Page No 44 of 52 Reznor, Photon, Installation Manual, EN 2021-04, D301310 Iss 0
FF
Does the
burner remain running
after several
minutes?
NO
YES
Does the burner attempt
to relight?
YES
CHECK: -
1. LED status light flash codes.
2. LC3 safety thermostat reset switch.
3. LC3 safety thermostat temperature not exceeding 96°C (71°C for models 10 and 20)
4. Lockout reset switch.
5. Heat demand still present.
CHECK: -
1. Throttle positioning – see commissioning data table.
2. Flame sensor probe corroded.
3. Flame signal (min. 1.0µA).
4. Flame sensor probe bent.
5. LC1 safety thermostat temperature not exceeding 95°C.
6. Air inlet / flue pipe for obstructions.
7. Integrity of chamber insulation.
YES
YES
YES
NO
Page 2
END
If the heater still fails to operate
correctly, contact your local
representative.
NOTE: presence
of a flame is
indicated by
the green lamp
illuminating.
Does the
circulation fan
start after 30
seconds?
NO
CHECK: -
1. Fan relay coil voltage 230V / 50Hz after 30 seconds from burner ignition.
2. Fan relay.
3. Ignition controller.
4. Voltage supply to circulation fan.
5. Integrity of wiring connections.
6. Fan, including the free movement of the fan wheel.
YES
YES