background image

12

3-Speed Units

The blower speed is preset at the factory for operation at the 

same speed for heating and cooling, by using the jumping 

terminal on the blower motor and connecting it to the desired 

speed with both the red and black wires connected to the 

jumping terminal. 

NOTE:

 The control board is programmed 

with a 40 second off delay in the cooling mode for optimum 

system performance and efficiency.

 CAUTION:

To avoid personal injury or property damage, 

make sure the motor leads do not come into 

contact with any uninsulated metal components 

of the unit.

For optimum system performance and comfort, it may be 

necessary to change the factory set speed. See 

Table 4 and 

Table 5 (page 16)

 for airflow data. To change the blower speed:

1. Disconnect all electrical power to the unit and remove the 

upper door.

2. Remove the black and red wires from the blower motor 

jumping terminal. Discard the blower motor jumping 

terminal.

3. Connect the heating speed wire (red) and the cooling 

speed wire (black) to the desired blower speed marked 

on the terminal block of the blower motor.

•  Terminal 4 = Hi speed

•  Terminal 5 = Med speed
•  Terminal 6 = Low speed

4. Replace the upper door and secure it to the unit.
5. Restore power to the unit.
Before operation, the air handler must be configured to 

match the unit with the system, system options, and climatic 

conditions. During normal operation, the motor will gradually 

change speeds during start-up, shut down, when thermostat 

inputs change, and when the duct static pressure changes 

(vents closed or opened, filter clogging, etc.). The air handler 
is configured by setting the selector switches and removing 

jumper connectors.

TROUBLESHOOTING

If the air handler fails to operate, check the following:

•  Is the electric turned on?

•  Is the thermostat operating properly?

•  Are the blower compartment door(s) in place?

•  Is the air handler disconnect closed?

•  Has the circuit breaker tripped or the control board fuse 

burned open?

•  Are any manual reset switches open?

•  Is the filter dirty or plugged?

•  Is the LED on both control boards constantly ON? If not, 

refer to 

Table 2

 to determine fault condition.

UNIT MAINTENANCE

Proper maintenance is most important to achieve the best 

performance from a air handler. Some of the components 

and their locations are shown in 

Figure 11 (page 15)

If 

any component of the air handler must be replaced, use 

only factory authorized replacement parts specified in the 

Replacement Parts List provided online.

 WARNING:

ELECTRICAL SHOCK, FIRE OR

EXPLOSION HAZARD

Failure to follow safety warnings exactly could 

result in serious injury or property damage.
Improper servicing could result in dangerous 

operation, serious injury, death or property 

damage.
•  Before servicing, disconnect all electrical power 

to the indoor blower.

•  When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

•  These maintenance instructions are primarily intended 

to assist qualified technicians experienced in the proper 

maintenance and operation of this appliance.

•  Always reinstall the doors on the air handler after servicing 

or cleaning/changing the filters. 

Do not operate the air 

handler without all doors and covers in place.

• Verify that the thermostat is properly installed and is 

not being affected by drafts or heat from lamps or other 

appliances.

•  To achieve the best performance and minimize equipment 

failure, it is recommended that a yearly maintenance 

checkup be performed. At a minimum, this check should 

include the following items:

Air Filter(s)

 - B64 Series Air Handlers are not supplied with 

a air filter when shipped from the factory. It is recommended 

that the filter be cleaned or replaced every 4 to 6 months at 

a minimum. Newly built or recently renovated homes may 

require more frequent changing until the construction dust 

has minimized. Filter sizes shown in 

Table 3

 are available 

at most local retailers.

 WARNING:

Never operate the air handler without a filter in 

place. Dust and lint in the return air can build 

up on internal components, resulting in loss of 

efficiency, equipment damage, and possible fire.

Filters designed to remove smaller particles such as pollen, 

may require additional maintenance.

Blower Compartment

 - Dirt and lint can create excessive 

loads on the motor resulting in higher than normal operating 

temperatures and shortened service life. It is recommended 

that the blower compartment be cleaned of dirt or lint that 

may have accumulated in the compartment or on the blower 

and motor as part of the annual inspection.

RED LED (AN2)

DIAGNOSTIC

OFF

Control Fault (No Power)

Flash

Blower Fault

ON

Normal Operation

Table 2. 

Air Handler Control Board Fault Conditions

Содержание B64BM Series

Страница 1: ...as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious inj...

Страница 2: ...10 Control Board 10 Twinning 10 Line Low Voltage Connections 11 Heater Kits 11 Electronic Air Cleaner EAC 11 STARTUP ADJUSTMENTS 11 Before You Start the Unit 11 Air Circulation 11 Running the Blower C...

Страница 3: ...s manual during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recomm...

Страница 4: ...ent Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationofthetot...

Страница 5: ...ance be sure to install all the needed gaskets and grommets around penetrations into the air handler such as for electrical wiring AIR HANDLER INSTALLATION B64 series air handlers are shipped ready fo...

Страница 6: ...Right Installations 1 Remove the coil access door Unscrew the line set tube close off plate from the front left cabinet rail 2 Slide the coil and drain pan assembly out of the unit 3 Remove the sheet...

Страница 7: ...ult in equipment damage personal injury or death The installer should make every effort to ensure the field installed refrigerant containing components of the system have been installed in accordance...

Страница 8: ...htenanadditional1 4turnusingtwowrenches The movement of the two lines will show how much the nut is tightened If a torque wrench is used tighten to 10 12 ft lbs or 14 16 Nm Connecting the Linesets The...

Страница 9: ...d tubing or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may result in condensation overflowing th...

Страница 10: ...plate Use UL listed conduit and conduit connectors for connecting the supply wires to the unit and for proper grounding Field supplied bushings for the power supply cables must be added to support and...

Страница 11: ...on is sized properly Verify filter is properly and securely installed IMPORTANT Before starting the unit install the initial charge on units that are factory shipped with a nitrogen holding charge 1 R...

Страница 12: ...locations are shown in Figure 11 page 15 If any component of the air handler must be replaced use only factory authorized replacement parts specified in the Replacement Parts List provided online WAR...

Страница 13: ...caution when preparing coils for field connections If repairs makeitnecessaryforevacuationandcharging it should only be attempted by qualified trained personnel thoroughly familiar with this equipmen...

Страница 14: ...11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A CABINET SIZE H W A DETAIL D A 43 5 16 14 3 16 12...

Страница 15: ...Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Upper Door Assembly Lower Door Assem...

Страница 16: ...s for maximum recommended external static pressure Table 4 B64BM Airflow Data With Horizontal Drain Pan DRY COIL ESP 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 18K A CABINET Low 760 722 676 622 561 492 414 330 M...

Страница 17: ...tly Blower off after 15 second delay W1 Y AUX HEAT ON 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 15 KW Stage...

Страница 18: ...R C E O Y Thermostat Typical Heat Pump with Standard Air Handler Heat Pump NOTE Jumper between W2 E is required when no OD T Stat is used W1 Y G R C Air Handler W1 Y G R C R C Y W2 O W2 NOTE See step...

Страница 19: ...19 LED 1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 14 Single Stage Control Board...

Страница 20: ...G RELAY RELAY Y L2 L1 EAC COOL HEAT W G R C R C L2 L1 7 6 5 4 3 2 1 1 COM 2 CAP 3 CAP 4 HI 5 MED 6 LOW 240 24 V 208 COM TRANSFORMER R C LOCATION OF T CONNECTOR MOTOR 3 SPEED 4 PIN PLUG 18 BLOWER LIMIT...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...t according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product Safety should always be the deciding factor when installin...

Отзывы: