![Nortek REZNOR PHOTON 10 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/nortek/reznor-photon-10/reznor-photon-10_installation-commissioning-and-servicing-manual_1706007011.webp)
Reznor, Photon, Installation Manual, EN 2021-04, D301310 Iss 0 Page No 11 of 52
TD
Unit Dimensions
Dimensions
Model
PHOTON
10
20
25
35
45
55
65
70
100
120
Unit Width A
mm
700
700
970
970
970
970
970
970
1010
1010
Unit Height B
mm
380
660
520
520
520
733
733
800
1080
1360
Overall Length C
mm
810
840
1160
1180
1180
1160
1190
1160
1140
1160
Side to Gas Connection Centre D
mm
73
96
180
174
179
158
154
154
163
101
Bottom to Gas Connection Centre E
mm
198
257
124
134
134
215
215
224
236
213
Side to Flue Connection Centre F
mm
185
185
204
204
204
204
204
204
244
244
Bottom to Flue Connection Centre G
mm
186
326
260
260
260
367
367
400
540
680
Side to Air Inlet Centre H
mm
109
109
141
141
141
141
141
141
197
177
Bottom to Air Inlet Centre J
mm
291
431
385
385
385
492
583
616
760
895
Top Suspension Centres K
mm
350
350
600
600
600
600
600
600
600
600
Top Suspension Centres L
mm
413
413
623
623
623
623
623
623
623
623
Combustion air, flue and gas connections
Connection Sizes
Model
PHOTON
10
20
25
35
45
55
65
70
100
120
Gas connection diameter
BSP
½"
¾"
1"
Combustion air inlet diameter
mm
80
100
130
Flue diameter
mm
80
100
130
Maximum Flue Length
m
9.0
Clearance distances
Clearance Distances
Model
PHOTON
10
20
25
35
45
55
65
70
100
120
Top clearance
mm
50
50
50
100
100
100
100
100
100
100
Rear clearance
mm
450
450
450
450
450
450
450
450
450
450
Bottom clearance *
mm
50
50
50
100
100
100
100
100
100
100
Side clearance
mm
50
50
50
100
100
100
100
100
100
100
Service panel clearance
mm
850
850
850
850
850
850
850
850
850
850
* Heaters can be base mounted on suitable non combustible supports.
A minimum 150mm clearance distance MUST be maintained at all points around
the entire flue system
.
Dimension Tables