in the location and installation section of this manual Check vent system to be sure that it is installed according to the combustion...

Страница 22: ...o adjust the throttle use a 4mm hex key on the screw located on the venturi Rotate counter clockwise to increase CO2 Rotate clockwise to decrease CO2 To adjust the offset use a T40 Torx key to remove...

Страница 23: ...o the commissioning section for more details Commissioning checks Commissioning requires the use of a CO CO2 flue gas analyser with an inaccuracy 0 1 and two pressure gauges For measuring gas pressure...

Страница 24: ...eeded to obtain nominal low fire CO2 0 1 CO2 Return heater to high fire 10V and recheck high fire CO2 value If necessary make any final adjustments to the throttle Disconnect pressure gauges and tight...

Страница 25: ...fset Pressure G25 Pa 32 55 24 34 26 72 105 134 66 N A CO2 at High Fire Throttle G25 3 8 60 8 70 8 70 8 70 8 70 8 60 8 70 8 70 8 60 8 60 CO G25 3 ppm 50 ppm Throttle Turns from G20 1 0 out 1 0 out 1 5...

Страница 26: ...mperature has been reached At this point the burner rate will adjust according to the heat demand from the thermostat When set point temperature is reached the burner will turn off and the appliance w...

Страница 27: ...eset the thermostat To turn off the heater for a prolonged period turn the room thermostat to lowest setting and turn off the gas supply to the appliance Switch off electrical supply to the air heater...

Страница 28: ...ior to activation of the ignition device Safety time The safety time is the delay between the gas valve being energised and the flame sensor checking for the presence of a flame This is a period of 4...

Страница 29: ...aintenance Photon 10 20 component layout LED status light Reset switch and burner lockout Combustion fan LC3 limit control bracket and reset Modulating gas valve Controls bracket Axial fan LC1 limit c...

Страница 30: ...4 D3013105 Iss 0 MS Photon 25 70 component layout Combustion fan LC1 and LC3 limit control bracket Modulating gas valve Controls bracket with LC3 reset Axial fan Gas connection Burner Venturi LED stat...

Страница 31: ...No 31 of 52 MS Photon 100 component layout Combustion fan LC1 and LC3 limit control bracket Modulating gas valve Controls bracket with LC3 reset Axial fan x2 Gas connection LED status light Reset swi...

Страница 32: ...Iss 0 MS Photon 120 component layout Combustion fan LC3 limit control bracket Modulating gas valve Controls bracket with 2 off LC3 reset Gas connection LED status light Reset switch and burner lockou...

Страница 33: ...ocedures should be carried out at least once each year Clean all dirt lint and grease from the fan and motor Check the heat exchanger internally and externally for evidence of physical damage Check th...

Страница 34: ...be first removed Photon 10 70 gas valve fixing screws Photon 100 remove combustion fan to reveal gas valve fixing screws Photon 100 gas valve fixing screws 3 off Fixing screws 6 off Fixing screws 4 o...

Страница 35: ...crews models 10 70 and 6 screws models100 120 as per the photographs shown under gas valve replacement Photon 10 70 venturi Photon 100 venturi O ring Throttle Screw Fixing Screws Throttle Screw Photon...

Страница 36: ...transferred across to the new fan 5 To remove unscrew the 8mm nuts 6 Attach new gasket to fan outlet flange all models and fit mounting plate models 10 70 only 7 Refit remaining items in reverse order...

Страница 37: ...available from the appliance manufacturer 7 With the burner removed the integrity of the combustion chamber and tube insulation can be verified It is normal for small superficial cracks to be present...

Страница 38: ...n the chamber insulation and tube inserts Up to three tube insert spacer gaskets may be needed per tube insert 15 Refit burner probes Check condition of probe bracket gasket and replace if necessary 1...

Страница 39: ...ll need to be replaced Probe mounting bracket fittings x2 Withdraw probe mounting bracket from chamber Flame probe Length of probe 46 55mm overall 32 95mm to angle 13 79 mm angle to tip Tip deflection...

Страница 40: ...ce one or both thermostats as needed Ensure sensor is pushed up to the return at the end of the bracket and secured in place with the retaining clips Replace clips if necessary Ensure thermostat is he...

Страница 41: ...board 1 Disconnect all electrical connections 2 Pinch circuit board retention clips to release 3 Refit in reverse order 4 Follow start up and commissioning procedure Replacement of fan relay 1 Disconn...

Страница 42: ...ts seams concentric adapters and the flue terminal cap Replace any defective or heavily corroded parts Fan motor and fan maintenance The fan motor is equipped with thermal overload protection of the a...

Страница 43: ...5 Throttle positioning see commissioning data table 6 Correct program key fitted 7 Gas valve 8 Integrity of appliance ground connection 9 Probe leads connected integrity 10 Flame sensor probe clean 11...

Страница 44: ...be corroded 3 Flame signal min 1 0 A 4 Flame sensor probe bent 5 LC1 safety thermostat temperature not exceeding 95 C 6 Air inlet flue pipe for obstructions 7 Integrity of chamber insulation YES YES Y...

Страница 45: ...sket o ring 1031374 120 Combustion fan Kit 10 25 1037269 10 25 Combustion fan Kit 35 70 1037270 35 70 Combustion fan Kit 100 1037271 100 Combustion fan Kit 120 1037272 120 Burner face insulation burne...

Страница 46: ...ial fan assembly 35 45 1030858 35 45 Axial fan assembly 55 01 27011 01 55 Axial fan assembly 65 1030860 65 Axial fan assembly 70 120 1030812 70 120 Axial fan assembly 100 1030859 100 Axial fan cable g...

Страница 47: ...2 90 6 25 26 5 15 4 0 062 0 036 0 001 81 9 86 2 0 0 0 0 49 94 5 78 5 90 9 20 18 4 9 4 0 053 0 025 0 001 81 7 86 6 0 0 0 0 50 95 9 80 4 90 7 10 9 3 4 9 0 026 0 020 0 001 82 8 86 9 0 0 0 0 31 95 6 80 2...

Страница 48: ...1 90 7 25 26 4 15 3 0 062 0 036 0 001 81 6 86 0 0 0 0 0 58 64 5 78 2 90 5 20 18 4 9 4 0 053 0 025 0 001 82 0 86 5 0 0 0 0 60 95 9 80 4 91 0 10 9 2 4 9 0 026 0 020 0 001 81 9 81 6 0 0 0 0 29 95 6 79 4...

Страница 49: ...0 0 90 5 25 26 5 15 3 0 062 0 036 0 001 81 7 86 1 0 0 0 0 55 94 5 78 3 90 7 20 18 4 9 4 0 053 0 025 0 001 81 7 86 3 0 0 0 0 58 95 9 80 2 90 7 10 9 2 4 9 0 026 0 020 0 001 81 6 86 0 0 0 0 0 29 95 6 79...

Страница 50: ...Notes...

Страница 51: ...Notes...

Страница 52: ...9707 reznorsales nortek com www reznor eu Nortek Global HVAC is a registered trademark of Nortek Global HVAC limited Because of the continuous product innovation Nortek Global HVAC reserves the right...

Отзывы: