background image

7

  IMPORTANT: If the webbing is not removed, the 

condensate will not drain properly and ceiling damage 

may occur.

 

NOTE:

 It is recommended that the suction line be insulated 

up to the coil inside of the cabinet.

7. Insert the plug (from horizontal drain pan) into the open 

and unused drain hole in the drain pan at the bottom of 

the unit to block bypass air.

8. Remove the corresponding drain line knockout from the 

coil access door to allow access to the horizontal drain.

9. Replace the door and attach the drain line.

Circuit Breaker Cover Installation

The air handler circuit breaker cover is designed to protect 

the breakers of an installed heater kit from debris and 

condensation.The cover attaches to the breaker recess 

of the air handler upper access door using a double-sided 

adhesive gasket. See 

Figure 5

The heater kit circuit breaker 

toggles are still accessible and can be switched with the 

cover in place.

•  2-breaker cover for 1.5, 2, 2.5, 3, 3.5 & 4 ton air handlers.
After the heater kit is properly installed, remove the appropriate 

knockouts in the upper air handler access door and follow 

these instructions to install the breaker cover:
1. Clean any oil, dirt, or insulation fibers from the recess area 

of the air handler access door. This step is important for 

ensuring the gasket adheres properly to the sheet metal 

door.

2. Remove release paper from one side of the gasket 

and attach to back side of the breaker cover. 

NOTE:

 For proper alignment, It is recommended to leave 

the center section of the gasket in place when attaching 

the gasket to the breaker cover. Remove the center section 

after the gasket is applied to the breaker cover.

3. Remove the release paper from the other side of the gasket 

and attach to the circuit breaker recess area.

4. Press firmly along all four sides of the cover to ensure 

gasket and cover are securely attached to the access door.

Refrigerant Line Connections

 WARNING:

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

The coil in the air handler is factory shipped with 

a nitrogen charge. Avoid direct face exposure 

or contact with valve when gas is escaping. 

Always ensure adequate ventilation is present 

during the depressurization process. Address 

any uncertainties before proceeding. Failure 

to comply with this warning could result in 

equipment damage, personal injury, or death.

•  The installer should make every effort to ensure the field 

installed refrigerant containing components of the system 

have been installed in accordance with these instructions 

and sound installation practices for reliable system 

operation and longevity.

•  The air handler coil does not contain a refrigerant charge. 

Refer to the installation instructions supplied with the 

outdoor unit for refrigerant charge information.

•  The  refrigerant piping to each air handler (or coil) should 

be of equal length and size. Run the copper pipes from 

condensing unit to a point equidistant between the air 

handlers (or coils). Place a tee in the lines at this point. After 

the tee (as close to the air handler as practical), reduce 

the pipe size to match the piping of the air handler or coil.

•  Always refer to the installation instructions supplied with 

the outdoor unit for piping requirements. The suction and 

liquid lines must be sized in accordance with the condensing 

unit specifications. See 

Figure 10 (page 14)

 for liquid and 

suction line locations.

• When connecting refrigerant linesets together, it is 

recommended that dry nitrogen be flowing through the 

joints during brazing. This will prevent internal oxidation 

and scaling from occurring.

• Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends in 

the tubing. It should be supported in a manner that prevents 

it from vibrating or abrading during system operation. Tubing 

should be kept clean of foreign debris during installation.

•  If precise forming of refrigerant lines is required, a copper 

tubing bender is recommended. Avoid sharp bends and 

contact of the refrigerant lines with metal surfaces.

•  Refrigerant lines should be wrapped with pressure sensitive 

neoprene or other suitable material where they pass against 

sharp sheet metal edges.

•  B64 Series air handlers are charged (with nitrogen) through 

service valves on the end of the liquid tube for each circuit. 
These must be removed before brazing the line sets.

Orifice Removal & Installation

The orifice installed in the air handler has been sized for use 

with the most popularly matched outdoor units. The orifice 

size as shipped from the factory is listed on the air handler 

rating plate. Perform steps 1 - 9 (

page 8

to confirm that the 

orifice size meets the requirements outlined in the outdoor 

unit installation manual.

Circuit Breaker

Cover

Circuit

Breakers

Recess

Air Handler A

ccess Door

Figure 5. 

Circuit Breaker Cover

Содержание B64BM Series

Страница 1: ...as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious inj...

Страница 2: ...10 Control Board 10 Twinning 10 Line Low Voltage Connections 11 Heater Kits 11 Electronic Air Cleaner EAC 11 STARTUP ADJUSTMENTS 11 Before You Start the Unit 11 Air Circulation 11 Running the Blower C...

Страница 3: ...s manual during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recomm...

Страница 4: ...ent Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationofthetot...

Страница 5: ...ance be sure to install all the needed gaskets and grommets around penetrations into the air handler such as for electrical wiring AIR HANDLER INSTALLATION B64 series air handlers are shipped ready fo...

Страница 6: ...Right Installations 1 Remove the coil access door Unscrew the line set tube close off plate from the front left cabinet rail 2 Slide the coil and drain pan assembly out of the unit 3 Remove the sheet...

Страница 7: ...ult in equipment damage personal injury or death The installer should make every effort to ensure the field installed refrigerant containing components of the system have been installed in accordance...

Страница 8: ...htenanadditional1 4turnusingtwowrenches The movement of the two lines will show how much the nut is tightened If a torque wrench is used tighten to 10 12 ft lbs or 14 16 Nm Connecting the Linesets The...

Страница 9: ...d tubing or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may result in condensation overflowing th...

Страница 10: ...plate Use UL listed conduit and conduit connectors for connecting the supply wires to the unit and for proper grounding Field supplied bushings for the power supply cables must be added to support and...

Страница 11: ...on is sized properly Verify filter is properly and securely installed IMPORTANT Before starting the unit install the initial charge on units that are factory shipped with a nitrogen holding charge 1 R...

Страница 12: ...locations are shown in Figure 11 page 15 If any component of the air handler must be replaced use only factory authorized replacement parts specified in the Replacement Parts List provided online WAR...

Страница 13: ...caution when preparing coils for field connections If repairs makeitnecessaryforevacuationandcharging it should only be attempted by qualified trained personnel thoroughly familiar with this equipmen...

Страница 14: ...11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A CABINET SIZE H W A DETAIL D A 43 5 16 14 3 16 12...

Страница 15: ...Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Upper Door Assembly Lower Door Assem...

Страница 16: ...s for maximum recommended external static pressure Table 4 B64BM Airflow Data With Horizontal Drain Pan DRY COIL ESP 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 18K A CABINET Low 760 722 676 622 561 492 414 330 M...

Страница 17: ...tly Blower off after 15 second delay W1 Y AUX HEAT ON 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 15 KW Stage...

Страница 18: ...R C E O Y Thermostat Typical Heat Pump with Standard Air Handler Heat Pump NOTE Jumper between W2 E is required when no OD T Stat is used W1 Y G R C Air Handler W1 Y G R C R C Y W2 O W2 NOTE See step...

Страница 19: ...19 LED 1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 14 Single Stage Control Board...

Страница 20: ...G RELAY RELAY Y L2 L1 EAC COOL HEAT W G R C R C L2 L1 7 6 5 4 3 2 1 1 COM 2 CAP 3 CAP 4 HI 5 MED 6 LOW 240 24 V 208 COM TRANSFORMER R C LOCATION OF T CONNECTOR MOTOR 3 SPEED 4 PIN PLUG 18 BLOWER LIMIT...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...t according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product Safety should always be the deciding factor when installin...

Отзывы: